Eaton Molded Case Circuit Breaker Series-C, K-Frame
K-Frame (70–400 Amperes)
Product Description
- K-Frame (70–400 Amperes)
- K-Frame circuit breakers are available as individual components (frame, trip unit, terminals), or factory assembled complete breakers
- K-Frame circuit breakers with non-interchangeable trip units are suitable for reverse feed use
Types KD, HKD and KDC Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units
Maximum Continuous Ampere Rating at 40°C |
Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac Factory Assembled Circuit Consisting of Frame, Trip Unit and Terminals(1) Part Number |
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac Factory Assembled Circuit Consisting of Frame, Trip Unit and Terminals(1) Part Number |
Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac Factory Assembled Circuit Consisting of Frame, Trip Unit and Terminals(1) Part Number |
Thermal-Magnetic Trip Unit Only(1) For Use with Standard or High or Ultra High Interrupting Frames Part Number |
Standard Terminals Only PartNumber |
Two-Pole | |||||
100 | KD2100 | HKD2100 | KDC2100 | KT2100T | TA300K (2) |
125 | KD2125 | HKD2125 | KDC2125 | KT2125T | TA300K (2) |
150 | KD2150 | HKD2150 | KDC2150 | KT2150T | TA300K (2) |
175 | KD2175 | HKD2175 | KDC2175 | KT2175T | TA300K (2) |
200 | KD2200 | HKD2200 | KDC2200 | KT2200T | TA300K (2) |
225 | KD2225 | HKD2225 | KDC2225 | KT2225T | TA300K (2) |
250 | KD2250 | HKD2250 | KDC2250 | KT2250T | TA350K (2) |
300 | KD2300 | HKD2300 | KDC2300 | KT2300T | TA350K (2) |
350 | KD2350 | HKD2350 | KDC2350 | KT2350T | TA350K (2) |
400 | KD2400 | HKD2400 | KDC2400 | KT2400T | 2TA400K(3) |
Three-Pole | |||||
100 | KD3100 | HKD3100 | KDC3100 | KT3100T | TA300K (2) |
125 | KD3125 | HKD3125 | KDC3125 | KT3125T | TA300K (2) |
150 | KD3150 | HKD3150 | KDC3150 | KT3150T | TA300K(2) |
175 | KD3175 | HKD3175 | KDC3175 | KT3175T | TA300K (2) |
200 | KD3200 | HKD3200 | KDC3200 | KT3200T | TA300K (2) |
225 | KD3225 | HKD3225 | KDC3225 | KT3225T | TA300K (2) |
250 | KD3250 | HKD3250 | KDC3250 | KT3250T | TA350K (2) |
300 | KD3300 | HKD3300 | KDC3300 | KT3300T | TA350K(2) |
350 | KD3350 | HKD3350 | KDC3350 | KT3350T | TA350K(2) |
400 | KD3400 | HKD3400 | KDC3400 | KT3400T | 3TA400K(3) |
Four-Pole | |||||
100 | KD4100 | HKD4100 | KDC4100 | KT4100T | TA300K (2) |
125 | KD4125 | HKD4125 | KDC4125 | KT4125T | TA300K (2) |
175 | KD4175 | HKD4175 | KDC4175 | KT4175T | TA300K(2) |
200 | KD4200 | HKD4200 | KDC4200 | KT4200T | TA300K (2) |
225 | KD4225 | HKD4225 | KDC4225 | KT4225T | TA300K (2) |
250 | KD4250 | HKD4250 | KDC4250 | KT4250T | TA350K (2) |
300 | KD4300 | HKD4300 | KDC4300 | KT4300T | TA350K(2) |
350 | KD4350 | HKD4350 | KDC4350 | KT4350T | TA350K(2) |
400 | KD4400 | HKD4400 | KDC4400 | KT4400T | 4TA400K(3) |
NOTES:
(1) Magnetic trip adjustable 5–10 times continuous ampere rating.
(2) Individually packed.
(3) 2TA400K, 3TA400K and 4TA400K terminal kits contain one terminal for each pole and one terminal cover.
