EATON Molded Case Circuit Breakers Series-G, Frame Size - RG
Series-G, RG-Frame (800–2500 Amperes)
- Complete Breaker (Includes Frame, Trip Unit, Standard Terminals and Mounting Hardware)
- All R-Frame circuit breakers are suitable for reverse feed use
70 kA at 415 Vac and 65 kA at 480 Vac
Type RGH with Digitrip 310+ High Interrupting Capacity—Ue Maximum 690 Vac, 70 kA Icu at 415 Vac
Circuit Breaker Frame Including Digitrip RMS 310 Electronic
Trip Unit with Adjustable Rating Plugs—Catalog Number(2)
L – Adjustable Long Delay Pickup (By Adjustable Rating Plug)
S – Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
LS | LSI | LSG(3) | LSIG(3) | Neutral CT for LSG & LSIG |
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | ||
Short Time Delay | — | I–300 ms | — | I–300 ms | ||
Ground Fault Pickup | — | — | 200–1200A | 200–1200A | ||
Ground Fault Delay | — | — | I–500 ms | I–500 ms | ||
1600(1) | 3 | RGH316033E | RGH316032E | RGH316035E | RGH316036E | RGFCT160A |
2000 | 3 | RGH320033E | RGH320032E | RGH320035E | RGH320036E | RGFCT200A |
2500 | 3 | RGH325033E | RGH325032E | RGH325035E | RGH325036E | RGFCT250A |
100 kA at Both 415 Vac and 480 Vac
Type RGH with Digitrip 310+ High Interrupting Capacity—Ue Maximum 690 Vac, 70 kA Icu at 415 Vac
Circuit Breaker Frame Including Digitrip RMS 310 Electronic
Trip Unit with Adjustable Rating Plugs—Catalog Number(2)
L – Adjustable Long Delay Pickup (By Adjustable Rating Plug)
S – Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
LS | LSI | LSG(3) | LSIG(3) |
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | |
Short Time Delay | — | I–300 ms | — | I–300 ms | |
Ground Fault Pickup | — | — | 200–1200A | 200–1200A | |
Ground Fault Delay | — | — | I–500 ms | I–500 ms | |
1600(1) | 4(4) | RGH416033E | RGH416032E | — | — |
2000 | 4(4) | RGH420033E | RGH420032E | — | — |
2500 | 4(4) | RGH425033E | RGH425032E | — | — |
100 kA at Both 415 Vac and 480 Vac
Type RGC with Digitrip 310+ Very High Interrupting Capacity—Ue Maximum 690 Vac, 100 kA Icu at 415 Vac
Circuit Breaker Frame Including Digitrip RMS 310 Electronic
Trip Unit with Adjustable Rating Plugs—Catalog Number(2)
L – Adjustable Long Delay Pickup (By Adjustable Rating Plug)
S – Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
LS | LSI | LSG(3) | LSIG(3) | Neutral CT for LSG & LSIG |
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | ||
Short Time Delay | — | I–300 ms | — | I–300 ms | ||
Ground Fault Pickup | — | — | 200–1200A | 200–1200A | ||
Ground Fault Delay | — | — | I–500 ms | I–500 ms | ||
1600(1) | 3 | RGC316033E | RGC316032E | RGC316035E | RGC316036E | RGFCT160A |
2000 | 3 | RGC320033E | RGC320032E | RGC320035E | RGC320036E | RGFCT200A |
2500 | 3 | RGC325033E | RGC325032E | RGC325035E | RGC325036E | RGFCT250A |
Type RGC with Digitrip 310+ Very High Interrupting Capacity—Ue Maximum 690 Vac, 100 kA Icu at 415 Vac, continued
Circuit Breaker Frame Including Digitrip RMS 310 Electronic
Trip Unit with Adjustable Rating Plugs—Catalog Number(2)
L – Adjustable Long Delay Pickup (By Adjustable Rating Plug)
S – Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
LS | LSI | LSG(3) | LSIG(3) |
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | |
Short Time Delay | — | I–300 ms | — | I–300 ms | |
Ground Fault Pickup | — | — | 200–1200A | 200–1200A | |
Ground Fault Delay | — | — | I–500 ms | I–500 ms | |
1600(1) | 4(4) | RGC416033E | RGC416032E | — | — |
2000 | 4(4) | RGC420033E | RGC420032E | — | — |
2500 | 4(4) | RGC425033E | RGC425032E | — | — |
NOTES:
(1) For SCR application, use 2000 ampere frame.
(2) Order terminals separately. Mounting hardware not included.
(3) Ground fault equipped trip units available with remote indicating panel. Add “R” to catalog number, for example, “RGH316035RW.”
(4) Unprotected left pole neutral. Add “P” to catalog number for 100% protected left pole neutral, add “E” for 60% protected, for example, “RGH416033PW,” “RGH416033EW.”
RG MCCBs have English threading on line and load conductors. Use suffix “M” for metric threading.
