EATON Freedom Series NEMA Contactors & Electric Motor Starters
Freedom Series - C440/XT Electronic Overload Relay
C440/XT Electronic Overload Relay
Product Description:
Eaton’s new electronic overload relay (EOL) is the most compact, highfeatured, economical product in its class. Designed on a global platform, the new EOL covers the entire power control spectrum including NEMA, IEC and DP contactors. The NEMA and DP versions are offered with the C440 designation while the IEC offering has the XT designation. The electronic design provides reliable, accurate and value driven protection and communications capabilities in a single compact device. It is the flexible choice for any application requiring easy-touse, reliable protection. Eaton has a long history of innovations and product development in motor control and protection, including both traditional NEMA, as well as IEC control. It was from this experience that the C440 was developed, delivering new solutions to meet today’s demands.
C440 is a self-powered electronic overload relay available up to 175A as a self contained unit. With external CTs, C440 can protect motor up to 1500 FLA. Available add-on accessories include remote reset capability and communication modules with I/O for DeviceNet, PROFIBUS, and Modbus.
Features:
Size/Range
Motor Control
Motor Protection
User Interface
|
Feature Options
|
Benefits
Reliability and Improved Uptime
- C440 provides the users with peace of mind knowing that their assets are protected with the highest level of motor protection and communication capability in its class
- Extends the life of plant assets with selectable motor protection features such as trip class, phase unbalance and ground fault
- Protects against unnecessary downtime by discovering changes in your system (line/load) with remote monitoring capabilities
- Status LED provides added assurance that valuable assets are protected by indicating the overload operational status
Flexibility
- Available with NEMA, IEC and DP contactors
- Improves return on investment by reducing inventory carrying costs with wide FLA adjustment (5:1) and selectable trip class
- Design incorporates built-in ground fault protection thus eliminating the need for separate CTs and modules
- Flexible communication with optional I/O enables easy integration into plant management systems for remote monitoring and control
- Available as an open component and in enclosed control and motor control center assemblies Monitoring Capabilities
- Individual phase currents RMS
- Average three-phase current RMS
- Thermal memory
- Fault indication (overload, phase loss, phase unbalance, ground fault)
Safety
|
Type AN19/59 Freedom Series Starters with C440 Electronic Overload Relays
NEMA Starter
Non-Reversing and Reversing | ||||||
NEMA Size | Continuous Ampere Rating |
Service Limit Current Rating (Amps) |
Maximum UL Horsepower | Three-Pole Non-Reversing (1)(2) Part Number |
Three-Pole Reversing (1)(2) Part Number |
|
230 V | 480V | |||||
00 | 9 | 11 | 1 | 2 | AN19AN0A5Exxx | AN59AN0A5Exxx |
0 | 18 | 21 | 2 | 5 | AN19BN0A5Exxx | AN59BN0A5Exxx |
1 | 27 | 32 | 3 | 10 | AN19DN0A5Exxx | AN59DN0A5Exxx |
2 | 45 | 52 | 7.5 | 25 | AN19GN0A5Exxx | AN59GN0A5Exxx |
3 | 90 | 104 | ~ | 50 | AN19KN0A5Exxx | AN59KN0A5Exxx |
4 | 135 | 156 | ~ | 100 | AN19NN0A5Exxx | AN59NN0A5Exxx |
5 (3) | 270 | 311 | ~ | 200 | AN19SN0A5Exxx | AN59SN0A5Exxx |
