Description |
Size 0
CN13BN010_ |
Size 1C
CN13CN010_ |
Size 1
CN13DN000_ |
Size 2
CN13GN000_ |
General |
Standards |
IEC/EN 60947,
VDE 0660, UL,
CSA,
CCC, RoHS |
IEC/EN 60947,
VDE 0660, UL,
CSA,
CCC, RoHS |
IEC/EN 60947,
VDE 0660, UL,
CSA,
CCC, RoHS |
IEC/EN 60947,
VDE 0660, UL,
CSA,
CCC, RoHS |
Weights in kg [lb]
AC operated |
0.42 [0.93] |
0.42 [0.93] |
0.9 [2.0] |
0.9 [2.0] |
Weights in kg [lb]
DC operated |
0.48 [1.06] |
0.48 [1.06] |
1.1 [2.4] |
1.1 [2.4] |
Mechanical life
operations |
10,000,000 |
10,000,000 |
10,000,000 |
10,000,000 |
Climatic proofing |
(1) |
(1) |
(1) |
(1) |
Insulation voltage
(Ui) Vac |
690 |
690 |
690 |
690 |
Impulse withstand
voltage (Uimp) Vac |
8000 |
8000 |
8000 |
8000 |
Operating voltage
(Ue) Vac |
690 |
690 |
690 |
690 |
Safe isolation to
VDE 0106 Part 101
and Part 101/A1
Between coil and
contacts (Vac) |
440 |
440 |
440 |
440 |
Safe isolation to
VDE 0106 Part 101
and Part 101/A1
Between contacts (Vac) |
238 |
440 |
440 |
440 |
Making capacity (amps) |
238 |
384 |
560 |
910 |
Breaking capacity (amps)
220/230V |
170 |
320 |
400 |
650 |
Breaking capacity (amps)
380/400V |
170 |
320 |
400 |
650 |
Breaking capacity (amps)
500V |
170 |
320 |
400 |
650 |
Breaking capacity (amps)
660/690V |
120 |
180 |
250 |
370 |
Short-circuit protection rating maximum fuse
(amps)
Type 2 coordination(2) |
400V; gG/gL 500V |
25 |
63 |
63 |
125 |
690V; gG/gL 690V |
25 |
35 |
50 |
80 |
Type 1 coordination(2) |
400V; gG/gL 500V |
63 |
125 |
125 |
250 |
690V; gG/gL 690V |
50 |
63 |
80 |
100 |
Degree of protection |
IP00 |
IP00 |
IP00 |
IP00 |
Protection against
direct contact when
actuated from
front (IEC 536) |
Finger and
back-of-hand
proof |
Finger and
back-of-hand
proof |
Finger and
back-of-hand
proof |
Finger and
back-of-hand
proof |
Terminal capacity main cable—screw terminals |
Solid (mm2) |
1 x (0.75–16)
2 x (0.75–10) |
1 x (0.75–16)
2 x (0.75–10) |
1 x (0.75–16)
2 x (0.75–10) |
1 x (0.75–16)
2 x (0.75–10) |
Flexible with
ferrule (mm2) |
1 x (0.75–16)
2 x (0.75–10) |
1 x (0.75–16)
2 x (0.75–10) |
1 x (2.5–35)
2 x (2.5–25) |
1 x (2.5–35)
2 x (2.5–25) |
Stranded (mm2) |
1 x 16 |
1 x 16 |
1 x (16–50)
2 x (16–35) |
1 x (16–50)
2 x (16–35) |
Solid or stranded (AWG) |
18–6 |
18–6 |
12–2 |
12–2 |
Flat conductor
(number of segments x
width x thickness) (mm) |
— |
— |
2 x (6 x 9 x 0.8) |
2 x (6 x 9 x 0.8) |
Main cable connection
screw/bolt |
M5 |
M5 |
M6 |
M6 |
Tightening torque
Nm |
3 |
3 |
3.3 |
3.3 |
Tightening torque
Lb-in |
26.6 |
26.6 |
29.2 |
29.2 |
Terminal capacity controlcircuit cable—screw
terminals |
Solid (mm2) |
1 x (0.75–4)
2 x (0.75–4) |
1 x (0.75–4)
2 x (0.75–4) |
1 x (0.75–4)
2 x (0.75–4) |
1 x (0.75–4)
2 x (0.75–4) |
Flexible with ferrule
(mm2) |
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5)
|
1 x (0.75–2.5)
2 x (0.75–2.5) |
Solid or stranded (AWG) |
18–14 |
18–14 |
18–14 |
18–14 |
Control circuit cable
connection screw/bolt |
M3.5 |
M3.5 |
M3.5 |
M3.5 |
Tightening torque
Nm |
1.2 |
1.2 |
1.2 |
1.2 |
Tightening torque
Lb-in |
10.6 |
10.6 |
10.6 |
10.6 |
Tools |
Main and control
circuit cable -
screw terminals |
Size 2 |
Size 2 |
Size 2 |
Size 2 |
Pozidriv screwdriver |
0.8 x 5.5 |
0.8 x 5.5 |
0.8 x 5.5 |
0.8 x 5.5 |
Standard screwdriver |
1 x 6 |
1 x 6 |
1 x 6 |
1 x 6 |
Terminal capacity control circuit
cable—spring cage terminals |
Solid (mm2)
|
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5) |
Flexible (mm2)
|
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5)
|
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5) |
Flexible with ferrule (mm2)
|
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5) |
1 x (0.75–2.5)
2 x (0.75–2.5) |
Solid or stranded (AWG) |
18–14 |
18–14 |
18–14 |
18–14 |
Tools
Main and control
circuit cable—spring cage terminals
Stripping length (mm) |
10 |
10 |
10 |
10 |
Screwdriver blade width (mm) |
3.5 |
3.5 |
3.5 |
3.5 |
Mounting position,
AC and DC operated |
|
|
|
|
Ambient temperature
Open |
–25 to 60°C
[–13 to 140°F] |
–25 to 60°C
[–13 to 140°F] |
–25 to 60°C
[–13 to 140°F] |
–25 to 60°C
[–13 to 140°F] |
Ambient temperature
Enclosed |
–25 to 40°C
[–13 to 104°F] |
–25 to 40°C
[–13 to 104°F] |
–25 to 40°C
[–13 to 104°F] |
–25 to 40°C
[–13 to 104°F] |
Ambient storage
temperature |
–40 to 80°C
[–40 to 176°F] |
–40 to 80°C
[–40 to 176°F] |
–40 to 80°C
[–40 to 176°F] |
–40 to 80°C
[–40 to 176°F] |
Environmental - Mechanical shock resistance
(IEC/EN 60068-2-27) |
Main contact -
NO Contact |
10 |
10 |
10 |
10 |
Auxiliary contact -
NO Contact |
7 |
7 |
7 |
7 |
Auxiliary contact -
NC Contact |
5 |
5 |
5 |
5 |
Overvoltage category/
pollution degree |
III/3 |
III/3 |
III/3 |
III/3 |