Types KD, HKD and KDC Thermal-Magnetic Circuit Breakers—Frame Only
Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac Part Number |
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac Part Number |
Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac Part Number |
Two-Pole | ||
KD2400F | HKD2400F | KDC2400F |
Three-Pole | ||
KD3400F | HKD3400F | KDC3400F |
Four-Pole | ||
KD4400F | HKD4400F | KDC4400F |
Types KD, HKD and KDC Electronic Circuit Breakers with Interchangeable 310+ Trip Units—Three-Pole(1)
Max. Cont. Ampere Rating at 40°C |
Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac |
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac |
Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac |
Digitrip RMS 310+ Trip Unit Only(2) | Adjustable Short Time Pickup with I2t Short Delay and Ground Fault Protection |
Independently Adjustable Short Time Pickup and Delay and Ground Fault Protection |
|
Standard Adjustable Short Time Pickup with I2t Short Delay Ramp |
Options Independently Adjustable Short Time Pickup and Delay |
||||||
125 | KD3400F | HKD3400F | KDC3400F | KES3125LS | KES3125LSI | KES3125LSG | KES3125LSIG |
250 | KD3400F | HKD3400F | KDC3400F | KES3250LS | KES3250LSI | KES3250LSG | KES3250LSIG |
400 | KD3400F | HKD3400F | KDC3400F | KES3400LS | KES3400LSI | KES3400LSG | KES3400LSIG |
Types KD, HKD and KDC Electronic Circuit Breakers with Interchangeable 310+ Trip Units—Four-Pole(3)(4)
Max. Cont. Ampere Rating at 40°C |
Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac |
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac |
Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac |
Digitrip RMS 310+ Trip Unit Only(2) | Adjustable Short Time Pickup with I2t Short Delay and Ground Fault Protection |
Independently Adjustable Short Time Pickup and Delay and Ground Fault Protection |
|
Adjustable Short Time Pickup with I2t Short Delay Ramp |
Independently Adjustable Short Time Pickup and Delay |
||||||
125 | KD4400F | HKD4400F | KDC4400F | KES4125LS | KES4125LSI | — | — |
250 | KD4400F | HKD4400F | KDC4400F | KES4250LS | KES4250LSI | — | — |
400 | KD4400F | HKD4400F | KDC4400F | KES4400LS | KES4400LSI | — | — |
NOTES:
(1) Three-pole KES trip units are for use in three-pole frames only.
(2) For AC use only.
(3) Trip unit includes protected neutral pole. Use corresponding three-pole trip unit if protected neutral pole is not required.
(4) Fully rated neutral pole protection is standard. For 50% rated protection on neutral pole, add Suffix E to four-pole trip unit catalog number.
Type KDB with Digitrip 310+ Non-Interchangeable Trip Unit Suitable for Reverse Feed
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
Circuit Breaker Frame Including Digitrip RMS
310+ Electronic Tip Unit Less Terminals—Catalog Number L – Adjustable Long Delay Pickup (By Adjustable Rating Plug) S – Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Time (Flat Response) I – Adjustable Instantaneous Pickup by Setting Short Time Delay Time to Instantaneous G –Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response) |
|||
LS | LSI | LSG | LSIG | ||
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | |
Short Time Delay | — | I–300 ms | — | 0–300 ms | |
Ground Fault Pickup | — | — | Varies by frame | Varies by frame | |
Ground Fault Delay | — | — | 0–500 ms | 0–500 ms | |
125 | 3 | KDB3125FT33W | KDB3125FT32W | KDB3125FT35W | KDB3125FT36W |
250 | 3 | KDB3250FT33W | KDB3250FT32W | KDB3250FT35W | KDB3250FT36W |
400 | 3 | KDB3400FT33W | KDB3400FT32W | KDB3400FT35W | KDB3400FT36W |
