EATON Motor Circuit Protectors (MCP)
Motor Circuit Protectors (MCP)
EG-Frame—480 Vac, 600Y/347 Vac Maximum(1)
Continuous Amperes | Cam Setting |
Motor Full Load Current Amperes(2) |
MCP Trip Setting(3) |
MCP Part Number |
3 | A | 0.69 -0.91 | 9 | HMCPE003A0C |
B | 1.1-1.3 | 15 | ||
C | 1.6-1.7 | 21 | ||
D | 2.0-2.2 | 27 | ||
E | 2.3-2.5 | 30 | ||
F | 2.6- 2.8 | 33 | ||
7 | A | 1.5-2.0 | 21 | HMCPE007C0C |
B | 2.6-3.1 | 35 | ||
C | 3.7-3.9 | 49 | ||
D | 4.8-5.2 | 63 | ||
E | 5.3-5.7 | 70 | ||
F | 5.8-6.1 | 77 | ||
15 | A | 3.4-4.5 | 45 | HMCPE015E0C |
B | 5.7-6.8 | 75 | ||
C | 8.0-9.1 | 105 | ||
D | 10.4-11.4 | 135 | ||
E | 11.5-12.6 | 150 | ||
F | 12.7-13.0 | 165 | ||
30 | A | 3.9-9.1 | 90 | HMCPE030H1C |
B | 11.5-13.7 | 150 | ||
C | 16.1-18.3 | 210 | ||
D | 20.7-22.9 | 270 | ||
E | 23.0-25.2 | 300 | ||
F | 25.3-26.1 | 330 |
NOTES:
(1) UL listed for use with Eaton Motor Starters.
(2) Motor FLA ranges are typical. The corresponding trip setting is at 13 times the minimum FLA value shown. Where a 13 times setting is required for an intermediate FLA value, alternate cam settings and/or MCP ratings should be used.
(3) For DC applications, actual trip levels are approximately 40% higher than values shown.
Continuous Amperes | Cam Setting |
Motor Full Load Current Amperes(2) |
MCP Trip Setting(3) |
MCP Part Number |
50 | A | 11.5-15.2 | 150 | HMCPE050K2C |
B | 19.2-22.9 | 250 | ||
C | 26.9-30.6 | 350 | ||
D | 34.6-38.3 | 450 | ||
E | 38.4-42.1 | 500 | ||
F | 42.2-43.5 | 550 | ||
70 | A | 16.1-30.6 | 210 | HMCPE070M2C |
B | 26.9-32.2 | 350 | ||
C | 37.6-42.9 | 490 | ||
D | 48.4-53.7 | 630 | ||
E | 53.8-59.1 | 700 | ||
F | 59.2-60.9 | 770 | ||
100 | A | 23.0-30.6 | 300 | HMCPE100R3C |
B | 38.4-46.0 | 500 | ||
C | 53.8-61.4 | 700 | ||
D | 69.2-76.8 | 900 | ||
E | 76.9-84.5 | 1000 | ||
F | 84.6-87.0 | 1100 | ||
100 | A | 38.4-46.0 | 500 | HMCPE100T3C |
B | 57.6-65.2 | 750 | ||
C | 76.9-84.5 | 1000 | ||
D | (4) | 1250 | ||
E | (4) | 1375 | ||
F | (4) | 1500 |
NOTES:
(1) UL listed for use with Eaton Motor Starters.
(2) Motor FLA ranges are typical. The corresponding trip setting is at 13 times the minimum FLA value shown. Where a 13 times setting is required for an intermediate FLA value, alternate cam settings and/or MCP ratings should be used.
(3) For DC applications, actual trip levels are approximately 40% higher than values shown.
(4) Settings above 10 x In are for special applications. Where the ampere rating of the disconnecting means cannot be
less than 115% of the motor full load ampere rating.
JG-Frame—600 Vac Maximum, 250 Vdc Maximum(1)
Continuous Amperes |
MCP Trip Range (Amperes) |
MCP Part Number |
250 | 500–1000 | HMCPJ250D5L |
625–1250 | HMCPJ250F5L | |
750–1500 | HMCPJ250G5L | |
875–1750 | HMCPJ250J5L | |
1000–2000 | HMCPJ250K5L | |
1125–2250 | HMCPJ250L5L | |
1250–2500 | HMCPJ250W5L |
LG-Frame—600 Vac Maximum, 250 Vdc Maximum(1)
Continuous Amperes |
MCP Trip Range (Amperes) |
MCP Part Number |
250 | 1250-2500 | HMCPL600L6G |
1500-3000 | HMCPL600N6G | |
1750-3500 | HMCPL600R6G | |
2000-4000 | HMCPL600X6G | |
2500-4500 | HMCPL600Y6G | |
2500-5000 | HMCPL600P6G | |
3000-6000 | HMCPL600M6G |
NOTES:
(1) UL listed for use with Eaton Motor Starters
800 and 1200 ampere, 600 Vac maximum motor circuit protectors are available as Series C HMCP product.