STANDARD FEATURES:
§ UL
listed, CSA certified, self-protected combination
motor controller. UL 508 / CSA 22.2, No. 14
Type E.
§ Factory
mounted and labeled contactor and disconnect portion
rates max 42A, 30 HP at 460V; max 27A HP at 575V.
§ No
backup over current protection required up to its
full interrupting rating.
§ Continuity of service (protects itself against
damage under fault conditions).
§ Plug in
trip module, which creates an open circuit path to
the motor when removed. For additional safety.
§ Adjustable thermal and magnetic trips; built in
phase loss differential trip.
§ Built
in 1normally open and 1 normally closed auxiliary
contacts in the contactor portions. 2 normally
open are also available.
§ Electrical life: 1 million operations, AC-3 (30/25
HP at 460/575V).
§ Adapter
plate for rail or panel mounting.
§ Control
circuit transformer tap-off terminals on load side
of disconnect.
§ Allows
mounting of accessories such as voltage trips,
standard and trip indicating auxiliary contacts.
§ Enclosed starters provided with door interlocking
handle.
§ In the
event of an overload condition, the normally closed
contactor in the ZMR trip module opens the contactor
coil circuit and the normally open contact may be
used to remotely signal an overload condition.
On a short circuit, the main disconnect switch
opens.