Molded Case Switches(5)
Ampere Rating | Number of Poles | Part Number |
1600 | 3 | RGK3160KSE |
2000 | 3 | RGK3200KSE |
1600 | 4 | RGK4160KSE |
2000 | 4 | RGK4200KSE |
NOTES:
(1) For SCR application, use 2000 ampere frame.
(2) Order terminals separately. Mounting hardware not included.
(3) Ground fault equipped trip units available with remote indicating panel. Add “R” to catalog number, for example, “RGH316035RW.”
(4) Unprotected left pole neutral. Add “P” to catalog number for 100% protected left pole neutral, add “E” for 60% protected, for example, “RGH416033PW,” “RGH416033EW.”
(5) Molded case switch will trip above 17,500 amperes.
RG MCCBs have English threading on line and load conductors. Use suffix “M” for metric threading.
Type RG with Digitrip 610 and 910
Circuit Breaker Frame Including Digitrip RMS 610 and 910 Electronic Trip Unit with Rating Plugs Order as Individual Component—Catalog Number(1)
L – Adjustable Long Delay Pickup (Ir) with Adjustable Long Delay Time
S – Adjustable Short Delay Pickup with Adjustable
Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable
Ground Fault Time Delay (I2t or Flat Response)
Maximum Continuous Ampere Rating at 40°C |
Num. of Poles |
LI | LS | LSI | LIG | LSG | LSIG | Digitrip RMS Interchangeable Rating Plug (Order as Individual Component) Fixed Rating Plug |
|
Long Delay Pickup |
0.5–1.0 x In | 0.5–I.0n | 0.5–1.0 x In | 0.5–1.0 x In | 0.5–1.0 x In | 0.5–1.0 x In | |||
Long Delay Time |
2–24 Seconds |
2–24 Seconds |
2–24 Seconds |
2–24 Seconds |
2–24 Seconds |
2–24 Seconds |
|||
Short Time Range |
2–6 x Ir | 2–6 x Ir | 2–6 x Ir | 2–6 x Ir | 2–6 x Ir | 2–6 x Ir | |||
Short Time Delay | — | 100–500 ms | 100–500 ms | — | 100–500 ms | 100–500 ms | |||
Instantaneous | 2–6 x M1 and M2 |
— | 2–6 x M1 and M2 |
2–6 x M1 and M2 |
— | 2–6 x M1 and M2 |
|||
Ground Fault Pickup | — | — | — | 0.25–1.0 x In(2) | 0.25–1.0 xIn(2) | 0.25–1.0 x In(2) | |||
Ground Fault Delay |
— | — | — | 100–500 ms | 100–500 ms | 100–500 ms | Ampere Rating |
Part Number |
|
Type RGH with Digitrip 610 High Interrupting Capacity—Ue Max. 690 Vac, 70 kA Icu at 415 Vac | |||||||||
1600 | 3 | RGH316T61WP44 | RGH316T63WP44 | RGH316T62WP44 | RGH316T64WP44 | RGH316T65WP44 | RGH316T66WP44 | 800 | RP6R16A080 |
1000 | RP6R16A100 | ||||||||
1200 | RP6R16A120 | ||||||||
1250 | RP6R16A125 | ||||||||
Includes 1600A rating plug | 1600 | RP6R16A160 | |||||||
2000 | 3 | RGH320T61WP49 | RGH320T63WP49 | RGH320T62WP49 | RGH320T64WP49 | RGH320T65WP49 | RGH320T66WP49 | 1000 | RP6R20A100 |
1200 | RP6R20A120 | ||||||||
1250 | RP6R20A125 | ||||||||
1600 | RP6R20A160 | ||||||||
Includes 2000A rating plug | 2000 | RP6R20A200 | |||||||
2500 | 3 | RGH325T61WP53 | RGH325T63WP53 | RGH325T62WP53 | RGH325T64WP53 | RGH325T65WP53 | RGH325T66WP53 | 1600 | RP6R25A160 |
2000 | RP6R25A200 | ||||||||
2500 | RP6R25A250 | ||||||||
Type RGC with Digitrip 610 Very High Interrupting Capacity—Ue Max. 690 Vac, 100 kA Icu at 415 Vac | |||||||||
1600 | 3 | RGC316T61WP44 | RGC316T63WP44 | RGC316T62WP44 | RGC316T64WP44 | RGC316T65WP44 | RGC316T66WP44 | 800 | RP6R16A080 |
1000 | RP6R16A100 | ||||||||
1200 | RP6R16A120 | ||||||||
1250 | RP6R16A125 | ||||||||
Includes 1600A rating plug | 1600 | RP6R16A160 | |||||||
2000 | 3 | RGC320T61WP49 | RGC320T63WP49 | RGC320T62WP49 | RGC320T64WP49 | RGC320T65WP49 | RGC320T66WP49 | 1000 | RP6R20A100 |
1200 | RP6R20A120 | ||||||||
1250 | RP6R20A125 | ||||||||
1600 | RP6R20A160 | ||||||||
Includes 2000A rating plug | 2000 | RP6R20A200 | |||||||
2500 | 3 | RGC325T61WP53 | RGC325T63WP53 | RGC325T62WP53 | RGC325T64WP53 | RGC325T65WP53 | RGC325T66WP53 | 1600 | RP6R25A160 |