Type HKDB with Digitrip 310+ Non-Interchangeable Trip Unit Suitable for Reverse Feed
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
Circuit Breaker Frame Including Digitrip RMS
310+ Electronic Tip Unit Less Terminals—Catalog Number L – Adjustable Long Delay Pickup (By Adjustable Rating Plug) S – Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Time (Flat Response) I – Adjustable Instantaneous Pickup by Setting Short Time Delay Time to Instantaneous G –Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response) |
|||
LS | LSI | LSG | LSIG | ||
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | |
Short Time Delay | — | I–300 ms | — | 0–300 ms | |
Ground Fault Pickup | — | — | Varies by frame | Varies by frame | |
Ground Fault Delay | — | — | 0–500 ms | 0–500 ms | |
125 | 3 | HKDB3125FT33W | HKDB3125FT32W | HKDB3125FT35W | HKDB3125FT36W |
250 | 3 | HKDB3250FT33W | HKDB3250FT32W | HKDB3250FT35W | HKDB3250FT36W |
400 | 3 | HKDB3400FT33W | HKDB3400FT32W | HKDB3400FT35W | HKDB3400FT36W |
Types DK and KDB Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip Units
Maximum Continuous Ampere Rating at 40°C |
240 Vac Rated, 250 Vdc Complete Circuit Breaker Without Line and Load Terminals |
With Line Terminals Only |
With Standard Line and Load Terminals Only |
600 Vac Rated, 250 Vdc Complete Circuit Breaker Without Line and Load Terminals |
With Standard Line and Load Terminals |
Two-Pole | |||||
100 | — | — | — | KDB2100W | KDB2100 |
125 | — | — | — | KDB2125W | KDB2125 |
150 | — | — | — | KDB2150W | KDB2150 |
175 | — | — | — | KDB2175W | KDB2175 |
200 | — | — | — | KDB2200W | KDB2200 |
225 | — | — | — | KDB2225W | KDB2225 |
250 | DK2250W | DK2250Y | DK2250 | KDB2250W | KDB2250 |
300 | DK2300W | DK2300Y | DK2300 | KDB2300W | KDB2300 |
350 | DK2350W | DK2350Y | DK2350 | KDB2350W | KDB2350 |
400 | DK2400W | DK2400Y | DK2400 | KDB2400W | KDB2400 |
Three-Pole | |||||
100 | — | — | — | KDB3100W | KDB3100 |
125 | — | — | — | KDB3125W | KDB3125 |
150 | — | — | — | KDB3150W | KDB3150 |
175 | — | — | — | KDB3175W | KDB3175 |
200 | — | — | — | KDB3200W | KDB3200 |
225 | — | — | — | KDB3225W | KDB3225 |
250 | DK3250W | DK3250Y | DK3250 | KDB3250W | KDB3250 |
300 | DK3300W | DK3300Y | DK3300 | KDB3300W | KDB3300 |
350 | DK3350W | DK3350Y | DK3350 | KDB3350W | KDB3350 |
400 | DK3400W | DK3400Y | DK3400 | KDB3400W | KDB3400 |
Molded Case Switches
Eaton’s molded case switches are used as compact switches in applications requiring high current switching capabilities. Molded case switches are constructed of circuit breaker components and are of the high instantaneous automatic type. Molded case switches are listed in accordance with Underwriters Laboratories Standard UL 489.
Maximum Continuous Ampere Rating at 40°C |
240 Vac Maximum, 250 Vdc | 600 Vac Maximum, 250 Vdc | 600 Vac Maximum, 250 Vdc |
Complete Circuit Breaker with Standard Line and Load Terminals |
Complete Circuit Breaker with Standard Line and Load Terminals |
Complete Circuit Breaker with Standard Line and Load Terminals. Suitable for Reverse Feed Use |
|
Two-Pole | |||
400 | DK2400K | KD2400K | KDB2400K |
— | HKD2400K | HKDB2400K | |
Three-Pole | |||
400 | DK3400K | KD3400K | KDB3400K |
— | HKD3400K | HKDB3400K | |
Four-Pole | |||
400 | — | KD4400K | KDB4400K |
— | HKD4400K | HKDB4400K |
NOTES:
Molded case switches may open above 4000 amperes.
100% Rated Types CKD and CHKD Electronic Circuit Breakers—Three-Pole
The NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at the 75°C ampacity. All 100% rated circuit breakers have electronic trip units.
