Menu

Eaton CN13SN022
Type CN13/53 Space-Savings
NEMA Contactors

CN13SN022 - Type CN13/53 Space-Savings Three-Pole Non-Reversing and Reversing

Type CN13/53
Space-Savings
Three-Pole Non-Reversing
Contactor


NEMA Size = 5

Continuous Ampere Rating = 270

NOTE: Add Coil Suffix Code (see table below)
For Complete Part Number

Series Part Numbers

NEMA
Size
Continuous
Ampere
Rating
Service Limit
Current
Rating (Amps)
Maximum
UL Horsepower
Three-Phase
Three-Pole
Non-Reversing (1)
Part Number
Three-Pole
Reversing (1)
Part Number
230V 480V
0 18 21 2 5 CN13BN010_ -
1C 27 32 3 10 CN13CN010_ CN53CN011_
1 27 32 3 10 CN13DN000_ CN53DN011_
2 45 52 7-1/2 25 CN13GN000_ CN53GN011_
3 90 104 15 50 CN13KN000_ CN53KN011_
4 135 156 - 100 CN13MN000_ -
5 (3) 270 311 - 200 CN13SN022_ -

NOTES:
(1) Available on Compact Size 1 starter only.
(2) Underscore (_) indicates coils suffix required - See Below.
(3) NEMA Size 5 starter available with 60-300A panel mounted CTs. Starter shipped as an assembled unit with 1–5A C440 overload relay (C440A1A005SELAX or C440A2A005SELAX).

Coil Suffix Code

Coil Voltage Suffix Code
Sizes 0–2
110V 50 Hz, 120V 60 Hz A
220V 50 Hz, 240V 60 Hz B
24–27 Vdc TD
Sizes 3, 4
100–120V 50/60 Hz A
190–240V 50/60 Hz B
24–27 Vdc TD
Sizes 5
100–120V 50/60 Hz A
24–48 Vdc TD

Technical Data and Specifications - Size 5

Standards IEC/EN 60947,
VDE 0660, UL, CSA
Weights in kg [lb] 6.5 [14.3]
Mechanical life—operations 10,000,000
Mechanical operating frequency (ops/hr)
AC operated
3000
Mechanical operating frequency (ops/hr)
DC operated
3000
Climatic proofing (1)
Insulation voltage (Ui) Vac 1000
Impulse withstand voltage (Uimp) Vac 8000
Operating voltage (Ue) Vac 1000
Safe isolation to VDE 0106 Part 101
and Part 101/A1
Between coil and contacts (Vac)
500
Safe isolation to VDE 0106 Part 101
and Part 101/A1
Between contacts (Vac)
500
Making capacity (amps) 3000
Breaking capacity (amps)
220/230V
2500
Breaking capacity (amps)
380/400V
2500
Breaking capacity (amps)
500V
2500
Breaking capacity (amps)
660/690V
2500
Breaking capacity (amps)
1000V
760
Short-circuit protection rating maximum fuse
Type 2 coordination (2)
400V; gG/gL 500V
315
Type 2 coordination (2)
690V; gG/gL 690V
315
Type 2 coordination (2)
1000V; gG/gL 1000V
160
Type 1 coordination (2)
400V; gG/gL 500V
400
Type 1 coordination (2)
690V; gG/gL 690V
400
Type 1 coordination (2)
1000V; gG/gL 1000V
200
Degree of protection IP00
Protection against direct contact when actuated
from front (IEC 536)
Finger and back-of-hand proof with
terminal shroud or terminal block
Main cable cross-section
Flexible with cable lug (mm2) 50–240
Stranded with cable lug (mm2) 70–240
Solid or stranded (AWG) 1/0–250 kcmil
Flat conductor (mm) (3)
Bus bar—width in mm 25
Main cable connection screw/bolt M10
Tightening torque
Nm
24
Tightening torque
Lb-in
213
Control circuit cable cross-sections
Solid (mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
Control circuit cable cross-sections
Flexible with ferrule (mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
Control circuit cable cross-sections
Solid or stranded (AWG)
2 x (18–12)
Control circuit cable connection screw/bolt M3.5
Tightening torque
Nm
1.2
Tightening torque
Lb-in
10.6
Tools
Main cable wrench
16 mm
Tools
Control circuit cable pozidriv screwdriver
Size 2
Mounting position, AC and DC operated NEMA Size - 5 Type CN13/53 Space-Savings Mounting
Ambient temperature –25 to 60°C
[–13 to 140°F]
Ambient storage temperature –40 to 80°C
[–40 to 176°F]
Main contact—NO contact 10g
Auxiliary contact—NO contact 10g
Auxiliary contact—NC contact 8g
Overvoltage category/pollution degree III/3
Switching capacity, kVAR 4
Individual compensation
230V
Individual compensation
400/420/440V
Individual compensation
525V
Individual compensation
690V
Group compensation, with choke
230V
100
Group compensation, with choke
400/420/440V
190
Group compensation, with choke
525V
260
Group compensation, with choke
690V
340
Group compensation, without choke
230V
Group compensation, without choke
400/420/440V
Group compensation, without choke
525V
Group compensation, without choke
690V

NOTES:
(1) Damp heat, constant, to IEC 60068-2-78; damp heat, cyclic, to IEC 60 068-2-30.
(2) IEC 60947 Standard.
(3) Screw tightening with flat cable terminal or cable terminal blocks. See terminal capacity for cable terminal blocks. (4) When using contactors for group compensation, a minimum inductance of approx. 6 uh per capacitor must be available to limit the high inrush current peaks. This corresponds to an air-cored coil with five windings and a coil diameter of approximately 140 mm. The conductor cross-section must be selected according to the rated current per phase.

Sizes 5 Dimensions

CN13SN022 Dimensions

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.