Eaton Series-C Flex Shaft Handle Mechanisms

Eaton Series-C Flex Shaft Handle Mechanisms
Molded Case Circuit Breaker Over

Flange-Mounted Handle Mechanisms

Flange-mounted handle mechanisms mount on the flange of an enclosure door. The Flex Shaft is an extra heavy-duty mechanism that includes a flexible shaft in various lengths, 3 feet (0.9m) through 10 feet (3m) for use with various size enclosures.

The Flex Shaft handle will accept up to three padlock shackles, each with a maximum diameter of 3/8 inches (9.5 mm). It can be used with Type12 fabricated enclosures. An optional handle is available for Flex Shaft that is suitable for use with Type 4 environments.

Flex Shaft comes preset from the factory, requiring only minor field adjustments on installation, which takes about 10 minutes—a significant time savings compared to installation of other types of flange handle mechanisms. The Flex Shaft mechanism also takes up less interior enclosure space than competitive designs, and the handle fits standard flange cutouts. Flex Shaft handle can be remotely mounted from breaker, where an operator can use it by “funneling” the cable through conduit.

Standards and Certifications

Flex Shaft is UL listed under
File E64983 and meets CSA requirements.


Product Selection

Note: Type 4X handle mechanisms are available. Add Suffix X to the complete Part Number.

Note: When selecting the length of shaft, ensure minimum bending radius of 4 inches (101.6 mm) is maintained to operate properly.

Note: The standard method of shipment includes the mechanism preset at the factory; however, minor field adjustments may be required.

Flex Shaft Flange-Mounted Handle Mechanisms(1)(2)

Breaker
Frame
Flexible Shaft Length in Feet (m)
3 (0.9) 4 (1.2) 5 (1.5) 6 (1.8) 7 (2.1)  8 (2.4)  9 (2.7) 10 (3.0)
G(1) F0S03C F0S04C F0S05C F0S06C
F F1S03C F1S04C F1S05C F1S06C F1S07C F1S08C F1S09C F1S10C
F (dual) F1S03CD F1S04CD F1S05CD F1S06CD F1S07CD F1S08CD F1S09CD F1S10CD
J F2S03C F2S04C F2S05C F2S06C F2S07C F2S08C F2S09C F2S10C
K F3S03C F3S04C F3S05C F3S06C F3S07C F3S08C F3S09C F3S10C
L and MDL F4S04C F4S05C F4S06C F4S10C
N F5S04C F5S05C F5S06C F5S10C
R F6S04 F6S05 F6S06
MD, MDS (old) F7S04 F7S05 F7S06 F7S10C

Type C371 — Flange-Mounted Handle Mechanisms

Frame
Size
Variable Depth
Mounting Range
Min./Max.(2)(3)
Operating
Mechanism Only(4)
Operating Mechanism w/ 4-Inch Handle
For NEMA 1—12
Enclosure
For NEMA 4/4X
Enclosure
150 6.50—16 (165.1—406.4) C371E C371E1 C371E2
250 6.50—16.63 (165.1—422.4) C371F C371F5 C371F6
400 6.50—16.63 (165.1—422.4) C371F C371F5 C371F6
600 8.50—22 (215.9—558.8) C371G C371G5 C371G6
800 8.75—22 (222.3—558.8) C371K C371K5 C371K6
1200 9.75—22 (247.7—558.8) C371K C371K5 C371K6

NOTES:
(1) Suitable for GC/GD MCCB; not suitable for GMCP.
(2) For increased maximum allowable depth, see connecting rods
(3) Dimensions shown are from panel flange surface.
(4) Does not include handle.
Type 4/4X handle mechanisms are available. Add Suffix X to complete catalog number. Add Suffix I to complete catalog number for IEC handle. Original narrow handle design (No C Suffix) is available. Remove C from catalog number.
When selecting the length of shaft, ensure minimum bending radius of 4 inches (101.6 mm) (5 inches, 12.7 mm for L-, N- and R-Frames) is maintained to operate properly. The standard method of shipment includes the mechanism preset at the factory; however, minor field adjustments may be required.
Dual breakers operator available on F-Frame only. Only the F, J and K can mount LH and RH all other RH only.

Handle Only

Circuit Breaker
Frame Size
(Amperes)
NEMA
Enclosure Type
Operating
Handle Length
Catalog
Number
150 1/3R/3/12 4.00 (101.6) C371H1
4/4X 4.00 (101.6) C371H2
1/3R/3/12 6.00 (152.4) C371H3
4/4X 6.00 (152.4) C371H4
250—1200 1/3R/3/12 4.00 (101.6) C371H5
4/4X 4.00 (101.6) C371H6
1/3R/3/12 6.00 (152.4) C371H7
4/4X 6.00 (152.4) C371H8

Channel Support Kit (Rod Not Supplied)

For use to prevent bending of the operating handle mounting surface. This is especially useful when the operating handle is mounted on a channel in a multi-door enclosure.

Amperes Part Number
600—1200 C371CS6

Connecting Rods(1)

Application PArt Number
Disconnect switches (30, 60, 100, 200A sizes) C371CS1
Circuit breakers (150, 250, 400A sizes) C371CS1
Circuit breakers (600, 800, 1200A sizes) C371CS2

NOTE:
(1) Increase maximum allowable depth by 5 inches (127 mm).

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.