Maximum Continuous Ampere Rating at 40°C |
Circuit Breaker Frame Only | Digitrip RMS 310+ Trip Unit Only | Adjustable Short Time Pickup with I2t Short Delay and Ground Fault Protection |
Independently Adjustable Short Time Pickup and Delay and Ground Fault Protection |
||
Standard Interrupting Capacity 35 kAIC at 480 Vac |
High Interrupting Capacity 65 kAIC at 480 Vac |
Standard Adjustable Short Time Pickup with I2t Short Delay Ramp |
Options Independently Adjustable Short Time Pickup and Delay |
|||
125 | CKD3400F | CHKD3400F | KES3125LS | KES3125LSI | KES3125LSG | KES3125LSIG |
250 | CKD3400F | CHKD3400F | KES3250LS | KES3250LSI | KES3250LSG | KES3250LSIG |
400 | CKD3400F | CHKD3400F | KES3400LS | KES3400LSI | KES3400LSG | KES3400LSIG |
Digitrip OPTIM 550 Electronic Circuit Breakers with Interchangeable Rating Plug
Maximum Continuous Ampere Rating at 40°C |
Circuit Breaker Frame Only L – Adjustable Long Delay Pickup (Ir) with Adjustable Long Delay Time (I2t or I4t Response)(1) S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I2t or Flat Response) A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I2t or Flat Response) |
Digitrip OPTIM Rating Plug Only | |||
LSI | LSIG | LSIA | Ampere Rating |
Fixed Rating Plug |
|
Three-Pole Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac | |||||
125 | KD3125T52W | KD3125T56W | KD3125T57W | 70 | ORPK125A70 |
90 | ORPK125A90 | ||||
100 | ORPK125A100 | ||||
110 | ORPK125A110 | ||||
125 | ORPK125A125 | ||||
250 | KD3250T52W | KD3250T56W | KD3250T57W | 125 | ORPK025A125 |
150 | ORPK025A150 | ||||
175 | ORPK025A175 | ||||
200 | ORPK025A200 | ||||
225 | ORPK025A225 | ||||
250 | ORPK025A250 | ||||
400 | KD3400T52W | KD3400T56W | KD3400T57W | 200 | ORPK40A200 |
225 | ORPK40A225 | ||||
250 | ORPK40A250 | ||||
300 | ORPK40A300 | ||||
350 | ORPK40A350 | ||||
400 | ORPK40A400 |
NOTES:
(1) Long delay I4t response selection limits short delay time to flat response.
(2) Zone interlocking, PowerNet, or both features can be added at the factory by adding suffixes ZG, PN or ZGP respectively to above part number.
Digitrip OPTIM 550 Electronic Circuit Breakers with Interchangeable Rating Plug
Maximum Continuous Ampere Rating at 40°C |
Circuit Breaker Frame Only L – Adjustable Long Delay Pickup (Ir) with Adjustable Long Delay Time (I2t or I4t Response)(1) S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I2t or Flat Response) A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I2t or Flat Response) |
Digitrip OPTIM Rating Plug Only | |||
OPTIM 550(2)
LSI |
LSIG | LSIA | Ampere Rating |
Fixed Rating Plug |
|
Three-Pole High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac | |||||
125 | HKD3125T52W | HKD3125T56W | HKD3125T57W | 70 | ORPK125A70 |
90 | ORPK125A90 | ||||
100 | ORPK125A100 | ||||
110 | ORPK125A110 | ||||
125 | ORPK125A125 | ||||
250 | HKD3250T52W | HKD3250T56W | HKD3250T57W | 125 | ORPK025A125 |
150 | ORPK025A150 | ||||
175 | ORPK025A175 | ||||
200 | ORPK025A200 | ||||
225 | ORPK025A225 | ||||
250 | ORPK025A250 | ||||
400 | HKD3400T52W | HKD3400T56W | HKD3400T57W | 200 | ORPK40A200 |
225 | ORPK40A225 | ||||
250 | ORPK40A250 | ||||
300 | ORPK40A300 | ||||
350 | ORPK40A350 | ||||
400 | ORPK40A400 | ||||
Three-Pole Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac | |||||
125 | KDC3125T52W | KDC3125T56W | KDC3125T57W | 70 | ORPK125A70 |
90 | ORPK125A90 | ||||
100 | ORPK125A100 | ||||
110 | ORPK125A110 | ||||
125 | ORPK125A125 | ||||
250 | KDC3250T52W | KDC3250T56W | KDC3250T57W | 125 | ORPK025A125 |
150 | ORPK025A150 | ||||
175 | ORPK025A175 | ||||
200 | ORPK025A200 | ||||
225 | ORPK025A225 | ||||
250 | ORPK025A250 | ||||
400 | KDC3400T52W | KDC3400T56W | KDC3400T57W | 200 | ORPK40A200 |
225 | ORPK40A225 | ||||
250 | ORPK40A250 | ||||
300 | ORPK40A300 | ||||
350 | ORPK40A350 | ||||
400 | ORPK40A400 |
NOTES:
(1) Long delay I4t response selection limits short delay time to flat response.
