Eaton Specialty Breaker - Engine Generator Circuit Breakers

Engine Generator Circuit Breakers
The following table lists FG through NG engine generator breakers with the maximum generator kVA and kW rating. Engine generator breakers are applied at 115% of the generator full load current rating (FLA). The maximum kW rating is based on threephase generators at 80% power factor.
Thermal-Magnetic
Magnetic Pickup Range |
Maximum Generator Rating 60 Hz | ||||||
240 Vac kVA(1) |
kW(2) | 480 Vac kVA(1) |
kW(2) | 600 Vac kVA(1) |
kW(1) | Engine Generator Breaker(3) Part Number |
|
Fixed | 5 | 4 | 11 | 9 | 14 | 11 | FG3015(4) |
Fixed | 7 | 6 | 14 | 12 | 18 | 14 | FG3020(4) |
Fixed | 9 | 7 | 18 | 14 | 23 | 18 | FG3025(4) |
Fixed | 11 | 9 | 22 | 17 | 27 | 22 | FG3030(4) |
Fixed | 13 | 10 | 25 | 20 | 32 | 25 | FG3035(4) |
Fixed | 14 | 12 | 29 | 23 | 36 | 29 | FG3040(4) |
Fixed | 16 | 13 | 32 | 26 | 41 | 32 | FG3045(4) |
Fixed | 18 | 14 | 36 | 29 | 45 | 36 | FG3050(4) |
Fixed | 22 | 17 | 43 | 35 | 54 | 43 | FG3060(4) |
Fixed | 25 | 20 | 51 | 40 | 63 | 51 | FG3070(4) |
Fixed | 29 | 23 | 58 | 46 | 72 | 58 | FG3080(4) |
Fixed | 32 | 26 | 65 | 52 | 81 | 65 | FG3090(4) |
Fixed | 36 | 29 | 72 | 58 | 90 | 72 | FG3100(4) |
Fixed | 40 | 32 | 79 | 64 | 99 | 79 | FG3110(4) |
Fixed | 45 | 36 | 90 | 72 | 113 | 90 | FG3125(4) |
Fixed | 54 | 43 | 108 | 87 | 135 | 108 | FG3150(4) |
Fixed | 63 | 51 | 126 | 101 | 158 | 126 | FG3175(4) |
Fixed | 72 | 58 | 144 | 116 | 181 | 144 | FG3200(4) |
Fixed | 81 | 65 | 162 | 130 | 203 | 162 | FG3225(4) |
350—700 | 63 | 51 | 126 | 101 | 158 | 126 | JG3175W(5) |
350—700 | 63 | 51 | 126 | 101 | 158 | 126 | JG3175(4) |
350—700 | 72 | 58 | 144 | 116 | 181 | 144 | JG3200W(5) |
350—700 | 72 | 58 | 144 | 116 | 181 | 144 | JG3200(4) |
350—700 | 81 | 65 | 162 | 130 | 203 | 162 | JG3225W(5) |
350—700 | 81 | 65 | 162 | 130 | 203 | 162 | JG3225(4) |
350—700 | 90 | 72 | 181 | 144 | 226 | 181 | JG3250W(5) |
350—700 | 90 | 72 | 181 | 144 | 226 | 181 | JG3250(4) |
500—1000 | 108 | 87 | 217 | 173 | 271 | 217 | KG3300W(5) |
500—1000 | 108 | 87 | 217 | 173 | 271 | 217 | KG3300(4) |
500—1000 | 126 | 101 | 253 | 202 | 316 | 253 | KG3350W(5) |
500—1000 | 126 | 101 | 253 | 202 | 316 | 253 | KG3350(4) |
1000—2000 | 144 | 116 | 289 | 231 | 361 | 289 | KG3400(4) |
NOTES:
(1) Breaker continuous current is based on 115% of the generator full load ampere rating.
(2) Based on three-phase generators at 80% power factor.
(3) FG, JG, KG include thermal-magnetic trip units, LG and NG include electronic trip units.
(4) Breaker includes line and load terminals.
(5) Without terminals.
The following catalog numbers have center tap studs for dual voltage applications: JG3070CT, JG3100CT, JG3125CT, KG3175CT, LG3300CTW.
Electronic
Magnetic Pickup Range |
Maximum Generator Rating 60 Hz | ||||||
240 Vac kVA(1) |
kW(2) | 480 Vac kVA(1) |
kW(2) | 600 Vac kVA(1) |
kW(2) | Engine Generator Breaker Part Number |
|
500—2500 | 162 | 130 | 325 | 260 | 406 | 325 | LG3450(4) |
500—2500 | 181 | 144 | 361 | 289 | 451 | 361 | LG3500(4) |
500—2500 | 217 | 173 | 433 | 347 | 542 | 433 | LG3600(4) |
500—2500 | 253 | 202 | 505 | 404 | 632 | 505 | NG3700(4) |
500—2500 | 289 | 231 | 578 | 462 | 722 | 578 | NG3800(4) |
1250—5000 | 325 | 260 | 650 | 520 | 812 | 650 | NG3900(4) |
1250—5000 | 361 | 289 | 722 | 578 | 903 | 722 | NG31000(4) |
1250—5000 | 433 | 347 | 867 | 693 | 1083 | 867 | NG31200(4) |
NOTES:
(1) Breaker continuous current is based on 115% of the generator full load ampere rating.
(2) Based on three-phase generators at 80% power factor.
(3) FG, JG, KG include thermal-magnetic trip units, LG and NG include electronic trip units.
(4) Breaker includes line and load terminals.
The following part numbers have center tap studs for dual voltage applications: JG3070CT, JG3100CT, JG3125CT, KG3175CT, LG3300CTW.