Lightning Fast Orders!
Call Now To Place a Quick Order
Call an Expert-Fast Response
Call 1-866-595-9616
KMParts.com is "THE" source for industrial automation control components
Eaton
EASY-E4-UC-16RE1
Expansion Unit
Eaton
EASY-E4-UC-16RE1
Expansion Unit
Eaton
EASY-E4-UC-16RE1
Expansion Unit
Description:
I/O expansion, Supply voltage: 12/24 V DC, 24 V AC, Can be used via easyConnect, Mounting position: Vertical or horizontal, Protection type (IEC/EN 60529, EN50178, VBG 4): IP20, Standards: EN 61000-6-2, EN 61000-6-3, IEC 60068-2-6, IEC 60068-2-27, IEC 60068-2-30, IEC 61131-2, EN 61010, EN 50178, cULus per UL 61010, CSA C22.2 No.61010
EASY-E4-UC-16RE1
Technical Specifications
Main Specifications
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Product range | Control relays easyE4 |
Subrange | easyE4 digital input/output enhancements |
Basic function | easyE4 extensions |
Description | Input/output extension for easyE4 control relay Expandable with the easyE4 series of digital input/output expansions with easy-E4-CONNECT1 connector (Item Y7-197225) Rated operating voltage 12V DC, 24V DC or 24V AC Digital inputs: 8 Digital outputs: 8 relays Screw terminals |
Inputs expansion (number) | digital: 8 |
Display | with diagnostic LED |
Software | EASYSOFT-SWLIC/easySoft 7 |
Supply voltage | 12/24 V DC 24 V AC |
For use with | easyE4 |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Screw terminals Solid | 0.2 - 4 mm2 |
Screw terminals flexible | 0.2 - 2.5 mm2 |
Screw terminals Solid or flexible conductor, with ferrule | 0,2 - 2,5 mm2 |
Screw terminals Solid or stranded | 22 - 12 AWG |
Screw terminals Standard screwdriver | 0.8 x 3.5 mm |
Screw terminals Tightening torque | 0.5 - 0.7 Nm |
Screw terminals Stripping length | 6.5 mm |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Operating ambient temperature | -25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C |
Condensation | Take appropriate measures to prevent condensation |
Storage [ϑ] | -40 - +70 °C |
relative humidity | in accordance with IEC 60068-2-30, IEC 60068-2-78 5 - 95 % |
Air pressure (operation) | 795 - 1080 hPa |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Protection type (IEC/EN 60529, EN50178, VBG 4) | IP20 |
Vibrations | In accordance with IEC 60068-2-6 constant amplitude 0.15 mm: 10 - 57 constant acceleration 2 g: 57 - 150 Hz |
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms | 18 Impacts |
Drop to IEC/EN 60068-2-31 [Drop height] | 50 mm |
Free fall, packaged (IEC/EN 60068-2-32) | 0.3 m |
Mounting position | Vertical or horizontal |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Overvoltage category/pollution degree | III/2 |
Electrostatic discharge (ESD) applied standard | nach IEC/EN 61000-4-2 |
Electrostatic discharge (ESD) Air discharge | 8 kV |
Electrostatic discharge (ESD) Contact discharge | 6 kV |
Electromagnetic fields (RFI) to IEC EN 61000-4-3 | 0.08 - 1.0 GHz: 10 1.4 - 2 GHz: 3 2.0 - 2.7 GHz: 1 V/m |
Radio interference suppression | EN 61000-6-3 Class B |
Burst | according to IEC/EN 61000-4-4 Supply cables: 2 Signal cables: 2 kV |
power pulses (Surge) | according to IEC/EN 61000-4-5 1 kV (supply cables, symmetrical) 2 kV (supply cables, asymmetrical) |
Immunity to line-conducted interference to (IEC/EN 61000-4-6) | 10 V |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Clearance in air and creepage distances | nach EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 |
Insulation resistance | in accordance with EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Rated operational voltage [Ue] | 12/24 DC (-15/+20%) 24 AC (-15/+10%) V |
Permissible range [Ue] | 10.2 - 28.8 V DC 20.4 - 26.4 V AC |
Residual ripple | ≦ 5 % |
Protection against polarity reversal | yes |
Frequency | 50/60 (± 5%) Hz |
Input current | max. 200 mA at 12 V DC max. 125 mA at 24 V DC |
Voltage dips | ≤ 20 ms at 24 V AC 10 ms at 24 V DC 1 ms at 12 V DC ms |
Fuse | ≧ 1A (T) A |
Heat dissipation at 24 V DC | 3 W |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Number | 8 |
Potential isolation | from power supply: no between inputs: no from the outputs: yes to base unit: yes to expansion devices: yes |