(2) Zone interlocking, PowerNet, or both features can be added at the factory by adding suffixes ZG, PN or ZGP respectively to above part number.
Digitrip OPTIM 1050 Electronic Circuit Breakers with Interchangeable Rating Plug
Order as individual components: breaker frame (which includes trip unit), rating plug, terminals.
Maximum Continuous Ampere Rating at 40°C |
Circuit Breaker Frame Only L – Adjustable Long Delay Pickup (Ir) with Adjustable Long Delay Time (I2t or I4t Response)(1) S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I2t or Flat Response) A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I2t or Flat Response) |
Digitrip OPTIM Rating Plug Only | ||
OPTIM 550(2)
LSIG |
LSIA | Ampere Rating |
Fixed Rating Plug |
|
Three-Pole Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac | ||||
125 | KD3125T106W | KD3125T107W | 70 | ORPK125A70 |
90 | ORPK125A90 | |||
100 | ORPK125A100 | |||
110 | ORPK125A110 | |||
125 | ORPK125A125 | |||
250 | KD3250T106W | KD3250T107W | 125 | ORPK025A125 |
150 | ORPK025A150 | |||
175 | ORPK025A175 | |||
200 | ORPK025A200 | |||
225 | ORPK025A225 | |||
250 | ORPK025A250 | |||
400 | KD3400T106W | KD3400T107W | 200 | ORPK40A200 |
225 | ORPK40A225 | |||
250 | ORPK40A250 | |||
300 | ORPK40A300 | |||
350 | ORPK40A350 | |||
400 | ORPK40A400 | |||
Three-Pole High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac | ||||
125 | HKD3125T106W | HKD3125T107W | 70 | ORPK125A70 |
90 | ORPK125A90 | |||
100 | ORPK125A100 | |||
110 | ORPK125A110 | |||
125 | ORPK125A125 | |||
250 | HKD3250T106W | HKD3250T107W | 125 | ORPK025A125 |
150 | ORPK025A150 | |||
175 | ORPK025A175 | |||
200 | ORPK025A200 | |||
225 | ORPK025A225 | |||
250 | ORPK025A250 | |||
400 | HKD3400T106W | HKD3400T107W | 200 | ORPK40A200 |
225 | ORPK40A225 | |||
250 | ORPK40A250 | |||
300 | ORPK40A300 | |||
350 | ORPK40A350 | |||
400 | ORPK40A400 | |||
Three-Pole Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac | ||||
125 | KDC3125T106W | KDC3125T107W | 70 | ORPK125A70 |
90 | ORPK125A90 | |||
100 | ORPK125A100 | |||
110 | ORPK125A110 | |||
125 | ORPK125A125 | |||
250 | KDC3250T106W | KDC3250T107W | 125 | ORPK025A125 |
150 | ORPK025A150 | |||
175 | ORPK025A175 | |||
200 | ORPK025A200 | |||
225 | ORPK025A225 | |||
250 | ORPK025A250 | |||
400 | KDC3400T106W | KDC3400T107W | 200 | ORPK40A200 |
225 | ORPK40A225 | |||
250 | ORPK40A250 | |||
300 | ORPK40A300 | |||
350 | ORPK40A350 | |||
400 | ORPK40A400 |
NOTES:
(1) Long delay I4t response selection limits short delay time to flat response.
(2) Factory sealed.
