Eaton AN13SN0A5E
Type CN13/53 Non-Reversing
& Reversing Space-Savings
NEMA Contactors

AN13SN0A5E - Type CN13/53 Space-Savings Three-Pole Non-Reversing and Reversing

Type AN13/53
Space-Savings
Non-Reversing Starter
with XTOE Electronic
Overload Relay


NEMA Size 5 starter available with 60-300A panel mounted CTs. Starter shipped as an assembled unit
with 1–5A C440 overload relay
(C440A1A005SELAX or C440A2A005SELAX).

NEMA Size = 5

Continuous Ampere Rating = 270

NOTE: Add Coil Suffix Code (see table below)
For Complete Part Number

Series Part Numbers

NEMA
Size
Continuous
Ampere
Rating
Service
Limit
Current
Rating (Amps)
Maximum
UL Hp
Three-Phase
Standard
MCC
Bucket Size
Three-Pole
Non-
Reversing (1)(2)
Part Number
Three-Pole
Reversing (1)(2)
Part Number
230V 480V
0 18 21 2 5 Not offered AN13BN0A5E_ AN53BN0A5E_
1C 27 32 3 10 Not offered AN13CN0A5E_ AN53CN0A5E_
1 27 32 3 10 1X AN13DN0A5E_ AN53DN0A5E_
2 45 52 7-1/2 25 1X AN13GN0A5E_ AN53GN0A5E_
3 90 104 - 50 2X AN13KN0A5E_ AN53KN0A5E_
4 135 156 - 100 2X AN13NN0A5E_ AN53NN0A5E_
5 (3) 270 311 - 200 6X AN13SN0A5E_ AN53SN0A5E_

XTOE Overload FLA Range
(FVNR and FVR Starters Only) Magnet Coil Suffix

NEMA Size OLR Code FLA Range OLR Code FLA Rating
0    1P6 0.33–1.65A 020 4.0–20A
005 1.0–5.0A
1C/1 1P6(4) 0.33–1.65A 020 4.0–20A
005 1.0–5.0A 045  9.0–45A
2 045 9.0–45A
3 100 20–100A
4 175 35–175A
5(3) 300 60–300A

Coil Suffix Code

Coil Voltage Suffix Code
Sizes 0–2
110V 50 Hz, 120V 60 Hz A
220V 50 Hz, 240V 60 Hz B
24–27 Vdc TD
Sizes 3, 4
100–120V 50/60 Hz A
190–240V 50/60 Hz B
24–27 Vdc TD
Sizes 5
100–120V 50/60 Hz A
24–48 Vdc TD

NOTES:
(1) RED A indicates coils suffix required, see Coil Suffix table above.
(2) Underscore (_) indicates OLR designation required, see XTOE FLA Range table above.
(3) NEMA Size 5 starter available with 60-300A panel mounted CTs. Starter shipped as an assembled unit with 1–5A C440 overload relay (C440A1A005SELAX or C440A2A005SELAX).
(4) Not available on AN13DN or AN53DN starters.

