Eaton Series-C Molded Case Circuit Breakers Internal Accessories

Eaton Series-C Internal Accessories
Molded Case Circuit Breaker Over

Internal Accessories

Product Overview

Alarm Switch

For remote indication of automatic trip operation. Does not function with manual switching; however, it will operate when either a shunt trip or undervoltage release is operated. A “make” contact closes and a “break” contact opens when the alarm/lockout switch operates. The switch automatically resets when the circuit breaker is reset.

Auxiliary Switch

The auxiliary switch provides circuit breaker contact status information by monitoring the position of the molded cross bar that contains the moving contact arms. The auxiliary switch is used for remote indication and interlock system verification, and consists of one or two SPDT switches housed in a plug-in module. Each SPDT switch has one “a” and one “b” contact. When the circuit breaker contacts are open, the “a” contact is open and the “b” contact is closed.

Auxiliary Switch and Alarm Switch Combination

In an auxiliary switch ASL switch combination, the auxiliary switch is always mounted on the side of the plug-in module next to the center pole of the circuit breaker.

Shunt Trip

The shunt trip provides remote controlled tripping of the circuit breaker. The shunt trip consists of an intermittent rated solenoid with a tripping plunger and a cutoff switch assembled to a plug-in module. When required for ground fault protection applications, certain AC rated shunt trips, as noted in the electrical rating table, are suitable for operation at 55 percent of rated voltage.

Low Energy Shunt Trip

Low energy shunt trip devices are designed to operate from low energy output signals from dedicated current sensors typically applied in ground fault protection schemes. However, with a proper control voltage source, they may be applied in place of conventional trip devices for special applications. Flux paths surrounding permanent magnets used in the shunt trip assembly hold a charged spring poised in readiness to operate the circuit breaker trip mechanism.

When a 100 microfarad capacitor charged to 28 Vdc is discharged through the shunt trip coil, the resultant flux opposes the permanent magnet flux field, which releases the stored energy in the spring to trip the circuit breaker. As the circuit breaker resets, the shunt trip reset arm is actuated by the circuit breaker handle, resetting the shunt trip. The plug-in module is mounted in retaining slots in the top of the trip unit. Coil is intermittent-rated only. Cutoff provisions required in control circuit.

Undervoltage Release Mechanism

The undervoltage release mechanism monitors a voltage (typically a line voltage) and trips the circuit breaker when the voltage falls to between 70 and 35 percent of the solenoid coil rating.

The undervoltage release mechanism consists of a continuous rated solenoid with a plunger and tripping lever mounted in a plug-in module. The tab on the tripping lever resets the undervoltage release mechanism when normal voltage has been restored and the circuit breaker handle is moved to the reset (or OFF) position. With less than pickup voltage applied to the undervoltage release mechanism, the circuit breaker contacts will not touch when a closing operation is attempted.

Note: Undervoltage release mechanism accessories are not designed for, and should not be used as, circuit interlocks.

Accessory Terminal Block (R-Frame)

(For fixed-mounted configuration.) Internal accessory wiring leads are normally supplied with pigtail leads (18 AWG) that exit from the right side of the circuit breaker. Where specified, fixed-mounted accessory terminal blocks are available. A maximum of one 24-point terminal block can be installed on the right side of the circuit breaker for the internal accessories.

PowerNet and Zone Interlock Kits (OPTIM 550 only) K-, L- and N-Frames

Eaton’s PowerNet Communications Kit can be ordered to add PowerNet communications to an existing OPTIM 550 breaker in the field. An 18-inch (457.2 mm) wiring pigtail is routed to the rear of the breaker: two wires for PowerNet and two wires for 24 Vdc (45 mA load). It is recommended that the power supply be an “isolated high quality” unit.

Alarm Switch

G-Frame Alarm Switch (RH Only)(1)

Alarm Switch

Electrical Ratings Contact
Arrangement
Factory
Suffix
Part
Number(2)(3)(4)
Volts Frequency Amperes
Alarm Switch
240 50/60 Hz 6 1 Make/1 Break B3 1288C75G03
Alarm Switch Auxiliary Switches Combination
240 50/60 Hz 6 1 Make/1 Break and 1A/1B B13 1288C76G09

F-Frame Alarm Switch(1)

Number of
Contacts
(Make and
Break)
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Factory Installation Kit(5)
Same Side Rear(6) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left(7) B01 B02 B03 B04 A1L1LPK A1L1LTK
Right B05 B06 B07 B08 A1L1RPK A1L1RTK
2 Left(7) B09 B10 B11 A2L1LPK A2L1LTK
Right B12 B13 B14 A2L1RPK A2L1RTK
1 (Make only) Single-pole B15(8)  —

F-Frame HMCP Alarm Switch(1)

Number of
Contacts
(Make and
Break)
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Factory Installation Kit(5)
Same Side Rear(6) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left(7) B01 B02 B03 B04 MA1L1LPK MA1L1LTK
Right B05 B06 B07 B08 MA1L1RPK MA1L1RTK
2 Left(7) B09 B10 B11 MA2L1LPK MA2L1LTK
Right B12 B13 B14 MA2L1RPK MA2L1RTK

J-Frame and HMCP (J) Alarm Switch

Number of
Contacts
(Make and
Break)
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Factory Installation Kit(9)
Same Side Rear(7) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left(10) B01 B02 B03 B04 A1L2LPK A1L2LTK
Right B05 B06 B07 B08 A1L2RPK A1L2RTK(6)

NOTES:
(1) F-Frame circuit breakers are factory sealed. Underwriters Laboratories requires that internal accessories be installed at the factory. Internal accessories are UL listed for factory installation under E7819. Where local codes and standards permit and UL listing is not required, internal accessories can be field installed. Accessory installation should be done before the circuit breaker is mounted and connected.
(2) Includes 24-inch (609.6 mm) external pigtail leads,18 AWG (16–0.010).
(3) A maximum of two internal accessories may be mounted in a three-pole circuit breaker.
(4) Suitable for mounting in right pole only of two- or three-pole breaker.
(5) Not listed with Underwriters Laboratories; for field installation.
(6) Standard pigtail lead exit location.
(7) Standard mounting location.
(8) Factory installation only. Leads exit load end of circuit breaker.
(9) Listed with Underwriters Laboratories; for field installation on interchangeable trip unit breakers under E64983.
(10) Standard mounting location—leads exit rear of breaker.