Type AN19/59 Freedom Series Starters with C440 with Ground Fault Electronic Overload Relays
NEMA Starter with Ground Fault
Non-Reversing and Reversing | ||||||
NEMA Size | Continuous Ampere Rating |
Service Limit Current Rating (Amps) |
Maximum UL Horsepower | hree-Pole Non-Reversing (1)(2) Part Number |
Three-Pole Reversing (1)(2) Part Number |
|
230 V | 480V | |||||
00 | 9 | 11 | 1 | 2 | AN19AN0A5G xxx | AN59AN0A5Gxxx |
0 | 18 | 21 | 2 | 5 | AN19BN0A5Gxxx | AN59BN0A5Gxxx |
1 | 27 | 32 | 3 | 10 | AN19DN0A5Gxxx | AN59DN0A5Gxxx |
2 | 45 | 52 | 7.5 | 25 | AN19GN0A5Gxxx | AN59GN0A5Gxxx |
3 | 90 | 104 | ~ | 50 | AN19KN0A5Gxxx | AN59KN0A5Gxxx |
4 | 135 | 156 | ~ | 100 | AN19NN0A5G xxx | AN59NN0A5Gxxx |
5 (3) | 270 | 311 | ~ | 200 | AN19SN0A5Gxxx | AN59SN0A5Gxxx |
Coil Voltage Code | ||||
Coil Volts and Hertz | Code Suffix | Coil Volts and Hertz | Code Suffix | |
120/60 or 110/50 | A | 380-415/50 | L | |
240/60 or 220/50 | B | 550/50 | N | |
480/60 or 440/50 | C | 24/60, 24/50 | T | |
600/60 or 550/50 | D | 24/50 | U | |
208/60 | E | 32/50 | V | |
277/60 | H | 48/60 | W | |
208-240/60 | J | 48/50 | Y | |
240/50 | K | 48/50 | Y |
C440 FLA Range (FVNR and FVR Starters Only) | ||||
NEMA Size | OLR Code | FLA Range | OLR Code | FLA Rating |
00 | 1p6 | 0.33 - 1.65A | 020 | 4.0 - 20A |
005 | 1.0 - 5.0A | ~ | ~ | |
0 | 1p6 | 0.33 - 1.65A | 020 | 4.0 - 20A |
005 | 1.0 - 5.0A | ~ | ~ | |
1 | 1p6 | 0.33 - 1.65A | 020 | 4.0 - 20A |
005 | 1.0 - 5.0A | 045 | 9.0 - 45A | |
2 | 1p6 | 1.0 - 5.0A | 045 | ~ |
020 | 4.0 - 20A | ~ | ~ | |
3 | 100 | 20 - 100A | ~ | ~ |
4 | 140 | 28 - 140A | ~ | ~ |
5 (3) | 300 | 60 - 300A | ~ | ~ |
Notes
(1) Gold A indicates coils suffix required, see Coil Suffix table above.
(2) xxx indicates OLR designation required, see C440 FLA Range table above.
(3) NEMA Size 5 starter available with 60-300A panel mounted CTs. Starter shipped as an assembled unit with 1–5A C440 overload relay (C440A1A005SELAX or C440A2A005SELAX)
Compact NEMA Size 1 and 4 Starters New Compact NEMA Size 1 and 4 starters - available with electronic overload relay only. |
|||||
NEMA Size | Continuous Ampere Rating |
Service Limit Current Rating (Amps) |
Maximum UL Horsepower | Three Pole Non-Reversing Part Number |
|
Single-Phase 230V |
Three-Phase 480V |
||||
Standard Fault Overload | |||||
1C | 27 | 32 | 3 | 10 | AN19CN0A5Exxx |
4C | 135 | 156 | ~ | 100 | AN19MN0A5Exxx |
Ground Fault Overload | |||||
1C | 27 | 32 | 3 | 10 | AN19CN0A5Gxxx |
4C | 135 | 156 | ~ | 100 | AN19MN0A5Gxxx |
Notes
(1) GOLD A indicates coils suffix required, see Coil Suffix table above.
(2) xxx indicates OLR designation required.
Electrical Life at Rated Continuous Current | ||
NEMA Size | Rated Current (Amperage) AC3/AC4 | Operations |
1C | 27/150 | 2,500,000/40,000 |
1 | 27/153 | 5,000,000/110,000 |
4C | 135/516 | 500,000/40,000 |
4 | 135/822 | 800,000/70,000 |
Freedom Series - C440/XT Standalone Overload Relays (XT, C440)
Short Circuit Ratings (North America CSA, cUL)
Changes to UL 508A and NEC in recent years have brought a focus to control panel safety with regard to short-circuit current ratings (SCCR). Eaton’s C440 electronic overload relays combined with XT series IEC and Freedom Series NEMA contactors provide a wide variety of SCCR solutions needed for a variety of applications. The SCCR data in this document reflects the latest information as of April 2010.