Technical Data and Specifications - Size 5

Standards IEC/EN 60947,
VDE 0660, UL, CSA
Weights in kg [lb] 6.5 [14.3]
Mechanical life—operations 10,000,000
Mechanical operating frequency (ops/hr)
AC operated
3000
Mechanical operating frequency (ops/hr)
DC operated
3000
Climatic proofing (1)
Insulation voltage (Ui) Vac 1000
Impulse withstand voltage (Uimp) Vac 8000
Operating voltage (Ue) Vac 1000
Safe isolation to VDE 0106 Part 101
and Part 101/A1
Between coil and contacts (Vac)
500
Safe isolation to VDE 0106 Part 101
and Part 101/A1
Between contacts (Vac)
500
Making capacity (amps) 3000
Breaking capacity (amps)
220/230V
2500
Breaking capacity (amps)
380/400V
2500
Breaking capacity (amps)
500V
2500
Breaking capacity (amps)
660/690V
2500
Breaking capacity (amps)
1000V
760
Short-circuit protection rating maximum fuse
Type 2 coordination (2)
400V; gG/gL 500V
315
Type 2 coordination (2)
690V; gG/gL 690V
315
Type 2 coordination (2)
1000V; gG/gL 1000V
160
Type 1 coordination (2)
400V; gG/gL 500V
400
Type 1 coordination (2)
690V; gG/gL 690V
400
Type 1 coordination (2)
1000V; gG/gL 1000V
200
Degree of protection IP00
Protection against direct contact when actuated
from front (IEC 536)
Finger and back-of-hand proof with
terminal shroud or terminal block
Main cable cross-section
Flexible with cable lug (mm2) 50–240
Stranded with cable lug (mm2) 70–240
Solid or stranded (AWG) 1/0–250 kcmil
Flat conductor (mm) (3)
Bus bar—width in mm 25
Main cable connection screw/bolt M10
Tightening torque
Nm
24
Tightening torque
Lb-in
213
Control circuit cable cross-sections
Solid (mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
Control circuit cable cross-sections
Flexible with ferrule (mm2)
1 x (0.75–2.5)
2 x (0.75–2.5)
Control circuit cable cross-sections
Solid or stranded (AWG)
2 x (18–12)
Control circuit cable connection screw/bolt M3.5
Tightening torque
Nm
1.2
Tightening torque
Lb-in
10.6
Tools
Main cable wrench
16 mm
Tools
Control circuit cable pozidriv screwdriver
Size 2
Mounting position, AC and DC operated NEMA Size - 5 Type CN13/53 Space-Savings Mounting
Ambient temperature –25 to 60°C
[–13 to 140°F]
Ambient storage temperature –40 to 80°C
[–40 to 176°F]
Main contact—NO contact 10g
Auxiliary contact—NO contact 10g
Auxiliary contact—NC contact 8g
Overvoltage category/pollution degree III/3
Switching capacity, kVAR 4
Individual compensation
230V
Individual compensation
400/420/440V
Individual compensation
525V
Individual compensation
690V
Group compensation, with choke
230V
100
Group compensation, with choke
400/420/440V
190
Group compensation, with choke
525V
260
Group compensation, with choke
690V
340
Group compensation, without choke
230V
Group compensation, without choke
400/420/440V
Group compensation, without choke
525V
Group compensation, without choke
690V

NOTES:
(1) Damp heat, constant, to IEC 60068-2-78; damp heat, cyclic, to IEC 60 068-2-30.
(2) IEC 60947 Standard.
(3) Screw tightening with flat cable terminal or cable terminal blocks. See terminal capacity for cable terminal blocks. (4) When using contactors for group compensation, a minimum inductance of approx. 6 uh per capacitor must be available to limit the high inrush current peaks. This corresponds to an air-cored coil with five windings and a coil diameter of approximately 140 mm. The conductor cross-section must be selected according to the rated current per phase.

