Menu

Eaton CN13CN010
Type CN13/53 Space-Savings
NEMA Contactors

CN13CN010 - Type CN13/53 Space-Savings Three-Pole Non-Reversing and Reversing

Type CN13/53
Space-Savings
Three-Pole Non-Reversing
Contactor


NEMA Size = 1C

Continuous Ampere Rating = 27

NOTE: Add Coil Suffix Code (see table below)
For Complete Part Number

Series Part Numbers

NEMA
Size
Continuous
Ampere
Rating
Service Limit
Current
Rating (Amps)
Maximum
UL Horsepower
Three-Phase
Three-Pole
Non-Reversing (1)
Part Number
Three-Pole
Reversing (1)
Part Number
230V 480V
0 18 21 2 5 CN13BN010_ -
1C 27 32 3 10 CN13CN010_ CN53CN011_
1 27 32 3 10 CN13DN000_ CN53DN011_
2 45 52 7-1/2 25 CN13GN000_ CN53GN011_
3 90 104 15 50 CN13KN000_ CN53KN011_
4 135 156 - 100 CN13MN000_ -
5 (3) 270 311 - 200 CN13SN022_ -

NOTES:
(1) Underscore (_) indicates coils suffix required - See Below.

Coil Suffix Code

Coil Voltage Suffix Code
Sizes 0–2
110V 50 Hz, 120V 60 Hz A
220V 50 Hz, 240V 60 Hz B
24–27 Vdc TD
Sizes 3, 4
100–120V 50/60 Hz A
190–240V 50/60 Hz B
24–27 Vdc TD
Sizes 5
100–120V 50/60 Hz A
24–48 Vdc TD