100% Rated Digitrip OPTIM 550 Electronic Circuit Breakers with Interchangeable Rating Plug
Maximum Continuous Ampere Rating at 40°C |
Circuit Breaker Frame Only L – Adjustable Long Delay Pickup (Ir) with Adjustable Long Delay Time (I2t or I4t Response)(1) S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I2t or Flat Response) A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I2t or Flat Response) |
Digitrip OPTIM Rating Plug Only | |||
OPTIM 550(2)
LSI |
LSIG | LSIA | Ampere Rating |
Fixed Rating Plug |
|
Three-Pole Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac | |||||
125 | CKD3125T52W | CKD3125T56W | CKD3125T57W | 70 | ORPK125A70 |
90 | ORPK125A90 | ||||
100 | ORPK125A100 | ||||
110 | ORPK125A110 | ||||
125 | ORPK125A125 | ||||
250 | CKD3250T52W | CKD3250T56W | CKD3250T57W | 125 | ORPK025A125 |
150 | ORPK025A150 | ||||
175 | ORPK025A175 | ||||
200 | ORPK025A200 | ||||
225 | ORPK025A225 | ||||
250 | ORPK025A250 | ||||
400 | CKD3400T52W | CKD3400T56W | CKD3400T57W | 200 | ORPK40A200 |
225 | ORPK40A225 | ||||
250 | ORPK40A250 | ||||
300 | ORPK40A300 | ||||
350 | ORPK40A350 | ||||
400 | ORPK40A400 | ||||
Three-Pole High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac | |||||
125 | CHKD3125T52W | CHKD3125T56W | CHKD3125T57W | 70 | ORPK125A70 |
90 | ORPK125A90 | ||||
100 | ORPK125A100 | ||||
110 | ORPK125A110 | ||||
125 | ORPK125A125 | ||||
250 | CHKD3250T52W | CHKD3250T56W | CHKD3250T57W | 125 | ORPK025A125 |
150 | ORPK025A150 | ||||
175 | ORPK025A175 | ||||
200 | ORPK025A200 | ||||
225 | ORPK025A225 | ||||
250 | ORPK025A250 | ||||
400 | CHKD3400T52W | CHKD3400T56W | CHKD3400T57W | 200 | ORPK40A200 |
225 | ORPK40A225 | ||||
250 | ORPK40A250 | ||||
300 | ORPK40A300 | ||||
350 | ORPK40A350 | ||||
400 | ORPK40A400 |
NOTES:
(1) Long delay I4t response selection limits short delay time to flat response.
(2) Zone interlocking, PowerNet, or both features can be added at the factory by adding suffixes ZG, PN or ZGP respectively to above part number.
100% Rated Digitrip OPTIM 1050 Electronic Circuit Breakers with Interchangeable Rating Plug
Order as individual components: breaker frame (which includes trip unit), rating plug, terminals.
Maximum Continuous Ampere Rating at 40°C |
Circuit Breaker Frame Only L – Adjustable Long Delay Pickup (Ir) with Adjustable Long Delay Time (I2t or I4t Response)(1) S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I2t or Flat Response) A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I2t or Flat Response) |
Digitrip OPTIM Rating Plug Only | ||
OPTIM 550(2)
LSIG |
LSIA | Ampere Rating |
Fixed Rating Plug |
|
Three-Pole Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac | ||||
125 | CKD3125T106W | CKD3125T107W | 70 | ORPK125A70 |
90 | ORPK125A90 | |||
100 | ORPK125A100 | |||
110 | ORPK125A110 | |||
125 | ORPK125A125 | |||
250 | CKD3250T106W | CKD3250T107W | 125 | ORPK025A125 |
150 | ORPK025A150 | |||
175 | ORPK025A175 | |||
200 | ORPK025A200 | |||
225 | ORPK025A225 | |||
250 | ORPK025A250 | |||
400 | CKD3400T106W | CKD3400T107W | 200 | ORPK40A200 |
225 | ORPK40A225 | |||
250 | ORPK40A250 | |||
300 | ORPK40A300 | |||
350 | ORPK40A350 | |||
400 | ORPK40A400 | |||
Three-Pole High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac | ||||
125 | CHKD3125T106W | CHKD3125T107W | 70 | ORPK125A70 |
90 | ORPK125A90 | |||
100 | ORPK125A100 | |||
110 | ORPK125A110 | |||
125 | ORPK125A125 | |||
250 | CHKD3250T106W | CHKD3250T107W | 125 | ORPK025A125 |
150 | ORPK025A150 | |||
175 | ORPK025A175 | |||
200 | ORPK025A200 | |||
225 | ORPK025A225 | |||
250 | ORPK025A250 | |||
400 | CHKD3400T106W | CHKD3400T107W | 200 | ORPK40A200 |
225 | ORPK40A225 | |||
250 | ORPK40A250 | |||
300 | ORPK40A300 | |||
350 | ORPK40A350 | |||
400 | ORPK40A400 |
NOTES:
(1) Long delay I4t response selection limits short delay time to flat response.