K-Frame and HMCP (K) Alarm Switch

Number of
Sets of
Contacts
(1M and 1B)
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(1)
Same Side Rear(6) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left(3) B01 B02 B03 B04 A1L3LPK A1L3LTK
Right(4) B05 B06 B07 B08 A1L3RPK A1L3RTK
2 Left(3) B09 B10 B11 A2L3LPK A2L3LTK
Right(4) B12 B13 B14 A2L3RPK A2L3RTK

L-, HMCP (L) and (M) Frames and Alarm Switch

Number of
Sets of
Contacts
(1M and 1B)
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(1)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left(3) B01 B02 B03 B04 A1L4LPK A1L4LTK
Right B05 B06 B07 B08 A1L4RPK A1L4RTK
2 Left(3) B09 B10 B11 A2L4LPK A2L4LTK
Right B12 B13 B14 A2L4RPK A2L4RTK

N-Frame and HMCP (N) Alarm Switch

Number of
Sets of
Contacts
(1M and 1B)
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(5)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left B01 B02 B03 B04 A1L5LPK A1L5LTK
Right(3) B05 B06 B07 B08 A1L5RPK A1L5RTK
2 Left B09 B10 B11 A2L5LPK A2L5LTK
Right(3) B12 B13 B14 A2L5RPK A2L5RTK

R-Frame Alarm Switch (RH Only)

Number of Contacts
(Make and Break)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(5)
Pigtail Leads
1 B05 A1L6RPK
2 B12 A2L6RPK

NOTES:
(1) Listed with Underwriters Laboratories; for field installation on interchangeable trip unit breakers under E64983.
(2) Standard mounting location.
(3) Standard mounting location—leads exit rear of breaker.
(4) Breakers with K-Frame OPTIM 550 can only accept accessories in left pole.
(5) Listed with Underwriters Laboratories for field installation under E64983.
(6) A maximum of three ASL plug-in modules may be installed in a circuit breaker.

Auxiliary Switch

G-Frame Auxiliary Switch (RH Only)

Auxiliary Switch

Volts Frequency Amperes Contact
Arrangement
Factory
Suffix
Part
Number(1)(2)
240 50/60 Hz 6 1a/1b A3 1288C74G03
240 50/60 Hz 6 2a/2b A6 1288C73G03

F-Frame and HMCP (F) Auxiliary Switch

Number of
Contacts
A and B
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Factory Installation Kit(4)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left(5) A01 A02 A03 A04 A1X1PK A1X1LTK
Left(5) A15(7) A16(7) A17(7) E1X1PK
Right or Neutral(6) A05 A06 A07 A08 A1X1PK A1X1RTK(8)
Right or Neutral(6) A18(7) A19(7) A20(7)
2 Left(5) A09 A10 A11 A2X1LPK A2X1LTK
Left(5) A21(7) A22(7) E2X1LPK
Right or Neutral(6) A12 A13 A14 A2X1RPK A2X1RTK(8)
Right or Neutral(6) A23(7) A24(7) E2X1RPK

F-Frame with Electronic Trip Unit Auxiliary Switch(9)

Number of
Contacts
A and B
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Factory Installation Kit(4)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Right A30 A31 A32 A1X1RPKFDE

J-Frame and HMCP (J) Auxiliary Switch

Number of
Contacts
A and B
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Factory Installation Kit(10)
Same Side Rear(3) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left A01 A02 A03 A04 A1X2PK A1X2LTK
Right(11) A05 A06 A07 A08 A1X2PK A1X2RTK(4)
2 Left A09 A10 A11 A2X2PK A2X2LTK
Right(11) A12 A13 A14 A2X2PK A2X2RTK(4)

NOTES:
(1) Includes 24-inch external pigtail leads, 18 AWG (16–0.010).
(2) A maximum of two internal accessories may be mounted in a three-pole circuit breaker. Suitable for mounting in right pole only of two- or three-pole breaker.
(3) Standard pigtail lead exit location.
(4) Not listed with Underwriters Laboratories; for field installation.
(5) Pigtail wire size: 18 AWG (0.82 mm2).
(6) Not for use on F-Frame with electronic trip unit.
(7) 125 volts (max.), 50/60 Hz switch for use in electronic circuit of 100 micro amperes and 15 Vdc minimum.
(8) Not for use on four-pole circuit breakers.
(9) Only for use on three-pole F-Frame breakers with electronic trip unit.
(10) Listed with Underwriters Laboratories for field installation or interchangeable trip unit breakers under E64983.
(11) Standard mounting location—leads exit rear of breaker.

K-Frame and HMCP (K) Auxiliary Switch

Number of
Contacts
A and B
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Factory Installation Kit(1)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left A01 A02 A03 A04 A1X3PK A1X3LTK
Right(2)(3) A05 A06 A07 A08 A1X3PK A1X3RTK(4)
2 Left A09 A10 A11 A2X3PK A2X3LTK
Right(2)(3) A12 A13 A14 A2X3PK A2X3RTK(4)
Right A21 A22 1482D28G10(6)(7)
3 Left A18 A15 A3X3LPK A3X3LTK
Right(3) A17 A16 A3X3RPK A3X3RTK(4)

L-, HMCP (L) and (M) Frames and Auxiliary Switch

Number of
Contacts
A and B
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Factory Installation Kit(1)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left A01 A02 A03 A04 A1X4PK A1X4LTK
Right(2) A05 A06 A07 A08 A1X4PK A1X4RTK(4)
2 Left A09 A10 A11 A2X4PK A2X4LTK
Right(2) A12 A13 A14 A2X4PK A2X4RTK(4)
3 Left A18 A15 A3X4PK A3X4LTK
Right(2) A17 A16 A3X4PK A3X4RTK(4)

