EATON Freedom Series NEMA Contactors & Electric Motor Starters
Eaton Freedom Series DC Magnet Coils
When Ordering Specify Conversion Kit for Field Assembly
- Part number
Factory Installed DC Coil
- For factory installed DC magnet coil on AC contactors or noncombination starters (open type only), substitute the code suffix from the table on this page for the magnet coil identifier in the device catalog number. EXAMPLE: For Size 0 AC contactor with a 24 Vdc coil, change AN16BN0AC to AN16BN0T1C
Application
- Connect for separate control
- Not for use with cover control switch operators
- Use twin break, heavyduty pilot devices
- Designed for +10%, –20% rated voltage, continuous duty operation
Non-Reversing Kit Consists of:
- One encapsulated DC magnet coil
- One NCI or NO/NCI side mounted auxiliary contact. Note: These kits are supplied with a NO/NCI side mounted auxiliary contact in place of the NCI contact.
- Two blue colored connection wires
- One instruction publication
Operation
These DC coil kits have separate pick-up and seal windings. A special (side mounted) early-break NCI auxiliary contact is used to either disconnect the pick-up winding or insert the seal winding in series with the pick-up winding, depending on the frame size of the contactor. DC coil kits come in two styles, a suffix 1 and a suffix 4. Suffix 1 contains only the special (side mounted) early break NCI auxiliary contact. Suffix 4 contains a NO contact in the same package as the special (side mounted) early-break NCI auxiliary contact.
Note: For NEMA Sizes 00 and 0 and IEC Sizes A–F, contactors may utilize either suffix 1 or 4 DC coil kits; starters may utilize suffix 4 DC coil kits only. For NEMA Sizes 1 and 2 and IEC Sizes G–K, both contactors and starters may utilize a suffix 4 DC coil kit only.
On the above sizes only, when the special auxiliary package is mounted on the side of a contactor or starter, no standard auxiliary contact may be mounted on the same side.
Note: For NEMA Sizes 3–5 and IEC Sizes L–S, special coil NCI clearing contact is an add-on auxiliary (must mount on a base mount auxiliary contact; normally a 1NO). This arrangement will normally account for two of the three contact positions on the side of each contactor or starter.
Contactor or Starter Size | Magnet Coil | Complete Conversion Kit | Factory Installed | |||||
NEMA | IEC | Volts | Coil Number | Amps P.U./Seal | Watts P.U./Seal | NCI Interlock | Part Number | Code Suffix |
Non-Reversing—Kit Includes NCI Side Mounted Auxiliary Contact | ||||||||
00 and 0 CN35-A, B, D D15 Relays |
A - F | 12 | 9-2988-11 | 6.4/0.28 | 76.8/3.36 | C320KGD1 | C335KD3R1 | R1 |
24 | 9-2988-12 | 3.2/0.14 | 76.8/3.36 | C320KGD1 | C335KD3T1 | T1 | ||
48 | 9-2988-13 | 1.6/0.07 | 76.8/3.36 | C320KGD1 | C335KD3W1 | W1 | ||
120 | 9-2988-14 | 0.64/0.028 | 76.8/3.36 | C320KGD1 | C335KD3A1 | A1 | ||
(1) 00 and 0 CN35-A, B, D D15 Relays |
A - F | 12 | 9-2988-11 | 6.4/0.28 | 76.8/3.36 | C320KGD2 (1) | C335KD3R4 | R4 |
24 | 9-2988-12 | 3.2/0.14 | 76.8/3.36 | C320KGD2 (1) | C335KD3T4 | T4 | ||
48 | 9-2988-13 | 1.6/0.07 | 76.8/3.36 | C320KGD2 (1) | C335KD3W4 | W4 | ||
120 | 9-2988-14 | 0.64/0.028 | 76.8/3.36 | C320KGD2 (1) | C335KD3A4 | A4 | ||
1 and 2 CN35-G |
G-K | 12 | 9-2990-1 | 15.4/0.42 | 185/4.98 | C320KGD5 | C335KD4R4 | R4 |
24 | 9-2990-2 | 7.7/0.021 | 185/4.96 | C320KGD5 | C335KD4T4 | T4 | ||
48 | 9-2990-3 | 3.9/0.11 | 185/5.04 | C320KGD5 | C335KD4W4 | W4 | ||
120 | 9-2990-4 | 1.5/0.041 | 185/4.87 | C320KGD5 | C335KD4A4 | A4 | ||
3 CN35-K |
L-N | 12 | 9-3002-1 | 24/0.40 | 293/4.84 | C320KGD3 | C335KD5R1 | R1 |
24 | 9-3002-2 | 12/0.20 | 288/4.75 | C320KGD3 | C335KD5T1 | T1 | ||
48 | 9-3002-3 | 6.1/0.097 | 295/4.67 | C320KGD3 | C335KD5W1 | W1 | ||
120 | 9-3002-4 | 2.5/0.038 | 298/4.57 | C320KGD3 | C335KD5A1 | A1 | ||
4 and 5 CN35-N, S |
P - S | 24 | 9-2026-4 | 18/0.22 | 400/5.3 | C320KGD3 | C335KA3T1 | T1B |
48 | 9-2026-3 | 9/0.11 | 400/5.2 | C320KGD3 | C335KA3W1 | W1B | ||
120 | 9-2026-2 | 3.3/0.05 | 450/5.4 | C320KGD3 | C335KA3A1 | A1B | ||
240 | 9-2026-1 | 1.7/0.02 | 440/4.9 | C320KGD3 | C335KA3B1 | B1B | ||
Reversing | ||||||||
00 and 0 CN35-A, B, D D15 relays |
A - F | 12 | (2) 9-2988-1 | 6.4/0.28 | 76.8/3.36 | (2) C320KGD1 | C335RD3R1 (2) | R1 (3) |
24 | (2) 9-2988-2 | 3.2/0.14 | 76.8/3.36 | (2) C320KGD1 | C335RD3T1 (2) | T1 (3) | ||
48 | (2) 9-2988-3 | 1.6/0.07 | 76.8/3.36 | (2) C320KGD1 | C335RD3W1 (2) | W1 (3) | ||
120 | (2) 9-2988-4 | 0.64/0.028 | 76.8/3.36 | (2) C320KGD1 | C335RD3A1 (2) | A1 (3) | ||
1 and 2 CN35-G |
G - K | 12 | (2) 9-2990-1 | 15.4/0.42 | 185/4.98 | (2) C320KGD3 | (4) | R1 (3) |
24 | (2) 9-2990-2 | 7.7/0.21 | 185/4.96 | (2) C320KGD3 | (4) | T1 (3) | ||
48 | (2) 9-2990-3 | 3.9/0.11 | 185/5.04 | (2) C320KGD3 | (4) | W1 (3) | ||
120 | (2) 9-2990-4 | 1.5/0.041 | 185/4.87 | (2) C320KGD3 | (4) | A1 (3) |
Notes
(1) These kits are supplied with a NO/NCI side mounted auxiliary contact in place of the NCI contact.
(2) Kit does not include mechanical interlock or crossover wiring. Two NO/NCI top mounted auxiliary contacts are supplied for electrical interlocking.
(3) Factory installed DC coils on NEMA contactors and starters include a NO/NC top mounted auxiliary contact on each contactor for electrical
interlocking. On IEC contactors and starters, a NC top mounted auxiliary contact is supplied on each contactor for electrical interlocking.
(4) Available factory assembled only.