EATON Motor Circuit Protectors (MCP)

EATON Motor Circuit Protectors (MCP)

Motor Circuit Protectors (MCP)

EG-Frame—480 Vac, 600Y/347 Vac Maximum(1)

Continuous Amperes Cam
Setting
Motor
Full Load
Current
Amperes(2)
MCP
Trip
Setting(3)
MCP
Part
Number
3 A 0.69 -0.91 9 HMCPE003A0C
B 1.1-1.3 15
C 1.6-1.7 21
D 2.0-2.2 27
E 2.3-2.5 30
F 2.6- 2.8 33
7 A 1.5-2.0 21 HMCPE007C0C
B 2.6-3.1 35
C 3.7-3.9 49
D 4.8-5.2 63
E 5.3-5.7 70
F 5.8-6.1 77
15 A 3.4-4.5 45 HMCPE015E0C
B 5.7-6.8 75
C 8.0-9.1 105
D 10.4-11.4 135
E 11.5-12.6 150
F 12.7-13.0 165
30 A 3.9-9.1 90 HMCPE030H1C
B 11.5-13.7 150
C 16.1-18.3 210
D 20.7-22.9 270
E 23.0-25.2 300
F 25.3-26.1 330

NOTES:
(1) UL listed for use with Eaton Motor Starters.
(2) Motor FLA ranges are typical. The corresponding trip setting is at 13 times the minimum FLA value shown. Where a 13 times setting is required for an intermediate FLA value, alternate cam settings and/or MCP ratings should be used.
(3) For DC applications, actual trip levels are approximately 40% higher than values shown.

Continuous Amperes Cam
Setting
Motor
Full Load
Current
Amperes(2)
MCP
Trip
Setting(3)
MCP
Part
Number
50 A 11.5-15.2 150 HMCPE050K2C
B 19.2-22.9 250
C 26.9-30.6 350
D 34.6-38.3 450
E 38.4-42.1 500
F 42.2-43.5 550
70 A 16.1-30.6 210 HMCPE070M2C
B 26.9-32.2 350
C 37.6-42.9 490
D 48.4-53.7 630
E 53.8-59.1 700
F 59.2-60.9 770
100 A 23.0-30.6 300 HMCPE100R3C
B 38.4-46.0 500
C 53.8-61.4 700
D 69.2-76.8 900
E 76.9-84.5 1000
F 84.6-87.0 1100
100 A 38.4-46.0 500 HMCPE100T3C
B 57.6-65.2 750
C 76.9-84.5 1000
D (4) 1250
E (4) 1375
F (4) 1500

NOTES:
(1) UL listed for use with Eaton Motor Starters.
(2) Motor FLA ranges are typical. The corresponding trip setting is at 13 times the minimum FLA value shown. Where a 13 times setting is required for an intermediate FLA value, alternate cam settings and/or MCP ratings should be used.
(3) For DC applications, actual trip levels are approximately 40% higher than values shown.
(4) Settings above 10 x In are for special applications. Where the ampere rating of the disconnecting means cannot be less than 115% of the motor full load ampere rating.

JG-Frame—600 Vac Maximum, 250 Vdc Maximum(1)

Continuous
Amperes
MCP
Trip Range
(Amperes)
MCP
Part
Number
250 500–1000 HMCPJ250D5L
625–1250 HMCPJ250F5L
750–1500 HMCPJ250G5L
875–1750 HMCPJ250J5L
1000–2000 HMCPJ250K5L
1125–2250 HMCPJ250L5L
1250–2500 HMCPJ250W5L

LG-Frame—600 Vac Maximum, 250 Vdc Maximum(1)

Continuous
Amperes
MCP
Trip Range
(Amperes)
MCP
Part
Number
250 1250-2500 HMCPL600L6G
1500-3000 HMCPL600N6G
1750-3500 HMCPL600R6G
2000-4000 HMCPL600X6G
2500-4500 HMCPL600Y6G
2500-5000 HMCPL600P6G
3000-6000 HMCPL600M6G

NOTES:
(1) UL listed for use with Eaton Motor Starters
800 and 1200 ampere, 600 Vac maximum motor circuit protectors are available as Series C HMCP product.