N-Frame and HMCP (N) Auxiliary Switch

Number of
Contacts
A and B
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Factory Installation Kit(1)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left A01 A02 A03 A04 A1X5PK A1X5LTK
Right(2) A05 A06 A07 A08 A1X5PK A1X5RTK(4)
2 Left A09 A10 A11 A2X5PK A2X5LTK
Right(2) A12 A13 A14 A2X5PK A2X5RTK(4)
3 Left A18 A15 A3X5LPK A3X5LTK
Right(2) A17 A16 A3X5RPK A3X5RTK(4)

R-Frame Auxiliary Switch (RH Only)

Number of
Contacts
A and B
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Suffix Number(5)
Field Mounted
Field Installation Kits(1)
Pigtail Leads
2 A12 A2X6RPK
4 A19 A4X6RPK

NOTES:
(1) Listed with Underwriters Laboratories for field installation under E64983.
(2) Standard mounting location—leads exit rear of breaker.
(3) Breakers with K-Frame OPTIM 550 can only accept accessories in left pole.
(4) Not for use on four-pole circuit breakers.
(5) A maximum of two auxiliary switches (any combination of 2a/2b or 4a/4b plug-in modules may be installed in a circuit breaker.
(6) This option is not field installable.
(7) Available on the OPTIM 550 only. Communications are not available with this option.

Auxiliary Switch and Alarm Switch Combination

F-Frame Auxiliary Switch and Alarm Switch Combination

Auxiliary Switch
and
Alarm Switch
Combination

Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457 mm) Pigtail Leads
Factory Installation Kit(1)
Same Side Rear(2) Terminal Block
Same Side
Pigtail Leads Terminal Block
Left(2) C01 C02 C03 AAL1LPK AAL1LTK
Right C04 C05 C06 AAL1RPK AAL1RTK(3)

F-Frame HMCP Auxiliary Switch and Alarm Switch Combination

Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457 mm) Pigtail Leads
Factory Installation Kit(1)
Same Side Rear(2) Terminal Block
Same Side
Pigtail Leads Terminal Block
Left(3) C01 C02 C03 MAAL1LPK MAAL1LTK
Right C04 C05 C06 MAAL1RPK MAAL1RPK

J-Frame and HMCP (J) Auxiliary Switch and Alarm Switch Combination

Number of
Sets of
Contacts
(1A and 1B)
(1M–1B)
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457 mm) Pigtail Leads
Field Mounted
Field Installation Kits(4)
Same Side Rear(5) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left C01 C02 C03 AAL2LPK AAL2LTK
Right(3) C04 C05 C06 AAL2RPK AAL2RTK(3)

K-Frame and HMCP (K) Auxiliary Switch and Alarm Switch Combination

Number of
Sets of
Contacts
(1A and 1B)
(1M–1B)
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457 mm) Pigtail Leads
Field Mounted
Field Installation Kits(4)
Same Side Rear(5) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1 Left C01 C02 C03 AAL3LPK AAL3LTK
Right(5)(6) C04 C05 C06 AAL3RPK(7) AAL3RTK
Right C07 C08 1482D28G09(8)(9)

NOTES:
(1) Not listed with Underwriters Laboratories for field installation.
(2) Standard mounting location.
(3) Standard mounting location.
(4) Listed with Underwriters Laboratories for field installation of interchangeable trip unit breakers under E64983.
(5) Standard mounting location—leads exit rear of breaker.
(6) Breakers with K-Frame OPTIM 550 can only accept accessories in left pole.
(7) Will not install on OPTIM Trip (RH).
(8) Available on the OPTIM 550 only. Communications are not available with this option.
(9) This option is not field installable.

L-, HMCP (L) and (M) Frames and Auxiliary Switch and Alarm Switch Combination

Number of
Sets of
Contacts
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457 mm) Pigtail Leads
Field Mounted
Field Installation Kits(1)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1A, 1B and
1 Make/1 Break
Left C01 C02 C03 AA114LPK AA114LTK
Right(2) C04 C05 C06 AA114RPK AA114RTK(3)
2A, 2B and
1 Make/1 Break
Left C07 C08 C12 AA214LPK AA214LTK
Right(2) C10 C11 C13 AA214RPK AA214RTK(3)
3A, 3B and
1 Make/1 Break
Left C14 AA314LPK
Right(2) C15 AA314RPK

N-Frame and HMCP (N) Auxiliary Switch and Alarm Switch Combination

Number of
Sets of
Contacts
Mounting
Location
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457 mm) Pigtail Leads
Field Mounted
Field Installation Kits(1)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
1A, 1B and
1 Make/1 Break
Left C01 C02 C03 AA115LPK AA115LTK
Right(2) C04 C05 C06 AA115RPK AA115RTK(3)
2A, 2B and
1 Make/1 Break
Left C07 C08 C12 AA215LPK AA215LTK
Right(2) C10 C11 C13 AA215RPK AA215RTK(3)

NOTES:
(1) Listed with Underwriters Laboratories for field installation under E64983.
(2) Standard mounting location—leads exit rear of breaker.
(3) Not for use on four-pole circuit breaker.