Rated operational voltage [Ue] | 12 V DC |
Input voltage | Condition 0: ≦ 5 (I1 - I8) Condition 1: ≧ 8 (I1 - I8) V DC |
Input current at signal 1 | 1.75 mA (I1 - I8) mA |
Deceleration time | type 0.2 (0 -> 1) type 0.15 (1 -> 0) ms |
Cable length | 100 (unshielded) m |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Number | 8 |
Potential isolation | from power supply: no between inputs: no from the outputs: yes to base unit: yes to expansion devices: yes |
Rated operational voltage [Ue] | 24 V DC |
Input voltage | Signal 0: ≦ 5 (I1 - I8) Condition 1: ≧ 15 (I1 - I8) V DC |
Input current at signal 1 | 3.3 (I5 - I8) mA |
Deceleration time | type 0.1 (0 -> 1) type 0.2 (1 -> 0) ms |
Cable length | 100 (unshielded) m |
Description | EASY-E4-AC-12RCX1 Expansion Unit |
---|---|
Number | 8 |
Potential isolation | from power supply: no between inputs: no from the outputs: yes to base unit: yes to expansion devices: yes |
Rated operational voltage [Ue] | 24 V AC |
Input voltage (AC = sinusoidal) [Ue] | Status 0: ≦ 5 (I1 - I8) Condition 1: ≧ 14 (I1 - I8) V |
Rated frequency | 50/60 Hz |
Input current at signal 1 | I5 - I8: 3.5 (at 24 VAC/DC) mA |
Deceleration time | type 25⁄21 (0 - > 1/1 -> 0, 50/60Hz) ms |
Cable length | 40 (unshielded) m |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Number | 8 |
Outputs in groups of | 1 |
Parallel switching of outputs for increased output | Not permitted |
Protection of an output relay | B16 circuit breaker or 8 A (T) fuse |
Potential isolation | Safe isolation according to EN 50178: 300 V AC Basic isolation: 600 V AC from power supply: yes From the inputs: yes between outputs: yes to expansion devices: yes |
Contacts Conventional thermal current (10 A UL) | 5 A |
Contacts Recommended for load: 12 V AC/DC | > 500 mA |
Contacts Rated impulse withstand voltage Uimp of contact coil | 6 kV |
Contacts Rated operational voltage [Ue] | 240 V AC |
Rated insulation voltage [Ui] | 240 V AC |
Safe isolation according to EN 50178 | 300 between coil and contact 300 between two contacts V AC |
Making capacity AC–-15, 250 V AC, 3 A (600 ops./h) [Operations] | 300000 |
Making capacity DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations] | 200000 |
Breaking capacity AC-15, 250 V AC, 3 A (600 Ops./h) [Operations] | 300000 |
Breaking capacity DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations] | 200000 |
Filament bulb load 1000 W at 230/240 V AC [Operations] | 25000 |
Filament bulb load 500 W at 115/120 V AC [Operations] | 25000 |
Fluorescent lamp load Fluorescent lamp load 10 x 58 W at 230/240 V AC With upstream electrical device [Operations] | 25000 |
Fluorescent lamp load Fluorescent lamp load 10 x 58 W at 230/240 V AC Uncompensated [Operations] | 25000 |
Fluorescent lamp load Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated [Operations] | 25000 |
Switching frequency Mechanical operations | 10 x 106 |
Switching frequency Switching frequency | 10 Hz |
Switching frequency Resistive load/lamp load | 2 Hz |
Switching frequency Inductive load | 0.5 Hz |
UL/CSA Uninterrupted current at 240 V AC | 5 A |
UL/CSA Uninterrupted current at 24 V DC | 5 A |
UL/CSA AC Control Circuit Rating Codes (utilization category) | B 300 Light Pilot Duty |
UL/CSA AC Max. rated operational voltage | 300 V AC |
UL/CSA AC max. thermal continuous current cos ϕ = 1 at B 300 | 5 A |
UL/CSA AC max. make/break cos ϕ ≠ capacity 1 at B 300 | 3600/360 VA |
UL/CSA DC Control Circuit Rating Codes (utilization category) | R 300 Light Pilot Duty |
UL/CSA DC Max. rated operational voltage | 300 V DC |
UL/CSA DC Max. thermal uninterrupted current at R 300 | 1 A |
UL/CSA DC Max. make/break capacity at R 300 | 28/28 VA |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
Static heat dissipation, non-current-dependent [Pvs] | 3 W |
Operating ambient temperature min. | -25 °C |
Operating ambient temperature max. | +55 °C |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
10.2 Strength of materials and parts 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
10.2 Strength of materials and parts 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
