C320KGT2 |
|
|
C320KGT2 Top Mounted |
Top Mounted Auxiliary Contact Shown |
Description | Contact Configuration Code(2) |
---|---|
1NC | 01 |
NOTES:
(1) NCI = Normally Closed early opening designed for use in reversing applications. EC = Early Closing. LO = Late Opening.
(2) For reference only—not part of catalog number.
Heater packs are shipped three to a carton. catalog numbers are for three heater packs.
NEMA Sizes 00–2, IEC Sizes A–K
The sketches below illustrate the maximum number of auxiliary contacts that can be assembled to a contactor or starter and their locations.
Size | Poles | Available Mounting Positions(1)(2) | Part Number |
|
---|---|---|---|---|
Open Type | Enclosed | |||
A–K | 3 | 1, L1 | L1 | AE16 |
00 | 3 | T1, L1, R1 | L1 | AN16 |
0–2 | 3 | T1, L1 | L1 | |
A–K | 3 | L1, R1 | L1, R1 | AE56 |
00–2 | 3 | T1, T2 | — | AN56 |
A–C | 2–4 | T1, L1, R1 | L1, R1 | CE15 |
D–K | 3 | T1, L1 | L1 | |
G–J | 4 | T1, R1 | — | |
G–J | 5 | T1 | — | |
00 | 2–4 | T1, L1, R1 | L1 | CN15 |
0–2 | 2–3 | T1, L1 | L1 | |
1, 2 | 4 | T1, L1 | — | |
1, 2 | 5 | T1, L1 | — | |
10A | 2–4 | T1, L1, R1 | L1 | CN35 |
20–60A | 2–3 | T1, L1 | L1 | |
60A | 4 | T1, L1 | — | |
60A | 5 | T1, L1 | — | |
A–K | 3 | L1, R1 | L1, R1 | CE55 |
00–2 | 3 | T1, T2 | — | CN55 |
NEMA Sizes 3–8, IEC Sizes L–Z
The sketches below illustrate the maximum number of auxiliary contacts that can be assembled to a contactor and their locations.
NOTE: A base auxiliary contact must be added in position R1 before additional auxiliary contacts can be mounted on NEMA Size 3 and IEC Sizes L–N, or in L1 on NEMA Sizes 4–5 and IEC Sizes P–S.
Size | Available Mounting Positions(1)(2) |
---|---|
NEMA Size 3, IEC Sizes L–N | R2, R3, L1, L2, L3 |
NEMA Sizes 4–5, IEC Sizes P–S | L2, L3, R1, R2, R3 |
NEMA Sizes 6–7, IEC Sizes T–X | R1 |
NEMA Size 8, IEC Size Z | L2, R2 |
NOTES:
(1) Available positions on contactors or starters other than what is factory installed.
(2) When a pneumatic timer is mounted on contactor, only side mounted auxiliary contact positions are available. The solid-state timer, when added, takes up side mounted auxiliary contact position.
© KMParts.com, Inc. All rights reserved.