Eaton A200 Series - NEMA Contactors, Starters, Relays & Shoe Breakes
Thermal Type B, Class 20, Manual Reset
Application DescriptionThe Type B overload relay is designed to protect industrial motors against overload conditions. Using modern block type, bimetallic design, this relay will provide Class 20 operation in either single-phase or three-phase applications. OperationThe Type B overload relay is a bimetallic actuated device. The bimetal elements are operated by precisely calibrated heaters. The heater elements are connected either directly in the circuit to be measured, or through current transformers on applications NEMA Size 5 and larger. As the bimetals are heated by motor current flow, a deflection force is produced. Upon a sustained level of abnormal current flow, the deflection becomes great enough to open the snapaction utput contact. HeatersEnter heaters as separate item by listing catalog number from tables CLICK HERE |
Ambient CompensationThe Type B ambient compensated design is supplied as standard on all A200 starters. This design uses a second compensating bimetal responsive to ambient air temperature in the surrounding enclosure. This feature reduces nuisance tripping in applications using compact control panels and motor control centers where internal temperature rise is significant compared to motor ambient temperature. The compensating characteristic is maintained in ambient temperatures from 40° to 77°C. Features
|
Motor Full Load Amps |
Panel Mounted | Starter Mounted | Replacement for Type A Overload Relays in Manual Reset Mode (Three-Pole Only) (1) |
|||
Ambient Comp. Part Number |
Non-Comp. Part Number |
Replacement for Type B Overload Relays |
Ambient Comp. Part Number |
Non-Comp. Part Number |
||
Ambient Comp. Part Number |
Non-Comp. Part Number |
|||||
Single-Pole (One NC Contact) | ||||||
0.25–26.2 | BA11JP | BN11JP | BA11A | BN11A | - | - |
26.3–45 | BA21JP | BN21JP | BA21A | BN21A | - | - |
19–90 | Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
19–135 | Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
Use three-pole design, wire three poles in series |
Three-Pole (One NC Contact) | ||||||
0.25–26.2 | BA13JP | BN13JP | BA13A (2) | BN13A (2) | BA13J | BN13J |
26.3–45 | BA23JP | BN23JP | BA23A | BN23A | BA23J | BN23J |
19–90 | BA33P | BN33P | BA33A | BN33A | BA33A | BN33A |
19–135 | BA43P | BN33P | BA43A | BN43A | BA43A | BN43A |
Accessories - Alarm Contact Kit Selection (1)
Type B Overload Relay Size | Part Number |
1, 2 | B3NO-2 |
3, 4 | B3NO-4 |
Notes:
(1) Includes contactor mounting bracket, overload relay and connection straps to contactor.
(2) For replacement on B200 size 00, 0, 1 use BA23A instead of BA13A and use BN23A instead
of BN13A.
Thermal Type A (1), Class 20, Auto/Manual Reset
Application DescriptionThe Type A overload relay is designed to protect industrial motors against overload conditions. Using modern block type, bimetallic design, this relay will provide Class 20 operation in either singleor three-phase applications. Features
HeatersEnter heaters as separate item by listing catalog number from tables CLICK HERE |
OperationThe Type A overload relay is a bimetallic actuated device. The bimetal elements are operated by precisely calibrated heaters. The heater elements are connected either directly in the circuit to be measured, or through current transformers on applications NEMA Size 5 and larger. As the bimetals are heated by motor current flow, a deflection force is produced. Upon a sustained level of abnormal current flow, the deflection becomes great enough to open the snapaction output contact. Automatic ResetThe Type A overload relay can be supplied as an option on all A200 starters to provide automatic reset operation. The overload relay is always shipped in the non-automatic mode. To set up auto operation, reposition the reset rod by loosening and retightening a hold-down clamp at the base of overload relay. |
Motor Full Load Amps |
Panel Mounted | Starter Replacement | ||||
Ambient Comp. Part Number |
Non-Comp. Part Number |
Ambient Comp. Part Number |
Non-Comp. Part Number |
|||
Single-Pole (One NC Contact) | ||||||
0.25–26.2 | AA11P | AN11P | AA11A | AN11A | ||
26.3–45 | AA21P | AN21P | AA21A | AN21A | ||
19–90 | AA31P | AN31P | AA31A | AN31A | ||
19–135 | AA41P | AN41P | AA41A | AN41A | ||
Three-Pole (One NC Contact) | ||||||
0.25–26.2 | AA13P (2) | AN13P (2) | AA13A (2) | AN13A (2) | ||
26.3–45 | AA23P (2) | AN23P (2) | AA23A (2) | AN23A (2) | ||
19–90 | AA33P (2) | AN33P (2) | AA33A (2) | AN33A (2) | ||
19–135 | AA43P (2) | AN43P (2) | AA43A (2) | AN43A (2) |
Notes:
(1) Includes contactor mounting bracket, overload relay and connection straps to contactor.