10.2 Strength of materials and parts 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
10.2 Strength of materials and parts 10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. |
10.2 Strength of materials and parts 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
10.2 Strength of materials and parts 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts 10.2.7 Inscriptions | Meets the product standard's requirements. |
10.3 Degree of protection of ASSEMBLIES | Meets the product standard's requirements. |
10.4 Clearances and creepage distances | Meets the product standard's requirements. |
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
10.8 Connections for external conductors | Is the panel builder's responsibility. |
10.9 Insulation properties 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
10.9 Insulation properties 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
10.9 Insulation properties 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating | Is the panel builder's responsibility. |
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. |
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
PLC's (EG000024) / Logic module (EC001417) | |
Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / Logic module (ecl@ss10.0.1-27-24-22-16 [AKE539014]) | |
Supply voltage AC 50 Hz | 20.4 - 28.8 V |
Supply voltage AC 60 Hz | 20.4 - 28.8 V |
Supply voltage DC | 10.2 - 28.8 V |
Voltage type of supply voltage | AC/DC |
Switching current | 5 A |
Number of analogue inputs | 0 |
Number of analogue outputs | 0 |
Number of digital inputs | 8 |
Number of digital outputs | 8 |
With relay output | Yes |
Number of HW-interfaces industrial Ethernet | 0 |
Number of interfaces PROFINET | 0 |
Number of HW-interfaces RS-232 | 0 |
Number of HW-interfaces RS-422 | 0 |
Number of HW-interfaces RS-485 | 0 |
Number of HW-interfaces serial TTY | 0 |
Number of HW-interfaces USB | 0 |
Number of HW-interfaces parallel | 0 |
Number of HW-interfaces Wireless | 0 |
Number of HW-interfaces other | 2 |
With optical interface | No |
Supporting protocol for TCP/IP | No |
Supporting protocol for PROFIBUS | No |
Supporting protocol for CAN | No |
Supporting protocol for INTERBUS | No |
Supporting protocol for ASI | No |
Supporting protocol for KNX | No |
Supporting protocol for MODBUS | No |
Supporting protocol for Data-Highway | No |
Supporting protocol for DeviceNet | No |
Supporting protocol for SUCONET | No |
Supporting protocol for LON | No |
Supporting protocol for PROFINET IO | No |
Supporting protocol for PROFINET CBA | No |
Supporting protocol for SERCOS | No |
Supporting protocol for Foundation Fieldbus | No |
Supporting protocol for EtherNet/IP | No |
Supporting protocol for AS-Interface Safety at Work | No |
Supporting protocol for DeviceNet Safety | No |
Supporting protocol for INTERBUS-Safety | No |
Supporting protocol for PROFIsafe | No |
Supporting protocol for SafetyBUS p | No |
Supporting protocol for other bus systems | No |
Radio standard Bluetooth | No |
Radio standard WLAN 802.11 | No |
Radio standard GPRS | No |
Radio standard GSM | No |
Radio standard UMTS | No |
IO link master | No |
Redundancy | No |
With display | No |
Degree of protection (IP) | IP20 |
Basic device | No |
Expandable | Yes |
Expansion device | Yes |
With timer | No |
Rail mounting possible | Yes |
Wall mounting/direct mounting | Yes |
Front build in possible | No |
Rack-assembly possible | No |
Suitable for safety functions | No |
Category according to EN 954-1 | None |
SIL according to IEC 61508 | None |
Performance level acc. EN ISO 13849-1 | None |
Appendant operation agent (Ex ia) | No |
Appendant operation agent (Ex ib) | No |
Explosion safety category for gas | None |
Explosion safety category for dust | None |
Width | 71.5 mm |
Height | 90 mm |
Depth | 58 mm |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|
UL File No. | E205091 |
UL Category Control No. | NRAQ/7 |
North America Certification | UL listed |
Degree of Protection | IEC: IP20, UL/CSA Type: - |
Description | EASY-E4-UC-16RE1 Expansion Unit |
---|---|