Electronic Overload Relays
Up to 1500A
Technical Data and Specifications

Description Specification
45 mm 55 mm 110 mm
Electrical Ratings Range Range  Range
Operating voltage (three-phase)
and frequency 
690 Vac (60/50 Hz) 690 Vac (60/50 Hz) 690 Vac (60/50 Hz)
FLA Range 0.33–1.65A
1–5A
4–20A
9–45A
20–100A 28–140A (NEMA)
35–175A (IEC)
Use with Contactors
Space-Savings NEMA Size
0, 1C 1, 2, 3 4
Trip Class 10A, 10, 20, 30
Selectable
10A, 10, 20, 30
Selectable
10A, 10, 20, 30
Selectable
Motor Protection
Thermal overload setting
1.05 x FLA: does not trip
1.15 x FLA: overload trip
1.05 x FLA: does not trip
1.15 x FLA: overload trip
1.05 x FLA: does not trip
1.15 x FLA: overload trip
Phase loss  Fixed threshold 50% Fixed threshold 50% Fixed threshold 50%
Phase unbalance
(selectable: enable/disable)
Fixed threshold 50% Fixed threshold 50% Fixed threshold 50%
Ground fault
(selectable: enable/disable)
50% of FLA dial setting
>150% = 2 sec
>250% = 1 sec
50% of FLA dial setting
>150% = 2 sec
>250% = 1 sec
50% of FLA dial setting
>150% = 2 sec
>250% = 1 sec
Reset Manual/automatic Manual/automatic Manual/automatic
Trip status Orange flag Orange flag Orange flag
Mode LED One flash:
Overload operating
properly
Two flashes:
Current is above
FLA dial
setting—
pending trip
One flash:
Overload operating
properly
Two flashes:
Current is above
FLA dial
setting—
pending trip
One flash:
Overload operating
properly
Two flashes:
Current is above
FLA dial
setting—
pending trip
Remote reset Yes Yes Yes
Reset bar Yes Yes Yes
Communication
expansion module
Yes Yes Yes
Communication adapter Yes Yes Yes
Load terminals
Terminal capacity
12–10 AWG (4–6 mm2)
8–6 AWG (6–16 mm2)
6–1 AWG (16–50 mm2) 8–4/0 AWG (10–95 mm2)
Load terminals
Tightening torque
20–25 lb-in (2.3–2.8 Nm)
25–30 lb-in (2.8–3.4 Nm)
25–30 lb-in (2.8–3.4 Nm) 124 lb-in (14 Nm)
Input, auxiliary contact
and remote reset terminals
Terminal capacity
2 x (18–12) AWG 2 x (18–12) AWG 2 x (18–12) AWG
Input, auxiliary contact
and remote reset terminals
Tightening torque
7–11 lb-in (0.8–1.2 Nm) 7–11 lb-in (0.8–1.2 Nm) 7–11 lb-in (0.8–1.2 Nm)
Voltages
Insulation voltage Ui
(three-phase)
690 Vac 690 Vac  690 Vac
Insulation
voltage Ui (control)
500 Vac  500 Vac 500 Vac
Rated impulse
withstand voltage
6000 Vac 6000 Vac  6000 Vac
Overvoltage category/
pollution degree
III/3 III/3 III/3
Auxiliary and Control Circuit Ratings
Conventional thermal
continuous current
5A 5A 5A
Rated operational current
—IEC AC-15
Make contact (1800 VA)
 
120V 15A 15A 15A
240V 15A 15A 15A
415V 0.5A 0.5A  0.5A
500V 0.5A 0.5A 0.5A
Break contact (180 VA)  
120V 1.5A 1.5A 1.5A
240V 1.5A 1.5A 1.5A
415V 0.9A 0.9A 0.9A
500V 0.8A 0.8A 0.8A
IEC DC-13 (L/R F 15 ms1)  
0–250V 1.0A 1.0A 1.0A
Rated operational current
UL B600
Make contact (3600 VA)
 
