Menu

Eaton CN53KN011
Type CN13/53 Space-Savings
NEMA Contactors

CN53KN011 - Type CN13/53 Space-Savings Three-Pole Non-Reversing and Reversing

Type CN13/53
Space-Savings
Three-Pole Reversing
Contactor


NEMA Size = 3

Continuous Ampere Rating = 90

NOTE: Add Coil Suffix Code (see table below)
For Complete Part Number

Series Part Numbers

NEMA
Size
Continuous
Ampere
Rating
Service Limit
Current
Rating (Amps)
Maximum
UL Horsepower
Three-Phase
Three-Pole
Non-Reversing (1)
Part Number
Three-Pole
Reversing (1)
Part Number
230V 480V
0 18 21 2 5 CN13BN010_ -
1C 27 32 3 10 CN13CN010_ CN53CN011_
1 27 32 3 10 CN13DN000_ CN53DN011_
2 45 52 7-1/2 25 CN13GN000_ CN53GN011_
3 90 104 15 50 CN13KN000_ CN53KN011_
4 135 156 - 100 CN13MN000_ -
5 (3) 270 311 - 200 CN13SN022_ -

NOTES:
(1) Underscore (_) indicates coils suffix required - See Below.

Coil Suffix Code

Coil Voltage Suffix Code
Sizes 0–2
110V 50 Hz, 120V 60 Hz A
220V 50 Hz, 240V 60 Hz B
24–27 Vdc TD
Sizes 3, 4
100–120V 50/60 Hz A
190–240V 50/60 Hz B
24–27 Vdc TD
Sizes 5
100–120V 50/60 Hz A
24–48 Vdc TD

Technical Data and Specifications - Sizes 3, 4

Description Size 3
CN13KN000_
Size 4
CN13MN000_
General
Standards IEC/EN 60947,
VDE 0660, UL, CSA,
CCC, RoHS
IEC/EN 60947,
VDE 0660, UL, CSA,
CCC, RoHS
Weights in kg [lb]
AC operated  2 [4.41] 2 [4.41]
DC operated 2.1 [4.63] 2.1 [4.63]
Mechanical life—operations 10,000,000 10,000,000
Climatic proofing (1) (1)
Insulation voltage (Ui) Vac  690 690
Impulse withstand voltage (Uimp) Vac  8000 8000
Operational voltage (Ue) Vac 690 690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between coil and contacts (Vac) 690 690
Between contacts (Vac)  690 690
Making capacity (amps) 1610  2100
Breaking capacity (amps)
220/230V 1150 1500
380/400V 1150 1500
500V 1150 1500
660/690V 1100 1200
1000V
Short-circuit protection rating maximum fuse
Type 2 coordination (2)
400V; gG/gL 500V
250 25
Type 2 coordination (2)
690V; gG/gL 690V
25 250
Type 1 coordination (2)
400V; gG/gL 500V
250 250
Type 1 coordination (2)
690V; gG/gL 690V
250 250
Degree of protection IP00 IP00
Protection against direct
contact when actuated
from front (IEC 536)
Finger and
back-of-hand proof
Finger and
back-of-hand proof
Terminal capacity main cable—screw terminals
Solid (mm2)
Flexible with ferrule (mm2) 1 x (10–95)
2 x (10–70)
1 x (10–95)
2 x (10–70)
Stranded (mm2) 1 x (10–95)
2 x (10–20)
1 x (10–95)
2 x (10–20)
Flat conductor
(number of segments x width x thickness) (mm)
2 x (6 x 16 x 0.8) 2 x (6 x 16 x 0.8)
Solid or stranded (AWG) 8–3/0 8–3/0
Main cable connection screw/bolt M10 M10
Tightening torque - Nm 14 14
Tightening torque - Lb-in 123.9 123.9
Terminal capacity control circuit cable—screw terminals
Solid (mm2) 1 x (0.75–4)
1 x (0.75–4)
1 x (0.75–4)
1 x (0.75–4)
Flexible with ferrule (mm2) 1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
Solid or stranded (AWG) 18–14 18–14
Control circuit cable connection screw/bolt M3.5 M3.5
Tightening torque
Nm
1.2 1.2
Tightening torque
Lb-in
10.6 10.6
Tools
Main circuit cable—screw terminals
Hexagon socket-head spanner (mm)
5 5
Control circuit cable—screw terminals Size 2 Size 2
Pozidriv screwdriver 0.8 x 5.5 0.8 x 5.5
Standard screwdriver 1 x 6 1 x 6
Terminal capacity control circuit cable—spring cage terminals
Solid (mm2) 1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
Flexible (mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
Flexible with ferrule (mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
1 x (0.75–2.5)
2 x (0.75–2.5)
Control circuit cable—spring cage terminals
Stripping length (mm)
10 10
Screwdriver blade width (mm) 3.5 3.5
Mounting position, AC and DC operated Size 3 - CN13KN000_ Mounting Position Size 4 - CN13MN000_ Mounting Position
Ambient temperature
Open
–25 to 60°C
[–13 to 140°F]
–25 to 60°C
[–13 to 140°F]
Ambient temperature
Enclosed
–25 to 40°C
[–13 to 104°F]
–25 to 40°C
[–13 to 104°F]
Ambient storage temperature
–40 to 80°C
[–40 to 176°F]
–40 to 80°C
[–40 to 176°F]
Environmental - Mechanical shock resistance
(IEC/EN 60068-2-27)
Half-sinusoidal shock 10 ms
Main contact—NO contact
10g 10g
Auxiliary contact—NO contact 7g 7g
Auxiliary contact—NC contact 5g 5g
Overvoltage category/pollution degree III/3 III/3

NOTES:
(1) Damp heat, constant, to IEC 60068-2-78; damp heat, cyclic, to IEC 60 068-2-30.
(2) IEC 60947 Standard.

Sizes 3-5 Dimensions

CN53KN011 Dimensions

Sizes 3 - 4 Reversing Contactor Dimensions

CN53CN011 Reversing Contactor Dimensions

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.