JD2250F
Thermal-Magnetic Circuit Breakers
Frame Only



Series-C
Frame Size - J
Part Index
CLICK HERE

Type JD (3-Pole) Shown

JD2250F Thermal-Magnetic Circuit Breakers
Frame Only

Number
of Poles
Amperes Interrupting
Capacity
Type
of Trip
Terminals
2 250 Standard
600 Vac Rated
35 kAIC at 480 Vac
None Standard

Quick Reference Guide

UL 489 Interrupting Capacity Ratings
Circuit
Breaker
Type
Number
of Poles
Interrupting Capacity (kA Symmetrical Amperes)
Volts AC (50/60 Hz) Volts DC
240 480 600 125 250(1)(2)
JDB 2, 3 65 35 18 10
JD 2, 3, 4 65 35 18 10
HJD 2, 3, 4 100 65 25 22
JDC(3) 2, 3, 4 200 100 35 22
IEC 157-1 (P1) Interrupting Capacity Ratings
Circuit
Breaker
Type
Number
of Poles
Interrupting Capacity (kA Symmetrical Amperes)
Volts AC (50/60 Hz) Volts DC
240 380 415 600 125 250(1)(2)
JD 2, 3, 4 65 35 35 10
HJD 2, 3, 4 100 65 65 22
JDC 2, 3, 4 200 100 100 22

NOTES:
(1) Two-pole circuit breaker or two outside poles of three-pole circuit breaker.
(2) Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
(3) Current limiting.

JD2250F Dimensions

Number of Poles Width Height Depth
2, 3 4.13 (105.0) 10.00 (254.0) 4.06 (104.1)
4 5.50 (139.7) 10.00 (254.0) 4.06 (104.1)