EATON Molded Case Circuit Breakers Series-G, Frame Size - NG

Series-G, Frame Size-NG
Complete Breaker (Includes Frame, Trip Unit, Standard Terminals and Mounting Hardware)
LG-Frame—630 Amperes (600 Amperes UL, CSA) IC Rating: 35 kAIC at 415 and 480 Vac(1)
Circuit Breaker Frame Including Digitrip RMS 310+ Electronic Trip Unit with Imperial Tapped Conductors
L – Adjustable Long Delay Pickup
S– Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
LS | LSI | LSG | LSIG | ALSI | ALSIG | Neutral CT for LSG & LSIG |
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | ||
Short Time Delay | — | I–300 ms | — | I–300 ms | I–300 ms | I–300 ms | ||
Ground Fault Pickup | — | — | 200–1200A | 200–1200A | — | 200–1200A | ||
Ground Fault Delay | — | — | I–500 ms | I–500 ms | — | I–500 ms | ||
800 | 3 | NGS308033E | NGS308032E | NGS308035E | NGS308036E | NGS308038E | NGS308039E | NGFCT120 |
4(4) | NGS408033E | NGS408032E | NGS408035E | NGS408036E | NGS408038E | NGS408039E | — | |
4(5) | NGS708033E | NGS708032E | — | — | NGS708038E | — | — | |
4(6) | NGS908033E | NGS908032E | — | — | NGS908038E | — | — | |
1200(3) | 3 | NGS312033E | NGS312032E | NGS312035E | NGS312036E | NGS312038E | NGS312039E | NGFCT120 |
4(4) | NGS412033E | NGS412032E | NGS412035E | NGS412036E | — | NGS412039E | — | |
4(5) | NGS712033E | NGS712032E | — | — | NGS712038E | — | — | |
4(6) | NGS912033E | NGS912032E | — | — | NGS912038E | — | — |
Type NGS Standard Interrupting Capacity—Ue Max. 690 Vac, 50 kA Icu at 415 Vac
Circuit Breaker Frame Including Digitrip RMS 310+ Electronic Trip Unit with Imperial Tapped Conductors
L – Adjustable Long Delay Pickup
S– Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
LS | LSI | LSG | LSIG | ALSI | ALSIG |
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | |
Short Time Delay | — | I–300 ms | — | I–300 ms | I–300 ms | I–300 ms | |
Ground Fault Pickup | — | — | 200–1200A | 200–1200A | — | 200–1200A | |
Ground Fault Delay | — | — | I–500 ms | I–500 ms | — | I–500 ms | |
1600(3) | 3 | NGS316033M | NGS316032M | NGS316035M | NGS316036M | NGS316038M | NGS316039M |
4(4) | NGS416033M | NGS416032M | NGS416035M | NGS416036M | NGS416038M | NGS416039M | |
4(5) | NGS716033M | NGS716032M | — | — | NGS716038M | — | |
4(6) | NGS916033M | NGS916032M | — | — | NGS916038M | — |
Molded Case Switches(7)(8) — Ue Maximum 690 Vac
Ampere Rating | Three-Pole | Part Number | Four-Pole | Part Number |
800 | MCS with Imperial line and load terminals | NGK3080KSE | MCS with Imperial line and load terminals | NGK4080KSE |
1200 | MCS with Imperial line and load terminals | NGK3120KSE | MCS with Imperial line and load terminals | NGK4120KSE |
1250 | MCS with Imperial line and load terminals | NGK3125KSE | MCS with Imperial line and load terminals | NGK43125KSE |
NOTES:
(1) For AC use only.
(2) NG MCCBs are suitable for 40°C or 50°C applications. Order suffix V3 to eliminate standard 40°C labeling.
(3) Non-UL listed NG 1250 with 1250 ampere trip unit is also available.
(4) Neutral 0% protected. NG, neutral in right pocket; GN, neutral in left pocket.
(5) Neutral 100% protected (denoted by 7 in digit four).
(6) Neutral 0%/60%/100% adjustable protection (denoted by 9 in digit four).
(7) Neutral 0%/60%/100% adjustable protection (denoted by 9 in digit four).
(8) For two-pole applications, use outer poles of three-pole molded case switch.