Technical Data and Specifications, Sizes 0-2

Description Size 0
CN13BN010_
Size 1C
CN13CN010_
Size 1
CN13DN000_
Size 2
CN13GN000_
General
Standards IEC/EN 60947,
VDE 0660, UL,
CSA,
CCC, RoHS
IEC/EN 60947,
VDE 0660, UL,
CSA,
CCC, RoHS
IEC/EN 60947,
VDE 0660, UL,
CSA,
CCC, RoHS
IEC/EN 60947,
VDE 0660, UL,
CSA,
CCC, RoHS
Weights in kg [lb]
AC operated
0.42 [0.93] 0.42 [0.93] 0.9 [2.0] 0.9 [2.0]
Weights in kg [lb]
DC operated
0.48 [1.06] 0.48 [1.06] 1.1 [2.4] 1.1 [2.4]
Mechanical life
operations
10,000,000 10,000,000 10,000,000 10,000,000
Climatic proofing (1) (1) (1) (1)
Insulation voltage
(Ui) Vac
690 690 690 690
Impulse withstand
voltage (Uimp) Vac
8000 8000 8000 8000
Operating voltage
(Ue) Vac
690 690 690 690
Safe isolation to
VDE 0106 Part 101
and Part 101/A1
Between coil and
contacts (Vac)
440 440 440 440
Safe isolation to
VDE 0106 Part 101
and Part 101/A1
Between contacts (Vac)
238 440 440 440
Making capacity (amps) 238 384 560 910
Breaking capacity (amps)
220/230V
170 320 400 650
Breaking capacity (amps)
380/400V
170 320 400 650
Breaking capacity (amps)
500V
170 320 400 650
Breaking capacity (amps)
660/690V
120 180 250 370
Short-circuit protection rating maximum fuse (amps)
Type 2 coordination(2)
400V; gG/gL 500V 25 63 63 125
690V; gG/gL 690V 25 35 50 80
Type 1 coordination(2)
400V; gG/gL 500V 63 125 125 250
690V; gG/gL 690V 50 63 80 100
Degree of protection   IP00 IP00 IP00 IP00
Protection against
direct contact when
actuated from
front (IEC 536)
Finger and
back-of-hand
proof
Finger and
back-of-hand
proof
Finger and
back-of-hand
proof
Finger and
back-of-hand
proof
Terminal capacity main cable—screw terminals
Solid (mm2) 1 x (0.75–16)
2 x (0.75–10)
1 x (0.75–16)
2 x (0.75–10)
1 x (0.75–16)
2 x (0.75–10)
1 x (0.75–16)
2 x (0.75–10)
Flexible with
ferrule (mm2)
1 x (0.75–16)
2 x (0.75–10)
1 x (0.75–16)
2 x (0.75–10)
1 x (2.5–35)
2 x (2.5–25)
1 x (2.5–35)
2 x (2.5–25)
Stranded (mm2) 1 x 16 1 x 16 1 x (16–50)
2 x (16–35)
1 x (16–50)
2 x (16–35)
Solid or stranded (AWG) 18–6 18–6 12–2 12–2
Flat conductor
(number of segments x
width x thickness) (mm)
2 x (6 x 9 x 0.8) 2 x (6 x 9 x 0.8)
Main cable connection
screw/bolt
M5 M5 M6 M6
Tightening torque
Nm
3 3 3.3 3.3
Tightening torque
Lb-in  
26.6 26.6 29.2 29.2
Terminal capacity controlcircuit cable—screw terminals
Solid (mm2) 1 x (0.75–4)
2 x (0.75–4)
1 x (0.75–4)
2 x (0.75–4)
1 x (0.75–4)
2 x (0.75–4)
1 x (0.75–4)
2 x (0.75–4)
Flexible with ferrule
(mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
Solid or stranded (AWG) 18–14 18–14 18–14 18–14
Control circuit cable
connection screw/bolt
M3.5 M3.5 M3.5  M3.5
Tightening torque
Nm
1.2 1.2 1.2 1.2
Tightening torque
Lb-in
10.6 10.6 10.6 10.6
Tools
Main and control
circuit cable -
screw terminals
Size 2 Size 2 Size 2 Size 2
Pozidriv screwdriver 0.8 x 5.5  0.8 x 5.5  0.8 x 5.5 0.8 x 5.5
Standard screwdriver 1 x 6 1 x 6 1 x 6 1 x 6
Terminal capacity control circuit cable—spring cage terminals
Solid (mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
Flexible (mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
Flexible with ferrule (mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
Solid or stranded (AWG) 18–14 18–14 18–14 18–14
Tools
Main and control
circuit cable—spring cage terminals
Stripping length (mm)   
10 10 10 10
Screwdriver blade width (mm) 3.5 3.5 3.5 3.5
Mounting position,
AC and DC operated
Mounting Positions - Size 0 - CN13BN010_ Mounting Positions - Size 1C - CN13CN010_ Mounting Positions - Size 1 - CN13DN000_ Mounting Positions - Size 2 - CN13GN000_
Ambient temperature
Open
–25 to 60°C
[–13 to 140°F]
–25 to 60°C
[–13 to 140°F]
–25 to 60°C
[–13 to 140°F]
–25 to 60°C
[–13 to 140°F]
Ambient temperature
Enclosed
–25 to 40°C
[–13 to 104°F]
–25 to 40°C
[–13 to 104°F]
–25 to 40°C
[–13 to 104°F]
–25 to 40°C
[–13 to 104°F]
Ambient storage
temperature
–40 to 80°C
[–40 to 176°F]
–40 to 80°C
[–40 to 176°F]
–40 to 80°C
[–40 to 176°F]
–40 to 80°C
[–40 to 176°F]
Environmental - Mechanical shock resistance
(IEC/EN 60068-2-27)
Main contact -
NO Contact
10 10 10 10
Auxiliary contact -
NO Contact  
7 7 7 7
Auxiliary contact -
NC Contact
5 5 5 5
Overvoltage category/
pollution degree 
III/3 III/3  III/3 III/3

Sizes 0-2 Dimensions

CN13CN010 Dimensions