120V 30A 30A 30A
240V 15A 15A 15A
480V 7.5A 7.5A 7.5A
600V 6A 6A 6A
Break contact (360 VA)  
120V 3A 3A 3A
240V 1.5A 1.5A 1.5A
480V 0.75A 0.75A 0.75A
600V 0.6A 0.6A 0.6A
R300—Vdc ratings (28 VA)  
0–120V 0.22A 0.22A 0.22A
250V 0.11A 0.11A 0.11A
Short-Circuit Rating without Welding
Maximum fuse   6A gG/gL 6A gG/gL 6A gG/gL
Environmental Ratings
Ambient temperature
(operating)
–13° to 149°F
(–25° to 65°C)
–13° to 149°F
(–25° to 65°C)
–13° to 149°F
(–25° to 65°C)
Ambient temperature
(storage)
–40° to 185°F
(–40° to 85°C)
 –40° to 185°F
(–40° to 85°C)
–40° to 185°F
(–40° to 85°C)
Operating humidity
UL 991 (H3)
5% to 95%
noncondensing
5% to 95%
noncondensing
5% to 95%
noncondensing
Altitude (no derating)
NEMA ICS1
2000m 2000m 2000m
Shock
(IEC 600068-2-27)
15g any direction 15g any direction 15g any direction
Vibration
(IEC 60068-2-6)
3g any direction 3g any direction 3g any direction
Pollution degree per
IEC 60947-4-1
3 for product (2 for pcb) 3 for product (2 for pcb) 3 for product (2 for pcb)
Ingress protection IP20 IP20 IP20
Protection against direct
contact when actuated from
front (IEC 536)
Finger- and
back-of-hand proof
Finger- and
back-of-hand proof
Finger- and
back-of-hand proof
Mounting position  Any Any Any
Climatic proofing Damp heat,
constant to
IEC 60068-2-30
Damp heat,
constant to
IEC 60068-2-30
Damp heat,
constant to
IEC 60068-2-30
Electrical/EMC
Radiated emissions
IEC 60947-4-1-Table 15
EN 55011 (CISPIR 11)
Group 1, Class A, ISM
30 MHz to
1000 MHz
30 MHz to
1000 MHz
30 MHz to
1000 MHz
Conducted emissions
IEC 60947-4-1-Table 14
EN 55011 (CISPIR 11)
Group 1; Class ISM
0.15 MHz to
30 MHz
0.15 MHz to
30 MHz
 0.15 MHz to
30 MHz
ESD immunity
IEC 60947-4-1
±8 kV air,
±6 kV contact
±8 kV air,
±6 kV contact
±8 kV air,
±6 kV contact
Radiated immunity
IEC 60947-4-1
IEC 61000-4-3
10 V/m 80
MHz–1000 MHz
3 V/m from
1.4 to 2.7 GHz
80% amplitude
modulated
1 kHz sine wave
10 V/m 80
MHz–1000 MHz
3 V/m from
1.4 to 2.7 GHz
80% amplitude
modulated
1 kHz sine wave
10 V/m 80
MHz–1000 MHz
3 V/m from
1.4 to 2.7 GHz
80% amplitude
modulated
1 kHz sine wave
Conducted immunity
IEC 60947-4-1,
IEC 61000-4-6
140 dub (10V rms)
150 kHz–100 MHz
140 dub (10V rms)
150 kHz–100 MHz
140 dub (10V rms)
150 kHz–100 MHz
Fast transient immunity
IEC 60947-4-1
IEC 61000-4-4
±4 kV using direct method
with accessory installed
in expansion bay
±2 kV using direct method
±4 kV using direct method
with accessory installed
in expansion bay
±2 kV using direct method
±4 kV using direct method
with accessory installed
in expansion bay
±2 kV using direct method
Surge immunity
IEC 60947-4-1
IEC 61000-4-5
a Class 4
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line
(DM) –>1.2/50 us;
2 kV line-to-earth,
1 kV line-to-line
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line
(DM) –>1.2/50 us;
2 kV line-to-earth,
1 kV line-to-line
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line
(DM) –>1.2/50 us;
2 kV line-to-earth,
1 kV line-to-line
±4 kV line-to-ground (CM)
Power freq. magnetic field immunity
IEC 60947-4-1,
IEC 61000-4-8
30 A/m, 50 Hz 30 A/m, 50 Hz 30 A/m, 50 Hz
Electromagnetic field
IEC 60947-4-1,
 IEC 61000-4-3
10 V/m 10 V/m 10 V/m
Distortion IEEE 519  5% THD max.,
5th harmonic 3% max.
5% THD max.,
5th harmonic 3% max.
5% THD max.,
5th harmonic 3% max.
Electrostatic discharge (ESD)
IEC 61000-4-2,
EN 61131-2
4 kV contact
8 kV air discharge
4 kV contact
8 kV air discharge
4 kV contact
8 kV air discharge
Electrical fast
transient (EFT)
IEC 61000-4-4,
EN 61131-2
±2 kV using
direct method
±2 kV using
direct method
±2 kV using
direct method
Surge immunity
IEC 61000-4-5,
EN 61131-2
±2 kV
line-to-ground (CM)
±2 kV
line-to-ground (CM)
±2 kV
line-to-ground (CM)