Shunt Trip

G-Frame Shunt Trip (LH Three-Pole Only)

Shunt Trip

Volts Frequency Amperes Suffix Part
Number
120 50/60 Hz 1.1 S1 1373D62G01
240 50/60 Hz 2.1 S2 1373D62G02
12 DC 2.8 S3 1373D62G15
24 DC 5.7 S4 1373D62G16
24 60 Hz S7 1373D62G20

F-Frame and HMCP (F) Shunt Trip

Voltage Rating
(AC Frequency = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads(2)
Factory Installation Kit(1)
Same Side Rear(3) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
Left-Pole Mounting AC/DC Ratings
12–24 Vac or Vdc S01 S02 S03 S04 SNT1LP03K SNT1LT03K
48–127 Vac or 48–60 Vdc(4) S05 S06 S07 S08 SNT1LP08K SNT1LT08K
208–380 Vac or 110–127 Vdc S09 S10 S11 S12 SNT1LP12K SNT1LT12K
415–600 Vac or 220–250 Vdc S13 S14 S15 S16 SNT1LP18K SNT1LT18K
Right- or Neutral-Pole Mounting AC/DC Ratings(5)
12–24 Vac or Vdc S17 S18 S19 S20 SNT1RP03K SNT1RT03K(6)
48–127 Vac or 48–60 Vdc(4) S21 S22 S23 S24 SNT1RP08K SNT1RT08K(6)
208–380 Vac or 110–127 Vdc S25 S26 S27 S28 SNT1RP12K SNT1RT12K(6)
415–600 Vac or 220–250 Vdc S29 S30 S31 S32 SNT1RP18K SNT1RT18K(6)

NOTES:
(1) Not listed with Underwriters Laboratories, for field installation.
(2) Pigtail wire size: 18 AWG (0.82 mm2).
(3) Standard pigtail lead exit location.
(4) 120 Vac marked suitable for ground fault protection devices.
(5) Standard mounting location.
(6) Not for use on four-pole circuit breakers.
G-Frame circuit breakers are factory sealed. Underwriters Laboratories requires that internal accessories be installed at the factory.
Internal accessories are UL listed for factory installation under E7819.
Where local codes and standards permit and UL listing is not required, internal accessories can be field installed. Accessory installation should be done before the circuit breaker is mounted and connected.

J-Frame and HMCP (J) Shunt Trip

Voltage Rating
(AC Frequency = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads(2)
Factory Installation Kit(1)
Same Side Rear(3) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
Left-Pole Mounting AC/DC Ratings(2)
12–24 Vac or Vdc S41 S42 S43 S44 SNT2P04K SNT2T04K
48–60 Vac or Vdc S49 S50 S51 S52 SNT2P06K SNT2T06K
110–240 Vac or 110–125 Vdc(3) S09 S10 S11 S12 SNT2P11K SNT2T11K
380–440 Vac or 220–250 Vdc S13 S14 S15 S16 SNT2P14K SNT2T14K
480–600 Vac S17 S18 S19 S20 SNT2P18K SNT2T18K
Right- or Neutral-Pole Mounting AC/DC Ratings
12–24 Vac or Vdc S45 S46 S47 S48 SNT2P04K SNT2T04K(4)
48–60 Vac or Vdc S53 S54 S55 S56 SNT2P06K SNT2T06K(4)
110–240 Vac or 110–125 Vdc(3) S29 S30 S31 S32 SNT2P11K SNT2T11K(4)
380–440 Vac or 220–250 Vdc S33 S34 S35 S36 SNT2P14K SNT2T14K(4)
480–600 Vac S37 S38 S39 S40 SNT2P18K SNT2T18K(4)

K-Frame and HMCP (K) Shunt Trip

Voltage Rating
(AC Frequency = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads(2)
Factory Installation Kit(1)
Same Side Rear(3) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
Left-Pole Mounting AC/DC Ratings(2)
12–24 Vac or Vdc S41 S42 S43 S44 SNT3P04K SNT3T04K
48–60 Vac or Vdc S49 S50 S51 S52 SNT3P06K SNT3T06K
110–240 Vac or 110–125 Vdc(3) S09 S10 S11 S12 SNT3P11K SNT3T11K
380–440 Vac or 220–250 Vdc S13 S14 S15 S16 SNT3P14K SNT3T14K
480–600 Vac S17 S18 S19 S20 SNT3P18K SNT3T18K
Right- or Neutral-Pole Mounting AC/DC Ratings(5)(6)
12–24 Vac or Vdc S45 S46 S47 S48 SNT3P04K SNT3T04K(4)
48–60 Vac or Vdc S53 S54 S55 S56 SNT3P06K SNT3T06K(4)
110–240 Vac or 110–125 Vdc(3) S29 S30 S31 S32 SNT3P11K SNT3T11K(4)
380–440 Vac or 220–250 Vdc S33 S34 S35 S36 SNT3P14K SNT3T14K(4)
480–600 Vac S37 S38 S39 S40 SNT3P18K SNT3T18K(4)

NOTES:
(1) Listed with Underwriters Laboratories for field installation under E64983.
(2) Standard mounting location—leads exit rear of breaker.
(3) Suitable for use with Class 1 ground fault sensing element.
(4) Not for use on four-pole circuit breakers.
(5) For use with KT (thermal-magnetic) trip units only.
(6) Breakers with K-Frame OPTIM 550 can only accept accessories in left pole.

L-, HMCP (L) and (M) Frames and Shunt Trip

Voltage Rating
(AC Frequency = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads(2)
Factory Installation Kit(1)
Same Side Rear(3) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
Left-Pole Mounting AC/DC Ratings(2)
12–24 Vac or Vdc S01 S02 S03 S04 SNT4LP03K SNT4LT03K
48–60 Vac S05 S06 S07 S08 SNT4LP05K SNT4LT05K
48–60 Vdc S85 S86 S87 SNT4LP23K SNT4LT23K
110–240 Vac S09 S10 S11 S12 SNT4LP11K SNT4LT11K
110–125 Vdc S41 S42 S43 S44 SNT4LP26K SNT4LT26K
380–440 Vac or 220–250 Vdc S13 S14 S15 S16 SNT4LP14K SNT4LT14K
480–600 Vac S17 S18 S19 S20 SNT4LP18K SNT4LT18K
Right- or Neutral-Pole Mounting AC/DC Ratings(3)
12–24 Vac or Vdc S21 S22 S23 S24 SNT4RP03K SNT4RT03K
48–60 Vac S25 S26 S27 S28 SNT4RP05K SNT4RT05K
48–60 Vdc S88 S89 S90 SNT4RP23K SNT4RT23K
110–240 Vac S29 S30 S31 S32 SNT4RP11K SNT4RT11K
110–125 Vdc S45 S46 S47 S48 SNT4RP26K SNT4RT26K
380–440 Vac or 220–250 Vdc S33 S34 S35 S36 SNT4RP14K SNT4RT14K
480–600 Vac S27 S38 S39 S40 SNT4RP18K SNT4RT18K

NOTES:
(1) Listed with Underwriters Laboratories, for field installation under E64983.
(2) Standard mounting location—leads exit rear of breaker.
(3) For use with LT (thermal-magnetic) three-pole trip units only.

