Menu

Moeller PKZM3
Thermal Magnetic Circuit Breaker
Index

PKZM 3

The older styles PKZM3-xx are now retired and replaced with the upgraded PKZ2 series.

 When upgrading to the new PKZ2 series the following considerations apply

 

 

 

1. The new PKZ2 series has a rotary operator knob instead of the older style stop and start button.

 

2. If any mechanical object was used to hit the stop button (as used in many wood working machines for end of travel) the system must be changed to use a limit switch and shunt trip. Call your Kmparts.com specialist for more info! No accessories from the PKZ3 series will work with the new PKZ2 series.

 

PKZM3
Old Style
Max HP 3 Phase at: 230 V Max HP 3 Phase at: 460 V
PKZM3-0.6 -- 1/4
PKZM3-1.0 -- 1/2
PKZM3-1.6 1/3 3/4
PKZM3-2.5 1/2 1
PKZM3-4 1 2
PKZM3-6.3 1 1/2 3
PKZM3-10 3 5
PKZM3-16 5 10
PKZM3-25 7 1/2 15
PKZM3-32 10 20
PKZM3-40 10 30

 

Old Style
PKZM3
 

New Style
PKZ2/ZM-xx

LOAD RANGE
PKZ2 with Trip Module Hp @ 230 Hp @ 460 Thermal

Amps

 

Magnetic

Amps

 

PKZM 3 PKZ2   Low Adjust
High Adjust
PKZM3-0.6

PKZ2/ZM-0.6

- - 0.4  5
0.6 8
PKZM3-1.0

PKZ2/ZM-1

- .5 0.6 8
1 14
PKZM3-1.6

PKZ2/ZM-1.6

- .75 1 14
1.6 22
PKZM3-2.5

PKZ2/ZM-2.4

.5 1 1.6 20
2.4 35
PKZM3-4

PKZ2/ZM-4

1 2 2.4 35
4 55
PKZM3-6.3

PKZ2/ZM-6

1.5 3 4 50
6 80
PKZM3-10

PKZ2/ZM-10

3 5 6 80
10 140
PKZM3-16

PKZ2/ZM-16

5 10 10 130
16 220
PKZM3-25

PKZ2/ZM-25

7.5 20 16 200
27 350
PKZM3-32

PKZ2/ZM-32

10 20 24 275
32 425
PKZM3-40

PKZ2/ZM-40

15 30 32 350
42 500

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.