H2105B-3 |
|
|
H2105B-3 For Use with:
|
Type H2111B-3 Heater Pack Shown |
Overload Relay Size |
Motor Full Load Ampere Rating Dial Position | |||
---|---|---|---|---|
A | B | C | D | |
NEMA Sizes 00-0 Series C, NEMA Sizes 1-2 Series B, IEC Sizes A-F Series C, IEC Sizes G-K Series B | ||||
32A or 75A | 1.28 | 1.55 | 1.83 | 2.1 |
Size 5 Starters Only-Series B and IEC P, R and S with 300/5 CT | ||||
32A(2) | 77 | 93 | 110 | 126 |
Size 6 Starters Only-Series B and IEC T-V with 600/5 CT | ||||
32A(2) | 154 | 186 | 220 | 252 |
Size 7 Starters Only-Series B and IEC W-X with 1000/5 CT | ||||
32A(2) | 256 | 310 | 366 | 420 |
Size 8 Starters Only-Series B and IEC Z with 1500/5 CT | ||||
32A(2) | 384 | 465 | 549 | 630 |
NOTES:
(1) The series of a starter is the last digit of the listed catalog number. Example: AN16DN0AB.
(2) Sizes 5–8 and IEC P–Z use the 32A overload relay with current transformers.
Heater packs are shipped three to a carton. catalog numbers are for three heater packs.
NEMA—AN Type | IEC—AE Type | ||
---|---|---|---|
Size | Series | Size | Series |
00–0 | C | A–F | C |
1–2 | B | G–K | B |
5 | B | G–K | B |
6 | C | G–K | B |
7–8 | B | G–K | B |
© KMParts.com, Inc. All rights reserved.