N-Frame and HMCP (N) Shunt Trip

Voltage Rating
(AC Frequency = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads(2)
Factory Installation Kit(1)
Same Side Rear(2) Opposite Side Terminal Block
Same Side
Pigtail Leads Terminal Block
Left-Pole Mounting AC/DC Ratings(2)
9–24 Vac or Vdc S01 S02 S03 S04 SNT5LP03K SNT5LT03K
48–60 Vac S05 S06 S07 S08 SNT5LP05K SNT5LT05K
110–240 Vac(3) S09 S10 S11 S12 SNT5LP11K SNT5LT11K
110–125 Vdc S412 S42 S43 S44 SNT5LP26K SNT5LT26K
380–440 Vac or 220–250 Vdc S13 S14 S15 S16 SNT5LP14K SNT5LT14K
480–600 Vac S17 S18 S19 S20 SNT5LP18K SNT5LT18K
48–60 Vdc S21 S22 S23 S24 SNT5LP23K SNT5LT23K

R-Frame Shunt Trip (RH Only)

Voltage Rating
(AC Frequency = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads(4)
Field Mounted
Field Installation Kits(1)
Pigtail Leads
24 Vac or Vdc S21 SNT6P03K
48–60 Vac S25 SNT6P05K
110–240 Vac S29 SNT6P11K
380–440 Vac or 220–250 Vdc S33 SNT6P14K
480–600 Vac S37 SNT6P18K
48–60 Vdc S88 SNT6P23KSNT6P26K
110–125 Vdc S45  

NOTES:
(1) Listed with Underwriters Laboratories for field installation under E64983. (2) Standard mounting location—leads exit rear of breaker.
(3) Supply voltages suitable for use with Class 1 GFP devices. Marking label included with accessory kits.
(4) A maximum of two shunt trip plug-in modules may be installed in a circuit breaker.

Low Energy Shunt Trip

Ordering Information

Select shunt trip catalog number for the voltage within the indicated voltage range. Shunt trip coils are designed to be applied at specific AC or DC voltages within the voltage range shown. Electrical ratings are also shown on applicable circuit breaker accessory nameplates.

F-, J-, K-, L-, M-, N- and R-Frames and HMCPs Low Energy Shunt Trip(1)

Low Energy Shunt Trip

Mounting
Positions
(Pole)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(2)
Terminal Block
Same Side Rear(3) Opposite
Side
Same Side Pigtail Leads Terminal Block
F-Frame
Left N01 N02 N03 N04 LST1LPK(4) LST1LTK(4)
Right(3) N05 N06 N07 N08 LST1RPK(4) LST1RTK(4)
J-Frame
Left N01 N02 N03 LST2LPK
Right(3) N05 N06 N07 LST2RPK
K-Frame
Left(3) N01 N02 N03 LST3LPK
Right(5)(6) N05 N06 N07 LST3RPK
L- and M-Frames
Left N01 N02 N03 LST4LPK
Right N05 N06 N07 LST4RPK
N-Frame
Left(3) N01 N02 N03 LST5LPK
R-Frame
Right N01 LST6RPK

NOTES:
(1) Cutoff provisions required in control circuit.
(2) Listed with Underwriters Laboratories for field installation under E64983.
(3) Standard mounting location—leads exit rear of breaker.
(4) For F-Frame HMCP, add an “M” to beginning of catalog number. Field Installation Kit referenced for factory use only, not UL listed for field installation.
(5) For use with thermal-magnetic trip units only.
(6) Breakers with K-Frame OPTIM 550 can only accept accessories in left pole.

Undervoltage Release Mechanism

Ordering Information

Select handle reset undervoltage release mechanism catalog number for the voltage within the indicated voltage range. Undervoltage release mechanism coils are designed to be applied at specific AC or DC voltages within the voltage range shown on applicable circuit breaker accessory nameplates.

G-Frame Undervoltage Release Mechanism (LH Three-Pole Only)

Undervoltage Release Mechanism

Volts (AC Only) Frequency (Hz) Amperes Style Numbers(1)(2)(3) Factory Suffix
120 50/60 0.05 1373D62G03 T1
24 50/60 0.22 1373D62G04 T2
48 50/60 0.11 1373D62G05 T3
60 50/60 0.10 1373D62G06 T4
110 50 0.049 1373D62G07 T5
2088 60 0.026 1373D62G08 T6
220 50 0.025 1373D62G09 T7
240 50/60 0.024 1373D62G10 T8
380 50 0.015 1373D62G11 T9
415 50 0.013 1373D62G12 T10
440 50 0.012 1373D62G13 T11
480 50 0.01 1373D62G14 T12

NOTES:
(1) Includes 24-inch (609.6 mm) external pigtail leads, 18 AWG (16–0.010).
(2) A maximum of two internal accessories may be mounted in a three-pole circuit breaker.
(3) Suitable for mounting in left pole only of three-pole breaker.
G-Frame circuit breakers are factory sealed. Underwriters Laboratories requires that internal accessories be installed at the factory.
Internal accessories are UL listed for factory installation under E7819.
Where local codes and standards permit and UL listing is not required, internal accessories can be field installed. Accessory installation should be done before the circuit breaker is mounted and connected.

