JDB3175W
Thermal-Magnetic Circuit Breaker
with Non-Interchangeable Trip Unit



Series-C
Frame Size - J
Part Index
CLICK HERE

Type JD (3-Pole) Shown

JDB3175W Thermal-Magnetic Circuit Breakers with Non-Interchangeable Thermal-Magnetic Trip Units Suitable for Reverse Feed Application

Number
of Poles
Amperes Interrupting
Capacity
Type
of Trip
Terminals
3 175 600 Vac Rated
250 Vdc
Thermal-Magnetic Without Line
and Load Terminals

Quick Reference Guide

UL 489 Interrupting Capacity Ratings
Circuit
Breaker
Type
Number
of Poles
Interrupting Capacity (kA Symmetrical Amperes)
Volts AC (50/60 Hz) Volts DC
240 480 600 125 250(1)(2)
JDB 2, 3 65 35 18 10
JD 2, 3, 4 65 35 18 10
HJD 2, 3, 4 100 65 25 22
JDC(3) 2, 3, 4 200 100 35 22
IEC 157-1 (P1) Interrupting Capacity Ratings
Circuit
Breaker
Type
Number
of Poles
Interrupting Capacity (kA Symmetrical Amperes)
Volts AC (50/60 Hz) Volts DC
240 380 415 600 125 250(1)(2)
JD 2, 3, 4 65 35 35 10
HJD 2, 3, 4 100 65 65 22
JDC 2, 3, 4 200 100 100 22

NOTES:
(1) Two-pole circuit breaker or two outside poles of three-pole circuit breaker.
(2) Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
(3) Current limiting.

JDB3175W Dimensions

Number of Poles Width Height Depth
2, 3 4.13 (105.0) 10.00 (254.0) 4.06 (104.1)
4 5.50 (139.7) 10.00 (254.0) 4.06 (104.1)