Eaton Molded Case Circuit Breaker Series-C, J-Frame

J-Frame (70–250 Amperes)
Product Description
- All Eaton’s J-Frame circuit breakers are HACR rated
- J-Frame circuit breakers are available as individual components (frame, trip unit, terminals), or factory assembled complete breakers
- J-Frame circuit breakers with non-interchangeable trip units are suitable for reverse feed use
Types JD, HJD and JDC Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units
Maximum Continuous Ampere Rating at 40°C |
Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac Factory Assembled Circuit Consisting of Frame, Trip Unit and Terminals(1) Part Number |
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac Factory Assembled Circuit Consisting of Frame, Trip Unit and Terminals(1) Part Number |
Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac Factory Assembled Circuit Consisting of Frame, Trip Unit and Terminals(1) Part Number |
Thermal-Magnetic Trip Unit Only(1) For Use with Standard or High or Ultra High Interrupting Frames Part Number |
Standard Terminals Only Part Number |
Two-Pole | |||||
70 | JD2070 | HJD2070 | JDC2070 | JT2070T | TA250KB(2) |
90 | JD2090 | HJD2090 | JDC2090 | JT2090T | |
100 | JD2100 | HJD2100 | JDC2100 | JT2100T | |
125 | JD2125 | HJD2125 | JDC2125 | JT2125T | |
150 | JD2150 | HJD2150 | JDC2150 | JT2150T | |
175 | JD2175 | HJD2175 | JDC2175 | JT2175T | |
200 | JD2200 | HJD2200 | JDC2200 | JT2200T | |
225 | JD2225 | HJD2225 | JDC2225 | JT2225T | |
250 | JD2250 | HJD2250 | JDC2250 | JT2250T | |
Three-Pole | |||||
70 | JD3070 | HJD3070 | JDC3070 | JT3070T | TA250KB(2) |
90 | JD3090 | HJD3090 | JDC3090 | JT3090T | |
100 | JD3100 | HJD3100 | JDC3100 | JT3100T | |
125 | JD3125 | HJD3125 | JDC3125 | JT3125T | |
150 | JD3150 | HJD3150 | JDC3150 | JT3150T | |
175 | JD3175 | HJD3175 | JDC3175 | JT3175T | |
200 | JD3200 | HJD3200 | JDC3200 | JT3200T | |
225 | JD3225 | HJD3225 | JDC3225 | JT3225T | |
250 | JD3250 | HJD3250 | JDC3250 | JT3250T | |
Four-Pole(3)(4) | |||||
125 | JD4125 | HJD4125 | JDC4125 | JT4125T | TA250KB(2) |
150 | JD4150 | HJD4150 | JDC4150 | JT4150T | |
175 | JD4175 | HJD4175 | JDC4175 | JT4175T | |
200 | JD4200 | HJD4200 | JDC4200 | JT4200T | |
225 | JD4225 | HJD4225 | JDC4225 | JT4225T | |
250 | JD4250 | HJD4250 | JDC4250 | JT4250T |
NOTES:
(1) Magnetic trip adjustable 5–10 times continuous ampere rating.
(2) Individually packed.
(3) Fully rated neutral pole with no protection.
(4) Neutral is in right pole.
Types JD, HJD and JDC Thermal-Magnetic Circuit Breakers—Frame Only
Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac Part Number |
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac Part Number |
Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac Part Number |
Two-Pole | ||
JD2250F | HJD2250F | JDC2250F |
Three-Pole | ||
JD3250F | HJD3250F | JDC3250F |
Four-Pole | ||
JD4250F | HJD4250F | JDC4250F |
Type JDB Thermal-Magnetic Circuit Breakers with Non- Interchangeable Thermal-Magnetic Trip Units Suitable for Reverse Feed Application
Maximum Continuous Ampere Rating at 40°C |
600 Vac Rated, 250 Vdc Complete Circuit Breaker | |
Without Line and Load Terminals Part Number |
With Standard Line and Load Terminals Only Part Number |
|
Two-Pole | ||
70 | JDB2070W | JDB2070 |
90 | JDB2090W | JDB2090 |
100 | JDB2100W | JDB2100 |
125 | JDB2125W | JDB2125 |
150 | JDB2150W | JDB2150 |
175 | JDB2175W | JDB2175 |
200 | JDB2200W | JDB2200 |
225 | JDB2225W | JDB2225 |
250 | JDB2250W | JDB2250 |
Three-Pole | ||
70 | JDB3070W | JDB3070 |
90 | JDB3090W | JDB3090 |
100 | JDB3100W | JDB3100 |
125 | JDB3125W | JDB3125 |
150 | JDB3150W | JDB3150 |
175 | JDB3175W | JDB3175 |
200 | JDB3200W | JDB3200 |
225 | JDB3225W | JDB3225 |
250 | JDB3250W | JDB3250 |
Molded Case Switches
Eaton’s molded case switches are used as compact switches in applications requiring high current switching capabilities. Molded case switches are constructed of circuit breaker components and are of the high instantaneous automatic type. Molded case switches are listed in accordance with Underwriters Laboratories Standard UL 489.
Maximum Continuous Ampere Rating at 40°C |
600 Vac Maximum, 250 Vdc Complete Circuit Breaker Only Without Line and Load Terminals |
Standard Terminals Only Part Number |
|
Part Number | Suitable for Reverse Feed Use Part Number |
||
Two-Pole | |||
250 | JD2250KW | JDB2250KW | TA250KB(1) |
HJD2250KW | HJDB2250KW | — | |
Three-Pole | |||
250 | JD3250KW | JDB3250KW | TA250KB(1) |
HJD3250KW | HJDB3250KW | — | |
Four-Pole | |||
250 | JD4250KW | JDB4250KW | TA250KB(1) |
HJD4250KW | HJDB4250KW | — |
NOTES:
(1) Individually packed.
Molded case switches may open above 2500 amperes.
Accessories Selection Guide and Ordering Information
Line and Load Terminals
Eaton’s line and load terminals provide wire connecting capabilities for specific ranges of continuous current ratings and wire types. All terminals comply with Underwriters Laboratories Standards UL 486A and UL 486B and CSA Standard C22.2 No. 65, or Electrical Bulletin 1165. Unless otherwise specified, JFrame circuit breaker line and load terminals are shipped separately for field installation.
The bottom of the standard TA250KB terminal contains a recess that is positioned over the J-Frame circuit breaker terminal conductor.
Ordering Information
J-Frame circuit breakers use Cu/AI terminals as standard. When optional copper-only terminals are required, order by catalog number. Specify if factory installation is required.
![]() |
|
T250KB Terminal | TA250KB Terminal (Standard) |
Line and Load Terminals
Maximum Breaker Amperes |
Terminal Body Material |
Wire Type |
AWG Wire Range/ No. Conductors |
Metric Wire Range mm2 |
Pat Number |
Standard Cu/AI Pressure Terminals | |||||
250 | Aluminum | Cu/AI | 4–350 kcmil | 25–185 | TA250KB |
Optional Cu Pressure Terminals | |||||
250 | Stainless Steel | Cu | 4–350 kcmil | 25–185 | T250KB |