F-Frame Factory Mounted (For F-Frame Breaker and F-Frame HMCP) Undervoltage Release Mechanism

Voltage Rating
(AC Freq. = 50/60 Hz)
Connection Type and Location
18-Inch Pigtail Leads
Terminal Block
Same Side
Same Side Rear(1) Opposite Side
Left-Pole Mounting AC Ratings
12 Vac U01 U02 U03 U04
24 Vac U05 U06 U07 U08
48 Vac U37 U38 U39 U40
60 Vac U97 U98 U99 U100
110—127 Vac U13 U14 U15 U16
208—240 Vac U17 U18 U19 U20
380—480 Vac U21 U22 U23 U24
525—600 Vac U25 U26 U27 U28
Right-Pole Mounting AC Ratings(2)(3)
12 Vac U49 U50 U51 U52
24 Vac U53 U54 U55 U56
48 Vac U85 U86 U87 U88
60 Vac U101 U102 U103 U104
110—127 Vac U61 U62 U63 U64
208—240 Vac U65 U66 U67 U68
380—480 Vac U69 U70 U71 U72
525—600 Vac U73 U74 U75 U76
Left-Pole Mounting DC Ratings
12 Vdc U29 U30 U31 U32
24 Vdc U33 U34 U35 U36
48 Vdc U37 U38 U39 U40
60 Vdc U97 U98 U99 U100
110—127 Vdc U41 U42 U43 U44
220—250 Vdc U45 U46 U47 U48
Right-Pole Mounting DC Ratings(2)(3)
12 Vdc U77 U78 U79 U80
24 Vdc U81 U82 U83 U84
48 Vdc U85 U86 U87 U88
60 Vdc U101 U102 U103 U104
110—127 Vdc U89 U90 U91 U92
220—250 Vdc U93 U94 U95 U96

NOTES:
(1) Standard pigtail lead exit location.
(2) Standard mounting location.
(3) Not for use on right pole of four-pole circuit breaker.
F-Frame circuit breakers are factory sealed. Underwriters Laboratories requires that internal accessories be installed at the factory.
Internal accessories are UL listed for factory installation under E7819.
Where local codes and standards permit and UL listing is not required, internal accessories can be field installed. Accessory installation should be done before the circuit breaker is mounted and connected.

F-Frame Field Mounted Undervoltage Release Mechanism

Voltage Rating
(AC Freq. = 50/60 Hz)
F-Frame Breaker
Factory Installation Kits(1)
F-Frame Breaker HMCP
Pigtail Leads Terminal Block Pigtail Leads Terminal Block
Left-Pole Mounting AC Ratings
12 Vac UVH1LP02K UVH1LT02K MUVH1LP02K MUVH1LT02K
24 Vac UVH1LP03K UVH1LT03K MUVH1LP03K MUVH1LT03K
48 Vac UVH1LP22K UVH1LT22K MUVH1LP22K MUVH1LT22K
60 Vac UVH1LP24K UVH1LT24K MUVH1LP24K MUVH1LT24K
110–127 Vac UVH1LP08K UVH1LT08K MUVH1LP08K MUVH1LT08K
208–240 Vac UVH1LP11K UVH1LT11K MUVH1LP11K MUVH1LT11K
380–480 Vac UVH1LP15K UVH1LT15K MUVH1LP15K MUVH1LT15K
525–600 Vac UVH1LP18K UVH1LT18K MUVH1LP18K MUVH1LT18K
Right-Pole Mounting AC Ratings(2)(3)
12 Vac UVH1RP02K UVH1RT02K MUVH1RP02K MUVH1RT02K
24 Vac UVH1RP03K UVH1RT03K MUVH1RP03K MUVH1RT03K
48 Vac UVH1RP22K UVH1RT22K MUVH1RP22K MUVH1RT22K
60 Vac UVH1RP24K UVH1RT24K MUVH1RP24K MUVH1RT24K
110–127 Vac UVH1RP08K UVH1RT08K MUVH1RP08K MUVH1RT08K
208–240 Vac UVH1RP11K UVH1RT11K MUVH1RP11K MUVH1RT11K
380–480 Vac UVH1RP15K UVH1RT15K MUVH1RP15K MUVH1RT15K
525–600 Vac UVH1RP18K UVH1RT18K MUVH1RP18K MUVH1RT18K
Left-Pole Mounting DC Ratings
12 Vdc UVH1LP20K UVH1LT20K MUVH1LP20K MUVH1LT20K
24 Vdc UVH1LP21K UVH1LT21K MUVH1LP21K MUVH1LT21K
48 Vdc UVH1LP22K UVH1LT22K MUVH1LP22K MUVH1LT22K
60 Vdc UVH1LP24K UVH1LT24K MUVH1LP24K MUVH1LT24K
110–127 Vdc UVH1LP26K UVH1LT26K MUVH1LP26K MUVH1LT26K
220–250 Vdc UVH1LP28K UVH1LT28K MUVH1LP28K MUVH1LT28K
Right-Pole Mounting DC Ratings(2)(3)
12 Vdc UVH1RP20K UVH1RT20K MUVH1RP20K MUVH1RT20K
24 Vdc UVH1RP21K UVH1RT21K MUVH1RP21K MUVH1RT21K
48 Vdc UVH1RP22K UVH1RT22K MUVH1RP22K MUVH1RT22K
60 Vdc UVH1RP22K UVH1RT22K MUVH1RP22K MUVH1RT22K
110–127 Vdc UVH1RP26K UVH1RT26K MUVH1RP26K MUVH1RT26K
220–250 Vdc UVH1RP28K UVH1RT28K MUVH1RP28K MUVH1RT28K

NOTES:
(1) Not listed with Underwriters Laboratories, for field installation.
(2) Standard mounting location.
(3) Not for use on right pole of four-pole circuit breaker.