Type NGS Standard Interrupting Capacity—Ue Max. 690 Vac, 50 kA lcu at 480 Vac or 415 Vac
Circuit Breaker Frame Including Digitrip RMS 310+ Electronic Trip Unit with Imperial Tapped Conductors
L – Adjustable Long Delay Pickup
S– Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
LS | LSI | LSG | LSIG | ALSI | ALSIG | Neutral CT for LSG & LSIG |
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | ||
Short Time Delay | — | I–300 ms | — | I–300 ms | I–300 ms | I–300 ms | ||
Ground Fault Pickup | — | — | 200–1200A | 200–1200A | — | 200–1200A | ||
Ground Fault Delay | — | — | I–500 ms | I–500 ms | — | I–500 ms | ||
800 | 3 | NGH308033E | NGH308032E | NGH308035E | NGH308036E | NGH308038E | NGH308039E | NGFCT120 |
4(4) | NGH408033E | NGH408032E | NGH408035E | NGH408036E | NGH408038E | NGH408039E | — | |
4(5) | NGH708033E | NGH708032E | — | — | NGH708038E | — | — | |
4(6) | NGH908033E | NGH908032E | — | — | NGH908038E | — | — | |
1200 | 3 | NGH312033E | NGH312032E | NGH312035E | NGH312036E | NGH312038E | NGH312039E | NGFCT120 |
4(4) | NGH412033E | NGH412032E | NGH412035E | NGH412036E | — | NGH412039E | — | |
4(5) | NGH712033E | NGH712032E | — | — | NGH712038E | — | — | |
4(6) | NGH912033E | NGH912032E | — | — | NGH912038E | — | — |
Type NGC Very High Capacity—Ue Max. 690 Vac, 100 kA lcu at 480 Vac or 415 Vac
Circuit Breaker Frame Including Digitrip RMS 310+ Electronic Trip Unit with Imperial Tapped Conductors
L – Adjustable Long Delay Pickup
S– Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)
Maximum Continuous Ampere Rating at 40°C |
Number of Poles |
LS | LSI | LSG | LSIG | ALSI | ALSIG | Neutral CT for LSG & LSIG |
Short Time Range | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | 2–8 x In | ||
Short Time Delay | — | I–300 ms | — | I–300 ms | I–300 ms | I–300 ms | ||
Ground Fault Pickup | — | — | 200–1200A | 200–1200A | — | 200–1200A | ||
Ground Fault Delay | — | — | I–500 ms | I–500 ms | — | I–500 ms | ||
800 | 3 | NGC308033E | NGC308032E | NGC308035E | NGC308036E | NGC308038E | NGC308039E | NGFCT120 |
4(4) | NGC408033E | NGC408032E | NGC408035E | NGC408036E | NGC408038E | NGC408039E | — | |
4(5) | NGC708033E | NGC708032E | — | — | NGC708038E | — | — | |
4(6) | NGC908033E | NGC908032E | — | — | NGC908038E | — | — | |
1200(3) | 3 | NGC312033E | NGC312032E | NGC312035E | NGC312036E | NGC312038E | NGC312039E | NGFCT120 |
4(4) | NGC412033E | NGC412032E | NGC412035E | NGC412036E | — | NGC412039E | — | |
4(5) | NGC712033E | NGC712032E | — | — | NGC712038E | — | — | |
4(6) | NGC912033E | NGC912032E | — | — | NGC912038E | — | — |
NOTES:
(1) For AC use only.
(2) NG MCCBs are suitable for 40°C or 50°C applications. Order suffix V3 to eliminate standard 40°C labeling.
(3) Neutral 0% protected. NG, neutral in right pocket; GN, neutral in left pocket.
(4) Neutral 100% protected (denoted by 7 in digit four).
(5) Neutral 0%/60%/100% adjustable protection (denoted by 9 in digit four).
Accessories Selection Guide and Ordering Information
Line and Load Terminals
N-Frame circuit breakers do not include terminals as standard. When copper or Cu/Al terminals are required, order by catalog number.
Maximum Breaker Amperes | Terminal Body Material |
Wire Type | AWG Wire (Number of Conductors) |
AWG Wire Part Number(1) |
Metric Wire Range mm2 |
Metric Part Number(1) |
Standard Cu/Al Pressure Terminals | ||||||
700 | Aluminum | Cu/Al | 1-500 (2) | TA700NB1 | 50-240 | TA700NB1M |
1000 | Aluminum | Cu/Al | 3/0-400 (3) | TA1000NB1 | 95-185 | TA1000NB1M |
1200 | Aluminum | Cu/Al | 4/0-500 (4) | TA1200NB1 | 120-240 | TA1200NB1M |
1200 | Aluminum | Cu/Al | 500-750 (3) | TA1201NB1 | 300-400 | TA1201NB1M |
Optional Copper and Cu/Al Pressure Type Terminals | ||||||
700 | Copper | Cu | 2/0-500 (2) | T700NB1 | 70-240 | T700NB1M |
1000 | Copper | Cu | 3/0-500 (3) | T1000NB1 | 95-240 | T1000NB1M |
1200 | Copper | Cu | 3/0-400 (4) | T1200NB3 | 95-185 | T1200NB3M |
Base Mounting Hardware(2)
Base mounting hardware is included with a circuit breaker or molded case switch.
Number of Poles | Description | Part Number |
Three and Four-pole |
Imperial hardware: 0.3125–18 x 1.25 pan-head steel screws and lock washers |
BMH5 |
Three- and four-pole | Metric hardware: M8 pan-head steel screws and lock washers |
BMH5M |
Terminal Shield
Description | Part Number |
Three-pole terminal shield | NTS3K |
Conductor Extension Kit(3)
Description | Part Number |
Three-pole both ends Metric | 5104A24G04 |
Three-pole both ends English | 5104A24G02 |
Handle Extension
Included with breaker. Additional handle extensions are available.
Description | Part Number |
Single handle extension | HEX5 |
Interphase Barriers
The interphase barriers provide additional electrical clearance between circuit breaker poles for special termination applications. Barriers are high dielectric insulating plates that are installed in the molded slots between the terminals. (Field installation only.)
Description | Part Number |
Interphase barriers | IPB5 |
Wire Seal
The wire seal can be used to secure the cover of the trip unit to prevent adjustments after settings are confirmed.
Description | Part Number |
Wire seal | 5108A03H01 |
NOTES:
(1) Single terminals individually packed.
(2) Metric hardware included with breaker.
(3) Included as standard on 100% rated 800/1200A breakers.