Eaton Specialty Breaker - Engine Generator Circuit Breakers

Eaton Molded Case Circuit Metering & Communications Modules - PM3
Molded Case Circuit Breaker Over

Engine Generator Circuit Breakers

The following table lists FG through NG engine generator breakers with the maximum generator kVA and kW rating. Engine generator breakers are applied at 115% of the generator full load current rating (FLA). The maximum kW rating is based on threephase generators at 80% power factor.

Thermal-Magnetic

Magnetic
Pickup Range
Maximum Generator Rating 60 Hz  
 240 Vac
kVA(1)
kW(2) 480 Vac
kVA(1)
kW(2) 600 Vac
kVA(1)
kW(1) Engine Generator Breaker(3)
Part Number
Fixed 5 4 11 9 14 11 FG3015(4)
Fixed 7 6 14 12 18 14 FG3020(4)
Fixed 9 7 18 14 23 18 FG3025(4)
Fixed 11 9 22 17 27 22 FG3030(4)
Fixed 13 10 25 20 32 25 FG3035(4)
Fixed 14 12 29 23 36 29 FG3040(4)
Fixed 16 13 32 26 41 32 FG3045(4)
Fixed 18 14 36 29 45 36 FG3050(4)
Fixed 22 17 43 35 54 43 FG3060(4)
Fixed 25 20 51 40 63 51 FG3070(4)
Fixed 29 23 58 46 72 58 FG3080(4)
Fixed 32 26 65 52 81 65 FG3090(4)
Fixed 36 29 72 58 90 72 FG3100(4)
Fixed 40 32 79 64 99 79 FG3110(4)
Fixed 45 36 90 72 113 90 FG3125(4)
Fixed 54 43 108 87 135 108 FG3150(4)
Fixed 63 51 126 101 158 126 FG3175(4)
Fixed 72 58 144 116 181 144 FG3200(4)
Fixed 81 65 162 130 203 162 FG3225(4)
350—700 63 51 126 101 158 126 JG3175W(5)
350—700 63 51 126 101 158 126 JG3175(4)
350—700 72 58 144 116 181 144 JG3200W(5)
350—700 72 58 144 116 181 144 JG3200(4)
350—700 81 65 162 130 203 162 JG3225W(5)
350—700 81 65 162 130 203 162 JG3225(4)
350—700 90 72 181 144 226 181 JG3250W(5)
350—700 90 72 181 144 226 181 JG3250(4)
500—1000 108 87 217 173 271 217 KG3300W(5)
500—1000 108 87 217 173 271 217 KG3300(4)
500—1000 126 101 253 202 316 253 KG3350W(5)
500—1000 126 101 253 202 316 253 KG3350(4)
1000—2000 144 116 289 231 361 289 KG3400(4)

NOTES:
(1) Breaker continuous current is based on 115% of the generator full load ampere rating.
(2) Based on three-phase generators at 80% power factor.
(3) FG, JG, KG include thermal-magnetic trip units, LG and NG include electronic trip units.
(4) Breaker includes line and load terminals.
(5) Without terminals.
The following catalog numbers have center tap studs for dual voltage applications: JG3070CT, JG3100CT, JG3125CT, KG3175CT, LG3300CTW.

Electronic

Magnetic
Pickup Range
Maximum Generator Rating 60 Hz  
 240 Vac
kVA(1)
kW(2) 480 Vac
kVA(1)
kW(2) 600 Vac
kVA(1)
kW(2) Engine Generator
Breaker
Part Number
500—2500 162 130 325 260 406 325 LG3450(4)
500—2500 181 144 361 289 451 361 LG3500(4)
500—2500 217 173 433 347 542 433 LG3600(4)
500—2500 253 202 505 404 632 505 NG3700(4)
500—2500 289 231 578 462 722 578 NG3800(4)
1250—5000 325 260 650 520 812 650 NG3900(4)
1250—5000 361 289 722 578 903 722 NG31000(4)
1250—5000 433 347 867 693 1083 867 NG31200(4)

NOTES:
(1) Breaker continuous current is based on 115% of the generator full load ampere rating.
(2) Based on three-phase generators at 80% power factor.
(3) FG, JG, KG include thermal-magnetic trip units, LG and NG include electronic trip units.
(4) Breaker includes line and load terminals.
The following part numbers have center tap studs for dual voltage applications: JG3070CT, JG3100CT, JG3125CT, KG3175CT, LG3300CTW.

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.