J-Frame and HMCP (J) Undervoltage Release Mechanism

Voltage Rating
(AC Freq. = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(3)
Same Side Rear(2) Opposite Side Terminal
Block(1)
Same Side
Pigtail Leads Terminal Block(3)
Left-Pole Mounting AC Ratings(4)
12 Vac U05 U06 U07 U08 UVH2LP02K UVH2LT02K
24 Vac U09 U10 U11 U12 UVH2LP03K UVH2LT03K
48—60 Vac U13 U14 U15 U16 UVH2LP05K UVH2LT05K
110—127 Vac U17 U18 U19 U20 UVH2LP08K UVH2LT08K
208—240 Vac U21 U22 U23 U24 UVH2LP11K UVH2LT11K
380—480 Vac U25 U26 U27 U28 UVH2LP15K UVH2LT15K
Right-Pole Mounting AC Ratings(3)
12 Vac U37 U38 U39 U40 UVH2RP02K UVH2RT02K
24 Vac U41 U42 U43 U44 UVH2RP03K UVH2RT03K
48—60 Vac U45 U46 U47 U48 UVH2RP05K UVH2RT05K
110—127 Vac U49 U50 U51 U52 UVH2RP08K UVH2RT08K
208—240 Vac U53 U54 U55 U56 UVH2RP11K UVH2RT11K
380—480 Vac U57 U58 U59 U60 UVH2RP15K UVH2RT15K
Left-Pole Mounting DC Ratings(4)
12 Vdc T01 T02 T03 T04 UVH2LP20K UVH2LT20K
24 Vdc T05 T06 T07 T08 UVH2LP21K UVH2LT21K
48—60 Vdc T09 T10 T11 T12 UVH2LP23K UVH2LT23K
110—127 Vdc T13 T14 T15 T16 UVH2LP26K UVH2LT26K
220—250 Vdc T17 T18 T19 T20 UVH2LP28K UVH2LT28K
Right-Pole Mounting DC Ratings(3)
12 Vdc T21 T22 T23 T24 UVH2RP20K UVH2RT20K
24 Vdc T25 T26 T27 T28 UVH2RP21K UVH2RT21K
48—60 Vdc T29 T30 T31 T32 UVH2RP23K UVH2RT23K
110—127 Vdc T33 T34 T35 T36 UVH2RP26K UVH2RT26K
220—250 Vdc T37 T38 T39 T40 UVH2RP28K UVH2RT28K

NOTES:
(1) For electrical rating data for manual, automatic and electrical reset undervoltage release mechanisms, refer to Eaton.
(2) Listed with Underwriters Laboratories for field installation under E64983.
(3) Not for use on right pole of four-pole circuit breakers.
(4) Standard mounting location—leads exit rear of breaker.

K-Frame and HMCP (K) Undervoltage Release Mechanism

Voltage Rating
(AC Freq. = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(1)
Same Side Rear(2) Opposite Side Terminal
Block
Same Side
Pigtail Leads Terminal Block
Left-Pole Mounting AC Ratings(2)
12 Vac U05 U06 U07 U08 UVH3LP02K UVH3LT02K
24 Vac U09 U10 U11 U12 UVH3LP03K UVH3LT03K
48—60 Vac U13 U14 U15 U16 UVH3LP05K UVH3LT05K
110—127 Vac U17 U18 U19 U20 UVH3LP08K UVH3LT08K
208—240 Vac U21 U22 U23 U24 UVH3LP11K UVH3LT11K
380—480 Vac U25 U26 U27 U28 UVH3LP15K UVH3LT15K
Right-Pole Mounting AC Ratings(3)(4)(5)
12 Vac U37 U38 U39 U40 UVH3RP02K UVH3RT02K
24 Vac U41 U42 U43 U44 UVH3RP03K UVH3RT03K
48—60 Vac U45 U46 U47 U48 UVH3RP05K UVH3RT05K
110—127 Vac U49 U50 U51 U52 UVH3RP08K UVH3RT08K
208—240 Vac U53 U54 U55 U56 UVH3RP11K UVH3RT11K
380—480 Vac U57 U58 U59 U60 UVH3RP15K UVH3RT15K
Left-Pole Mounting DC Ratings(2)
12 Vdc T01 T02 T03 T04 UVH3LP20K UVH3LT20K
24 Vdc T05 T06 T07 T08 UVH3LP21K UVH3LT21K
48—60 Vdc T09 T10 T11 T12 UVH3LP23K UVH3LT23K
110—127 Vdc T13 T14 T15 T16 UVH3LP26K UVH3LT26K
220—250 Vdc T17 T18 T19 T20 UVH3LP28K UVH3LT28K
Right-Pole Mounting DC Ratings(3)(4)(5)
12 Vdc T21 T22 T23 T24 UVH3RP20K UVH3RT20K
24 Vdc T25 T26 T27 T28 UVH3RP21K UVH3RT21K
48—60 Vdc T29 T30 T31 T32 UVH3RP23K UVH3RT23K
110—127 Vdc T33 T34 T35 T36 UVH3RP26K UVH3RT26K
220—250 Vdc T37 T38 T39 T40 UVH3RP28K UVH3RT28K

NOTES:
(1) Listed with Underwriters Laboratories, for field installation under E64983.
(2) Standard mounting location—leads exit rear of breaker.
(3) For use with KT (thermal-magnetic) trip units only.
(4) Not for use on right pole of four-pole circuit breaker.
(5) Breakers with K-Frame OPTIM 550 can only accept accessories in left pole.