(2) Factory sealed.
Accessories Selection Guide and Ordering Guide
Line and Load Terminals
Eaton’s line and load terminals provide wire connecting capabilities for specific ranges of continuous current ratings and wire types. All terminals comply with Underwriters Laboratories Standards UL 486A and UL 486B and CSA Standard C22.2 No. 65, or Electrical Bulletin 1165. Unless otherwise specified, K-Frame circuit breaker line and load terminals are shipped separately for field installation.
Ordering Information
K-Frame circuit breakers use Cu/AI terminals as standard. When optional copper or Cu/ AI terminals are required, order by catalog number. Specify if factory installation is required.
TA401K | TA400K, T400K | TA350K, T350K | TA300K, T300K | T400KCW, TA400KCW, TA401KCW |
TA402K, T402K |
Line and Load Terminals
Maximum Terminal Breaker Body Amperes Material |
Wire Type |
AWG Wire Range/No. Conductors |
Metric Wire Range mm2 |
Terminal | Terminals with Control Wire Termination |
|
Standard Cu/AI Pressure Terminals | ||||||
225 | Aluminum | Cu/AI | 3—350 (1) | 35—185 | TA300K(1) | — |
400 | Aluminum | Cu/AI | 250—500 (1) | 120—240 | TA350K(1) | — |
400 | Aluminum | Cu/AI | 3/0—250 (2) | 95—120 | 2TA400K(2)(3) | 2TA400KCW(2)(3) |
400 | Aluminum | Cu/AI | 3/0—250 (2) | 95—120 | 3TA400K(2)(4) | 3TA400KCW(2)(4) |
400 | Aluminum | Cu/AI | 3/0—250 (2) | 95—120 | 4TA400K(5)(6) | 4TA400KCW(5)(6) |
Optional Copper and Cu/AI Pressure Type Terminals | ||||||
225 | Copper | Cu | 3—350 (1) | 35—185 | T300K(1) | — |
400 | Copper | Cu | 250—500 (1) | 120—240 | T350K(1) | — |
400 | Copper | Cu | 3/0—250 (2) | 95—120 | 2T400K(3) | 2T400KCW(2)(3) |
3T400K(4) | 3T400KCW(2)(4) | |||||
4T400K(5) | 4T400KCW(5)(6) | |||||
400 | Aluminum | Cu/AI | 2/0—250 (2) or 2/0—500 (1) |
70—120 | 2TA401K(2)(3) | 2TA401KCW(2)(3) |
70—240 | 3TA401K(2)(4) | 3TA401KCW(2)(4) | ||||
70—240 | 4TA401K(5)(6) | 4TA401KCW(5)(6) | ||||
400 | Aluminum | Cu/AI | 500—750 (1) | 300—400 | 2TA402K(2)(3) | — |
3TA402K(2)(4) | — | |||||
4TA402K(5)(6) | — | |||||
400 | Copper | Cu | 500—750 (1) | — | 2T402K(2)(3) | — |
3T402K(2)(4) | — | |||||
4T402K(5)(6) | — |
NOTES:
(1) Individually packed.
(2) Terminal kits contain one terminal for each pole and one terminal cover.
(3) Two-pole kit.
(4) Three-pole kit.
(5) Three-pole kit.
(6) Terminal kits contain one terminal for each pole and three interphase barriers.