Menu

Eaton Space Saver - Contactors, Starters & Overload Relays

Eaton Freedom Series Family Photo

Type CN13/53 Space-Savings NEMA Contactors

Eaton Type-CN13-53-Contactor

Non-Reversing and Reversing

NEMA
Size
Continuous
Ampere
Rating
Service Limit
Current
Rating (Amps)
Maximum
UL Horsepower
Three-Phase
Three-Pole
Non-Reversing (2)
Part Number
Three-Pole
Reversing (2)
Part Number
230V 480V
0 18 21 2 5 CN13BN010A -
1C 27 32 3 10 CN13CN010A CN53CN011A
1 27 32 3 10 CN13DN000A CN53DN011A
2 45 52 7-1/2 25 CN13GN000A CN53GN011A
3 90 104 15 50 CN13KN000A CN53KN011A
4 135 156 - 100 CN13MN000A -
5 (3) 270 311 - 200 CN13SN022A -

Notes

(1) Available on Compact Size 1 starter only.
(2) Gold A indicates coils suffix required, see Coil Suffix table below.
(3) NEMA Size 5 starter available with 60-300A panel mounted CTs. Starter shipped as an assembled unit with 1–5A C440 overload relay (C440A1A005SELAX or C440A2A005SELAX).

Type AN13/53 Space-Savings Starters with XTOE Electronic Overload Relays

Type-AN13-53-Starter-XTOE-Overload

Non-Reversing and Reversing

NEMA
Size
Continuous
Ampere
Rating
Service
Limit
Current
Rating (Amps)
Maximum
UL Horsepower
Three-Phase
Standard
MCC
Bucket Size
Three-Pole
Non-Reversing (1)(2)
Part Number
Three-Pole
Reversing (1)(2)
Part Number
230V 480V
0 18 21 2 5 Not offered AN13BN0A5E_ AN53BN0A5E_
1C 27 32 3 10 Not offered AN13CN0A5E_ AN53CN0A5E_
1 27 32 3 10 1X AN13DN0A5E_ AN53DN0A5E_
2 45 52 7-1/2 25 1X AN13GN0A5E_ AN53GN0A5E_
3 90 104 - 50 2X AN13KN0A5E_ AN53KN0A5E_
4 135 156 - 100 2X AN13NN0A5E_ AN53NN0A5E_
5 (3) 270 311 - 200 6X AN13SN0A5E_ AN53SN0A5E_

Notes

(1) Gold A indicates coils suffix required, see Coil Suffix table above.
(2) Underscore (_) indicates OLR designation required, see XTOE FLA Range table above.
(3) NEMA Size 5 starter available with 60-300A panel mounted CTs. Starter shipped as an assembled unit with 1–5A C440 overload relay (C440A1A005SELAX or C440A2A005SELAX).
(4) Not available on AN13DN or AN53DN starters.

Type AN13/53 Space-Savings Starters with XTOE Ground Fault Electronic Overload Relays

Type AN13/53 Starter XTOE Ground Fault Overload.jpg

Non-Reversing and Reversing

NEMA
Size
Continuous
Ampere
Rating
Service
Limit
Current
Rating (Amps)
Maximum
UL Horsepower
Three-Phase
Standard
MCC
Bucket Size
Three-Pole
Non-Reversing (1)(2)
Part Number
Three-Pole
Reversing (1)(2)
Part Number
230V 480V
0 18 21 2 5 Not offered AN13BN0A5G _ AN53BN0A5G _
1C 27 32 3 10 Not offered AN13CN0A5G _ AN53CN0A5G _
1 27 32 3 10 2X AN13DN0A5G _ AN53DN0A5G _
2 45 52 7-1/2 25 2X AN13GN0A5G _ AN53GN0A5G _
3 90 104 - 50 4X AN13KN0A5G _ AN53KN0A5G _
4 135 156 - 100 4X AN13NN0A5G_ AN53NN0A5G _
5 (3) 270 311 - 200 8X AN13SN0A5G _ AN53SN0A5G _

Notes

(1) Gold A indicates coils suffix required, see Coil Suffix table above.
(2) Underscore (_) indicates OLR designation required, see XTOE FLA Range table above.
(3) NEMA Size 5 starter available with 60-300A panel mounted CTs. Starter shipped as an assembled unit with 1–5A C440 overload relay (C440A1A005SELAX or C440A2A005SELAX).
(4) Not available on AN13DN or AN53DN starters.

XTOE Overload FLA Range (FVNR and FVR Starters Only) Magnet Coil Suffix

NEMA Size OLR Code FLA Range OLR Code FLA Rating
0 1P6 0.33-1.65A 020 4.0-20A
005 1.0-5.0A - -
1C/1 1P6 (4) 0.33-1.65A 020 4.0-20A
005 1.0-5.0A 045 9.0-45A
2 - - 045 9.0-45A
- - - -
3 100 20-100A - -
4 175 35-175A - -
5 (3) 300 60-300A - -
Coil Voltage Suffix Code
Sizes 0-2
110V 50 Hz, 120V 60 Hz A
220V 50 Hz, 240V 60 Hz B
24-27 Vdc TD
Sizes 3, 4
100-120V 50/60 Hz A
190-240V 50/60 Hz B
24-27 Vdc TD
Sizes 5
100-120V 50/60 Hz A
24-48 Vdc TD

Notes

(1) Gold A indicates coils suffix required, see Coil Suffix table above.
(2) Underscore (_) indicates OLR designation required, see XTOE FLA Range table above.
(3) NEMA Size 5 starter available with 60-300A panel mounted CTs. Starter shipped as an assembled unit with 1–5A C440 overload relay (C440A1A005SELAX or C440A2A005SELAX).
(4) Not available on AN13DN or AN53DN starters.

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.