(2) For replacement on B200 size 00, 0, 1 use BA23A instead of BA13A and use BN23A instead
of BN13A.
Type FT Fast Trip, Class 10
Application DescriptionThe Type FT overload relay is designed to protect special purpose motors having restricted thermal and locked rotor capabilities. Using modern block type, bimetallic design, this relay will provide Class 10 operation in singleor three-phase applications. Features
|
OperationThe Type FT overload relay is a bimetallic actuated device. The bimetal elements are operated directly from line current, thus separate calibrating heater elements are not utilized. The overload relay may be wired directly in the motor circuit, or throughcurrent transformers on applications larger than 150A. As the bimetals are heated by motor current flow, a deflection force is produced. Upon a sustained level of abnormal current flow, the deflection becomes great enough to open the snap action output contact. |
Motor Full Load Amperes |
Panel Mounted | Starter Replacement | ||
Single-Pole Part Number |
Three-Pole Part Number |
NEMA Size | Single-Pole Part Number |
|
0.76–1.1 | FT11P-1.1 | FT13P-1.1 | - | FT11A-1.1 |
1.1–1.6 | FT11P-1.6 | FT13P-1.6 | - | FT11A-1.6 |
1.6–2.4 | FT11P-2.4 | FT13P-2.4 | 0, 1 | FT11A-2.4 |
2.4–3.6 | FT11P-3.6 | FT13P-3.6 | 0, 1 | FT11A-3.6 |
3.6–5.4 | FT11P-5.4 | FT13P-5.4 | 0, 1 | FT11A-5.4 |
5.4–8.0 | FT11P-8.0 | FT13P-8 | 0, 1 | FT11A-8 |
8.0–12 | FT11P-12 | FT13P-12 | 0, 1 | FT11A-12 |
12–18 | FT11P-18 | FT13P-18 | 1 | FT11A-18 |
16–24 | - | FT13P-24 | - | - |
22–32 | FT11P-32 | FT13P-32 | 0, 1 | FT11A-32 |
24–36 | FT21P-36 | FT23P-36 | 2 | FT21A-36 |
36–54 | FT21P-54 | FT23P-54 | 12 | FT21A-54 |
22–32 | FT31P-32 | FT33P-32 | 3 | FT31A-32 |
32–48 | FT31P-48 | FT33P-48 | 3 | FT31A-48 |
48–72 | FT31P-72 | FT33P-72 | 3 | FT31A-72 |
72–110 | FT41P-110 | FT43P-110 | 4 | FT41A-110 |
100–150 | FT41P-150 | FT43P-150 | 4 | FT41A-150 |
Notes:
(1) Single-pole (1NO-NC contact): add suffix B. Three-pole (3NO-NC contacts): add suffix B. Example: FT13PB-12.
Relays—Current Sensing Protective
Product DescriptionThe IQ500 is a heaterless, current-sensing, solid-state motor protective relay with optional communications capabilities. Several functions are incorporated into the base relay (IQ502/IQ504) as standard:
The base relay can serve as the initial building block for a motor protection system by adding the IQ500M Special Function Module. The module can address application related motor load functions with the additional features:
|
The IQ500 can provide a costeffective alternative to conventional protective relays such as current relays, ground fault relays and phase loss or phase unbalance relays. Used with the PowerNet system, a lowcost, local area communication network, information such as current values, status, setpoint values and cause of trip can be displayed remotely. The IQ500 relay is ideal for a variety of industrial applications such as mining, timber, material handling, air conditioning compressors, wastewater treatment plants and petrochemical industries. Standards and Certifications
|
Features
|
Benefits
|
Optional Benefits
|
Maximum Horsepower | Control Voltage | ||||
200V | 230V | 460–475V | Ampere Rating |
110/120V 50/60 Hz Part Number |
220/240V 50/60 Hz Part Number |
20 | 25 | 50 | 3.4–66A | IQ502A | IQ502B |
60 | 75 | 150 | 10.8–207A | IQ504A | IQ504B |
- | - | - | 0.32–5.4A | IQ500LA (1) | IQ500LB (1) |
Special function module | IQ500M | IQ500M |
Notes:
(1) Can be used with external CTs having 5A secondary.