Overload FLA Range |
Maximum Operating Voltage |
Standard-Fault Short Circuit Data | High-Fault Short Circuit Data Fuses (RK5, J, CC) |
Thermal-Magnetic Circuit Breakers | ||||||
600V (kA) | Maximum Fuse Size (A) (RK5) |
Maximum Breaker Size (A) |
480V (kA) | 600V (kA) | Fuse Size | 480V (kA) | 600V (kA) | Breaker Size | ||
0.33-1.65A | 600 Vac | 1 | 6 | 15 | ~ | ~ | ~ | ~ | ~ | ~ |
1-5A | 600 Vac | 5 | 20 | 20 | 100 | 100 | 30 | 100 | 35 | 20 |
4-20A | 600 Vac | 5 | 80 | 80 | 100 | 100 | 100 | 100 | 35 | 80 |
9-45A | 600 Vac | 5 | 175 | 175 | 100 | 100 | 100 | 100 | 35 | 100/175 (480/600) |
20-100A | 600 Vac | 10 | 400 | 400 | 100 | 100 | 200 | 150 | 35 | 250/400 (480/600) |
28-140A | 600 Vac | 10 | 450 | 500 | 100 | 100 | 400 | 100 | 65 | 400 |
35-175A | 690 Vac | 10 | 500 (gG) | 350 (690 Vac) 320 (415 Vac) |
100 | 100 | 500 (gG) | 100 (415 Vac) | ~ | 350 (LGC3350) 320 (NZMH3) |
NEMA Freedom Series Starters with C440 Electronic Overload Relays
NEMA Size |
Maximun Operating Voltage |
High-Fault Short Circuit Data | Thermal-Magnetic Circuit Breakers | ||||
Fuses (RK5, J, CC) 480V |
600V | Maximun Fuse Size |
480V | 600V | Maximum Breaker Size |
||
00 | 0.33-1.65A | 100 | 100 | 30 | ~ | ~ | ~ |
1-5A | 100 | 100 | 30 | 100 | 35 | 35 | |
4-20A | 100 | 100 | 30 | 100 | 35 | 35 | |
0 | 0.33-1.65A | 100 | 100 | 60 | ~ | ~ | ~ |
1-5A | 100 | 100 | 60 | 100 | 35 | 70 | |
4-20A | 100 | 100 | 60 | 100 | 35 | 70 | |
1 | 0.33-1.65A | 100 | 100 | 100 | ~ | ~ | ~ |
1-5A | 100 | 100 | 100 | 100 | 35 | 100 | |
4-20A | 100 | 100 | 100 | 100 | 35 | 100 | |
9-45A | 100 | 100 | 100 | 100 | 35 | 100 | |
2 | 1-5A | 100 | 100 | 100 | 100 | 35 | 175 |
4-20A | 100 | 100 | 100 | 100 | 35 | 175 | |
9-45A | 100 | 100 | 100 | 100 | 35 | 175 | |
3 | 20-100A | 100 | 100 | 200 | 50 | 50 | 250 |
4 | 28-140A | 100 | 100 | 400 | 100 | 65 | 300 |
Freedom Series - Communication
The C440/XTOE is provided with two levels of communication capability
The following information can be viewed using the communication option:
|
|
|
Advanced Communication—Communication Adapter with Communication Module
Basic Communication via Expansion Module— Monitoring Only
Basic communication on the C440 is accomplished using an expansion module (C440-XCOM). The expansion module plugs into the expansion bay on the C440 overload relay, enabling communications with the overload via their Modbus RTU (RS-485) network. No additional cards or modules are required.
Advanced Communication—Monitoring and Control
C440 also has the ability to communicate on industrial protocols such as Modbus RTU, DeviceNet, PROFIBUS, Modbus TCP, and EtherNet/IP while providing control capability using I/O. An expansion module (C440- XCOM) combined with a communication adapter (C440-COM-ADP) and a communication module allows easy integration onto the customer's network.