L-, HMCP (L) and (M)-Frames and Undervoltage Release Mechanism

Voltage Rating
(AC Freq. = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(1)
Same Side Rear(2) Opposite Side Terminal
Block
Same Side
Pigtail Leads Terminal Block
Left-Pole Mounting AC Ratings(2)
12 Vac U05 U06 U07 U08 UVH4LP02K UVH4LT02K
24 Vac U09 U10 U11 U12 UVH4LP03K UVH4LT03K
48—60 Vac U13 U14 U15 U16 UVH4LP05K UVH4LT05K
110—127 Vac U17 U18 U19 U20 UVH4LP08K UVH4LT08K
208—240 Vac U21 U22 U23 U24 UVH4LP11K UVH4LT11K
380—480 Vac U25 U26 U27 U28 UVH4LP15K UVH4LT15K
Right-Pole Mounting AC Ratings(3)(4)
12 Vac U37 U38 U39 U40 UVH4RP02K UVH4RT02K
24 Vac U41 U42 U43 U44 UVH4RP03K UVH4RT03K
48—60 Vac U45 U46 U47 U48 UVH4RP05K UVH4RT05K
110—127 Vac U49 U50 U51 U52 UVH4RP08K UVH4RT08K
208—240 Vac U53 U54 U55 U56 UVH4RP11K UVH4RT11K
380—480 Vac U57 U58 U59 U60 UVH4RP15K UVH4RT15K
Left-Pole Mounting DC Ratings(2)
12 Vdc T01 T02 T03 T04 UVH4LP20K UVH4LT20K
24 Vdc T05 T06 T07 T08 UVH4LP21K UVH4LT21K
48—60 Vdc T09 T10 T11 T12 UVH4LP23K UVH4LT23K
110—127 Vdc T13 T14 T15 T16 UVH4LP26K UVH4LT26K
220—250 Vdc T17 T18 T19 T20 UVH4LP28K UVH4LT28K
Right-Pole Mounting DC Ratings(3)(4)
12 Vdc T21 T22 T23 T24 UVH4RP20K UVH4RT20K
24 Vdc T25 T26 T27 T28 UVH4RP21K UVH4RT21K
48—60 Vdc T29 T30 T31 T32 UVH4RP23K UVH4RT23K
110—127 Vdc T33 T34 T35 T36 UVH4RP26K UVH4RT26K
220—250 Vdc T37 T38 T39 T40 UVH4RP28K UVH4RT28K

NOTES:
(1) Listed with Underwriters Laboratories for field installation under E64983.
(2) Standard mounting location—leads exit rear of breaker.
(3) For use with LT (thermal-magnetic) trip units only.
(4) Not for use on right pole of four-pole circuit breaker.

N-Frame and HMCP (N) Undervoltage Release Mechanism

Voltage Rating
(AC Freq. = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(1)
Same Side Rear(2) Opposite Side Terminal
Block
Same Side
Pigtail Leads Terminal Block
Left-Pole Mounting AC Ratings(2)
12 Vac U05 U06 U07 U08 UVH5LP02K UVH5LT02K
24 Vac U09 U10 U11 U12 UVH5LP03K UVH5LT03K
48—60 Vac U13 U14 U15 U16 UVH5LP05K UVH5LT05K
110—127 Vac U17 U18 U19 U20 UVH5LP08K UVH5LT08K
208—240 Vac U21 U22 U23 U24 UVH5LP11K UVH5LT11K
380—480 Vac U25 U26 U27 U28 UVH5LP29K UVH5LT29K
Left-Pole Mounting DC Ratings(2)
12 Vdc T01 T02 T03 T04 UVH5LP20K UVH5LT20K
24 Vdc T05 T06 T07 T08 UVH5LP21K UVH5LT21K
48—60 Vdc T09 T10 T11 T12 UVH5LP23K UVH5LT23K
110—127 Vdc T13 T14 T15 T16 UVH5LP26K UVH5LT26K
220—250 Vdc T17 T18 T19 T20 UVH5LP28K UVH5LT28K

R-Frame Undervoltage Release Mechanism (RH only)

Voltage Rating
(AC Freq. = 50/60 Hz)
Factory Mounted
Connection Type and Location
18-Inch (457.2 mm) Pigtail Leads
Field Mounted
Field Installation Kits(3)
Suffix Number(4) Part Number(4)
12 Vac U37 UVH6RP02K
24 Vac U41 UVH6RP03K
48–60 Vac U45 UVH6RP05K
110–127 Vac U49 UVH6RP08K
208–240 Vac U53 UVH6RP11K
380–500 Vac U57 UVH6RP29K
12 Vdc T21 UVH6RP20K
24 Vdc T25 UVH6RP21K
48–60 Vdc T29 UVH6RP23K
110–125 Vdc T33 UVH6RP26K
220–250 Vdc T37 UVH6RP28K

NOTES:
(1) Listed with Underwriters Laboratories for field installation under E64983.
(2) Standard mounting location—leads exit rear of breaker.
(3) Endurance: 500 electrical operations plus 2500 mechanical operations.
(4) Pigtail wire size: 18 AWG (0.82 mm2). Leads are orange and brown.

Accessory Terminal Block (R-Frame)

R-Frame Accessory Terminal Block(1)

Accessory Terminal Block (R-Frame)

Factory Installed Field Mounted
Q01 TBRDK

Number of Control Wires for Each Internally Mounted Accessory

Type of Accessory Number of Contacts
per Single Accessory
Required Number
of Wires
Auxiliary switch 2a/2b 6
4a/4b 12
Alarm (Signal)/
Lockout switch
1m/1b 6
2m/2b 12
Shunt trip N/A 2
Low energy shunt N/A 2
Undervoltage release mechanism N/A 2

PowerNet and Zone Interlock Kits (OPTIM 550 Only) K-, L- and N-Frames

PowerNet Interlock Kit(2)

PowerNet and Zone Interlock Kits

Circuit Breaker Factory Install Suffix Part Number
K-Frame PN ICK550K
L-Frame PN ICK550L
N-Frame PN ICK550N

Zone Interlock/Ground Kit(2)(3)

Circuit Breaker Factory Install Suffix Part Number
K-Frame ZG ZGK550K
L-Frame ZG ZGK550L
N-Frame ZG ZGK550N

PowerNet and Zone Interlock/Ground Kit(2)(3)

Circuit Breaker Factory Install Suffix Part Number
K-Frame ZGP ZGPK550K
L-Frame ZGP ZGPK550L
N-Frame ZGP ZGPK550N

NOTES:
(1) One 24-point accessory terminal block provided with circuit breaker when ordered factory installed or shipped from warehouse as separate item when ordered for field installation. See Digitrip RMS master connection diagram (IL 29C714).
(2) Installation of these kits restrict any other attachments from being installed in the RH pole.
(3) Includes a ground fault alarm signal that can drive the ground fault alarm unit (catalog number GFAU).