Menu

AN16SN0AB



AN16SN0AB
Replace the desired magnet coil alpha designation in the part number (A) with the proper Coil Voltage Code.
See chart below.

Prices of starters do not include heater packs. Select two packs (two overload relays, one for each speed). Click Here for Heater Pack Selection.

For Product Description & General Information Page Click Here.

AN16SN0AB Type AN16 NEMA
Manual or Automatic Reset Overload Relay
Non-Reversing and Reversing Starters(1)

NEMA Size Continuous
Amperes Rating
Service-Limit
Current
Rating
(Amperes)(4)
Maximum UL Horsepower(2)
Three-Phase
Type
230V 480V
5 270 311 200 Three-Pole
Non-Reversing (3)

NOTES:
(1) Starter Part numbers do not include heater packs. Select one carton of three heater packs. Heater pack selection
(2) Maximum horsepower rating of starters for 380V 50 Hz applications please see Horsepower Chart Below.
(3) Underscore (_) indicates coil suffix required, see AC Suffix table
(4) The service-limit current ratings represent the maximum rms current, in amperes, which the controller shall be permitted to carry for protracted periods in normal service. At service-limit current ratings, temperature rises shall be permitted to exceed those obtained by testing the controller at its continuous current rating. The current rating of overload relays or trip current of other motor protective devices used shall not exceed the service-limit current rating of the controller.
(5) Common control. For separate 120V control, insert letter D in 7th position of listed catalog number. Example: AN56VND0CB.
(6) NEMA Sizes 00 and 0 only.
(7) NEMA Sizes 00 and 0 only. Sizes 1–8 are 24/60 only.

Coil Voltage Chart

Coil Volts and Hertz Code Suffix   Coil Volts and Hertz Code Suffix
120/60 or 110/50 A 380-415/50 L
240/60 or 220/50 B 550/50 N
480/60 or 440/50 C 24/60, 24/50 T
600/60 or 550/50 D 24/50 U
208/60 E 32/50 V
277/60 H 48/60 W
208-240/60 J 48/50 Y
240/50 K

For Sizes 00–2, the magnet coil alpha designation will be the next to the last digit of the listed catalog number.
EXAMPLE: For a 380V, 50 Hz coil, change CN15BN3_B to CN15BN3LB. For all other sizes, the magnet coil alpha designation will be the last digit of the listed catalog number.


Horsepower Chart

NEMA Size 00 0 1 2 3 4 5 6 7 8
Horsepower 1.5 5 10 25 50 75 150 300 600 900

Dimensions




NEMA
Size
Wide
A
High
B
Deep
C
Mounting
D
Mounting
E
Mounting
F
Mounting
G
Shipping Weight
Lbs (kg)
00–0 1.80
(45.7)
6.60
(167.6)
3.52
(89.4) 
6.07
(154.2)
4.90
(124.5)
0.54
(13.7)
2.2
(1.0)
1–1P 2.56
(65.0)
7.08
(179.8)
4.44
(112.8)
2.00
(50.8)
6.63
(168.4)
5.80
(147.3)
0.54
(13.7)
4.5
(2.0)
2 2.56 (65.0) 8.08
(205.2)
4.44
(112.8)
2.00
(50.8)
7.63
(193.8)
5.80
(147.3)
0.54
(13.7)
4.7
(2.1)
3 4.08 (103.6) 11.35 (288.3) 5.94 (150.9) 3.00
(76.2)
10.81
(274.6)
11.0
(5.0)
4 7.05 (179.1) 12.06 (306.3) 7.25 (184.2) 6.00 (152.4) 8.50 (215.9) 23.0
(10.4)
7.00 (177.8) 17.77 (451.4) 7.76 (197.1) 6.00 (152.4) 16.00 (406.4) 36.0 (16.3)
6 9.47 (240.5) 21.69 (550.9) 9.90 (251.5) 3.10 (78.7) 18.00 (457.2) 75.0 (34.1)
7 15.13 (384.3) 29.13 (739.9) 12.64 (321.1) 13.25 (336.6) 21.25 (539.8) 120.0 (54.5)
8 15.13 (384.3) 34.50 (876.3) 15.00 (381.0) 13.25 (336.6) 16.75 (425.5) 210.0 (95.3)

NOTES:
(1) Holding circuit contact for Size 00 occupies 4th power pole position—no increase in width




Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.