BUY HERE
CALL NOW
IN STOCK
866.595.9616

Eaton
JG3225W
Thermal-Magnetic
Engine Generator Circuit Breakers


JG3225W - Thermal-Magnetic Engine Generator Circuit Breakers

JG-Frame
225 Amp

Engine Generator
Circuit Breaker Index
CLICK HERE

JG (3-Pole) Shown

JG3225W - Thermal-Magnetic
Engine Generator Circuit Breakers

Magnetic
Pickup Range
Maximum Generator Rating 60 Hz
 240 Vac
kVA(1)
kW(2) 480 Vac
kVA(1)
kW(2) 600 Vac
kVA(1)
kW(1)
350—700 81 65 162 130 203 162

NOTES:
(1) Breaker continuous current is based on 115% of the generator full load ampere rating.
(2) Based on three-phase generators at 80% power factor.
(3) FG, JG, KG include thermal-magnetic trip units, LG and NG include electronic trip units.
(4) Breaker includes line and load terminals.
(5) Without terminals.

Technical Data and Specifications

Volts AC (50/60 Hz) Interrupting Capacity
(Symmetrical Amperes)
UL 489 Interrupting Capacity Ratings
240 18,000
480 14,000
600 10,000
IEC 947-2 Interrupting Capacity Ratings
220, 240 18,000/ 9,000
380, 415 14,000/ 7,000
660, 690 18,000/ 9,000
14,000/ 7,000
10,000/5,000

Dimensions and Weights - inches (mm)

Breaker
Frame
Amperes
Enclosure
Type Class
A B C D E Approx.
Weight
Lbs (kg)
FG
15–225
Type 1 23.25 (590.6) 8.41 (213.6) 6.28 (159.5) 18.75 (476.3) 1.20 (30.5) 15 (7)
Type 3R 25.66 (651.8) 8.84 (224.7) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) 19 (9)
Type 12 25.66 (651.8) 8.84 (224.7) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) 18 (8)
JG
175–250
Type 1 34.70 (881.4) 10.92 (277.4) 7.20 (182.9) 30.00 (762.0) 1.88 (47.8) 31 (14)
Type 3R 37.50 (952.5) 11.56 (293.6) 10.22 (259.6) 35.77 (908.6) 1.94 (49.3) 40 (18)
Type 12 37.53 (953.3) 11.56 (293.6) 10.22 (259.6) 35.77 (908.6)  1.94 (49.3) 37 (17)
KG
300–400
Type 1 38.81 (985.8) 11.06 (280.9) 10.94 (277.9) 34.00 (863.6) 2.28 (57.9) 53 (24)
Type 3R ) 41.69 (1058.9 11.75 (298.5) 14.06 (357.1) 39.90 (1013.5) 1.97 (50.0) 60 (27)
Type 12 41.69 (1058.9) 11.75 (298.5) 14.06 (357.1) 39.90 (1013.5) 1.97 (50.0) 53 (24)
LG
450–600
Type 1 45.88 (1165.4) 14.31 (363.5) 12.38 (314.5) 46.56 (1182.6) 1.91 (48.5) 81 (37)
Type 3R 48.31 (1227.1) 14.91 (378.7) 15.50 (393.7) 46.56 (1182.6) 1.92 (48.8) 84 (38)
Type 12 48.31 (1227.1) 14.91 (378.7) 15.50 (393.7) 46.56 (1182.6) 1.92 (48.8) 81 (37)
NG
700–1200
Type 1 61.22 (1555.0) 21.44 (544.6) 15.41 (391.4) 61.84 (1570.7) 1.97 (50.0) 178 (81)
Type 3R 63.59 (1615.2) 22.00 (558.8) 17.63 (447.8) 61.84 (1570.7) 1.97 (50.0) 175 (79)
Type 12 63.59 (1615.2) 22.00 (558.8) 17.63 (447.8) 61.84 (1570.7) 1.97 (50.0) 170 (77)
Eaton JG3225W Thermal-Magnetic Engine Generator Circuit Breaker Dimensions



Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.