Eaton
|
|
![]() |
Series-C Frame Size - J Part Index CLICK HERE |
Type JD (3-Pole) Shown |
Number of Poles |
Amperes | Interrupting Capacity |
Type of Trip |
Terminals |
---|---|---|---|---|
3 | 225 | High Interrupting 600 Vac Rated 65 kAIC at 480 Vac |
Adjustable Thermal-Magnetic |
Standard |
UL 489 Interrupting Capacity Ratings | |||||||
Circuit Breaker Type |
Number of Poles |
Interrupting Capacity (kA Symmetrical Amperes) | |||||
---|---|---|---|---|---|---|---|
Volts AC (50/60 Hz) | Volts DC | ||||||
240 | 480 | 600 | 125 | 250(1)(2) | |||
JDB | 2, 3 | 65 | 35 | 18 | — | 10 | |
JD | 2, 3, 4 | 65 | 35 | 18 | — | 10 | |
HJD | 2, 3, 4 | 100 | 65 | 25 | — | 22 | |
JDC(3) | 2, 3, 4 | 200 | 100 | 35 | — | 22 | |
IEC 157-1 (P1) Interrupting Capacity Ratings | |||||||
Circuit Breaker Type |
Number of Poles |
Interrupting Capacity (kA Symmetrical Amperes) | |||||
Volts AC (50/60 Hz) | Volts DC | ||||||
240 | 380 | 415 | 600 | 125 | 250(1)(2) | ||
JD | 2, 3, 4 | 65 | 35 | 35 | — | — | 10 |
HJD | 2, 3, 4 | 100 | 65 | 65 | — | — | 22 |
JDC | 2, 3, 4 | 200 | 100 | 100 | — | — | 22 |
NOTES:
(1) Two-pole circuit breaker or two outside poles of three-pole circuit breaker.
(2) Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
(3) Current limiting.
![]() |
Number of Poles | Width | Height | Depth |
---|---|---|---|
2, 3 | 4.13 (105.0) | 10.00 (254.0) | 4.06 (104.1) |
4 | 5.50 (139.7) | 10.00 (254.0) | 4.06 (104.1) |