STANDARD FEATURES:
§ UL listed, CSA certified,
self-protected combination motor controller. UL 508 / CSA 22.2, No.
14 Type E.
§ Factory mounted and labeled
contactor and disconnect portion rates max 42A, 30 HP at 460V; max 27A HP
at 575V.
§ No backup over current
protection required up to its full interrupting rating.
§ Continuity of service
(protects itself against damage under fault conditions).
§ Plug in trip module, which
creates an open circuit path to the motor when removed. For
additional safety.
§ Adjustable thermal and
magnetic trips; built in phase loss differential trip.
§ Built in 1normally open and 1
normally closed auxiliary contacts in the contactor portions. 2
normally open are also available.
§ Electrical life: 1 million
operations, AC-3 (30/25 HP at 460/575V).
§ Adapter plate for rail or
panel mounting.
§ Control circuit transformer
tap-off terminals on load side of disconnect.
§ Allows mounting of
accessories such as voltage trips, standard and trip indicating auxiliary
contacts.
§ Enclosed starters provided
with door interlocking handle.
§ In the event of an overload
condition, the normally closed contactor in the ZM trip module opens the
contactor coil circuit and the normally open contact may be used to
remotely signal an overload condition. On a short circuit, the main
disconnect switch opens.