2000 | RP6R25A200 | ||||||||
Includes 2500A rating plug | 2500 | RP6R25A250 | |||||||
Type RGH with Digitrip 910 High Interrupting Capacity—Ue Max. 690 Vac, 70 kA Icu at 415 Vac | |||||||||
1600 | 3 | RGC320T61WP49 | RGC320T63WP49 | RGC320T62WP49 | RGC320T64WP49 | RGC320T65WP49 | RGC320T66WP49 | 800 | RP6R16A080 |
1000 | RP6R16A100 | ||||||||
1200 | RP6R16A120 | ||||||||
1250 | RP6R16A125 | ||||||||
Includes 1600A rating plug | 1600 | RP6R16A160 | |||||||
2000 | 3 | RGH320T91WP49 | RGH320T93WP49 | RGH320T92WP49 | RGH320T94WP49 | RGH320T95WP49 | RGH320T96WP49 | 1000 | RP6R20A100 |
1200 | RP6R20A120 | ||||||||
1250 | RP6R20A125 | ||||||||
1600 | RP6R20A160 | ||||||||
Includes 2000A rating plug | 2000 | RP6R20A200 | |||||||
2500 | 3 | RGH325T91WP53 | RGH325T93WP53 | RGH325T92WP53 | RGH325T94WP53 | RGH325T95WP53 | RGH325T96WP53 | 1600 | RP6R25A160 |
2000 | RP6R25A200 | ||||||||
Includes 2500A rating plug | 2500 | RP6R25A250 | |||||||
Type RGC with Digitrip 910 Very High Interrupting Capacity—Ue Max. 690 Vac, 100 kA Icu at 415 Vac | |||||||||
1600 | 3 | RGC316T91WP44 | RGC316T93WP44 | RGC316T92WP44 | RGC316T94WP44 | RGC316T95WP44 | RGC316T96WP44 | 800 | RP6R16A080 |
1000 | RP6R16A100 | ||||||||
1200 | RP6R16A120 | ||||||||
1250 | RP6R16A125 | ||||||||
Includes 1600A rating plug | 1600 | RP6R16A160 | |||||||
2000 | 3 | RGC320T91WP49 | RGC320T93WP49 | RGC320T92WP49 | RGC320T94WP49 | RGC320T95WP49 | RGC320T96WP49 | 1000 | RP6R20A100 |
1200 | RP6R20A120 | ||||||||
1250 | RP6R20A125 | ||||||||
1600 | RP6R20A160 | ||||||||
Includes 2000A rating plug | 2000 | RP6R20A200 | |||||||
2500 | 3 | RGC325T91WP53 | RGC325T93WP53 | RGC325T92WP53 | RGC325T94WP53 | RGC325T95WP53 | RGC25T96WP53 | 1600 | RP6R25A160 |
2000 | RP6R25A200 | ||||||||
Includes 2500 A rating plug | 2500 | RP6R25A250 |
NOTES:
(1) Order terminals separately. Mounting hardware not included.
(2) Not to exceed 1200 ampere ground fault pickup.
RG MCCBs have metric threading on line and load conductors. Use RD MCCBs if imperial threading is required.
Accessories Selection Guide
Line and Load Terminals
R-Frame circuit breakers use Cu/Al terminals as standard and copper only terminals as an option. Specify if factory installation is required. Must have terminals for 100% rated and or freeze testing requirements.
Maximum Breaker Amperes |
Terminal Body Material |
Wire Type |
Hardware | AWG/kcmil Wire Range/ Number of Conductors |
Metric Wire Range mm2 |
Part Number |
Wire Terminals | ||||||
1600 | Aluminum | Cu/Al | Metric | 500–1000 (4) | 300–500 | TA1600RDM(1) |
1600 | Copper | Cu | Metric | 1–600 (4) | 50–300 | T1600RDM(1) |
2000 | Aluminum | Cu/Al | Metric | 2–600 (6) | 35–300 | TA2000RDM(2) |
Rear Connectors | ||||||
2000 | Copper | — | Metric | — | — | B2016RDM(1) |
2000 | Copper | — | Metric | — | — | B2016RDLM(1) |
2500 | Copper | — | Metric | — | — | B2500RDM(1) |
Handle Extension
Description | Part Number |
Single handle extension |
HEX6 |
TA2000RD Wire Terminal
Note: Order one TA2000RDM kit per three poles. Catalog number includes bus connection, terminals and hardware for either line side or load side of three-pole breaker.
RG Rear Connector Exploded View
NOTES:
(1) Order one per pole—single terminals individually packed.
(2) Order one TA2000RD kit per three poles. Catalog number includes bus connection, terminals and hardware for either line side or load side of three-pole breaker.
(3) For use with 2500A Frame. Do not order separately unless for replacement purposes. Included in breaker carton when 2500A frame is ordered.
RG MCCBs have metric threading on line and load conductors. Use RD MCCBs if imperial threading is required.