Advanced Communication— Communication Adapter 2
The communication adapter (C440-COM-ADP) is required for obtaining control capability via communications within the C440 family. Combined with a communication module, the customer is provided with flexible mounting options (DIN rail or panel) along with four inputs and two outputs (24 Vdc or 120 Vac) as standard.
Notes
(1) Customer can wire remote mounted button to reset module (that is, 22 mm pushbutton, catalog number M22-D-B-GB14-K10).
(2) Modbus TCP and EtherNet/IP communication modules do not require the C440-COM-ADP communication adapter.
Communication Accessories
Description | Part Number | Description | Part Number | ||
Expansion module (Remote Reset/Modbus RTU, RS-485 Communication) | C440-XCOM | Communication adapter kit (DIN C Panel mounted adapter, required for advance communication option) | C440-XCOM |
Description | Part Number |
DeviceNet communication module kit-120V I/O (consists of C440-XCOM + C441K + C440-COM-ADP) |
C440-DN-120 |
DeviceNet communication module kit-24 Vdc I/O (consists of C440-XCOM + C441L + C440-COM-ADP) |
C440-DN-24 |
PROFIBUS communication module kit-120V I/O (consists of C440-XCOM + C441S + C440-COM-ADP) |
C440-DP-120 |
PROFIBUS communication module kit-24V I/O (consists of C440-XCOM + C441Q + C440-COM-ADP) |
C440-DP-24 |
Modbus communication module kit-120V I/O (consists of C440-XCOM + C441N + C440-COM-ADP) |
C440-MOD-120 |
Modbus communication module kit-24 Vdc I/O (consists of C440-XCOM + C441P + C440-COM-ADP) |
C440-MOD-24 |
Modbus TCP/Ethernet IP communication module kit-120V I/O (consists of C440-XCOM + C441U) |
C440-ET-120 |
Modbus TCP/Ethernet IP communication module kit-24V I/O (consists of C440-XCOM + C441V) |
C440-ET-24 |
Freedom Series - Communication Modules
- ↑
- Modbus Communication Module
- DeviceNet Communication Modules
- PROFIBUS Communication Modules
- Ethernet Communication Modules
Click Above Tab to Open Content - Click ↑ to Close |
Modbus Communication Module
Modbus Communication Module
Overview
The Modbus communication module combined with an expansion module and a communication adapter provides monitoring and control capability to the C440/XTOE electronic overload relay via Modbus RTU communications. These modules also provide convenient I/O with 24 Vdc or 120 Vac options.
Features and Benefits
Terminals
|
Selectable I/O assemblies
|
DeviceNet Communication Modules
DeviceNet Communication Module
Overview
The DeviceNet communication module combined with an expansion module and a communication adapter provides monitoring and control capability to the C440/XTOE electronic overload relay via DeviceNet communications. These modules also provide convenient I/O with 24 Vdc or 120 Vac options
Features and Benefits
Configuration
Terminals
|
Selectable I/O assemblies
|
PROFIBUS Communication Modules
PROFIBUS Communication Module
Overview
The PROFIBUS communication module combined with an expansion module and a communication adapter provides monitoring and control capability to the C440 / XTOE electronic overload relay via PROFIBUS communications. These modules also provide convenient I/O with 24 Vdc or 120 Vac options.
Features and Benefits
|
Terminals
Selectable I/O assemblies
|
Ethernet Communication Modules
Ethernet with I/O Module
Overview
The Ethernet communication module combined with an expansion module provides both Modbus TCP and EtherNet/IP communication capabilities with built-in HTTP web services to the C440/ XTOE overload relay. Unlike the other communications modules, a communication adapter (C440-COM-ADP) is not required when using the Ethernet communication module in C440/XTOE applications.
The Ethernet communication module has built-in I/O providing communication, monitoring and control for the C440/XTOE overload relay.
Features and Benefits
Terminals
|
Selectable I/O assemblies
|
Description | I/O | Part Number |
Modbus TCP / EtherNet/IP Communication Module, 4IN/2OUT (DIN/Panel) | 120 Vac | C441U |
Modbus TCP / EtherNet/IP Communication Module, 4IN/2OUT (DIN/Panel) | 24 Vdc | C441V |