Searching...

Eaton Klockner Moeller
PROGRAMMABLE RELAYS

easy500 Stand Alone

Overview

  • 1:1 electronic circuit diagram entry
  • Circuit diagram entry directly on the device possible
  • 128 rungs with 3 contacts each and 1 coil in series
  • Functions such as multi-function timing relays, impulse relays, counters, analog value comparators, week and year time switches, value entry, value display….
  • Connection possible to Ethernet (programming and OPC functionality

Function

  • 16 counting relays (0 to 32000, up and down counter relays)
  • 2 frequency counters (max. 1 kHz)
  • 2 high-speed frequency counters (max. 1 kHZ)
  • 4 operating hours counters (the operating hours value is super retentive, i.e. also retained with program change)
  • 8 week time switches (4 channels per time switch, 1 on/off point per channel)
  • 16 timing relays (0.01s - 99h 59m, on-delayed and/or off-delayed (optional random switching), single pulse, flashing)
  • 8 jump function blocks
  • 3 master reset function blocks
  • 16 analog value comparators
  • 16 comparators
  • 16 text displays (4 x 12 characters, editable via programming software
  • Value entry (counter values, setpoints,…)
  • Value display (actual values,…)
  • Date and time entry
Inputs Outputs Further Features Supply Voltage Part Number
Digital Can be used for analog Relay 10A (UL) Transistor Display & Keypad Real-time clock
8 2 4 ~ 24 V AC EASY512- AB-RC
8 2 4 ~ ~ 24 V AC EASY512- AB-RCX
8 ~ 4 ~ ~ 100 - 240 V AC EASY512- AC-R
8 ~ 4 ~ 100 - 240 V AC EASY512- AC-RC
8 ~ 4 ~ ~ 100 - 240 V AC EASY512- AC-RCX
8 2 4 ~ 12 V DC EASY512- DA-RC
8 2 4 ~ ~ 12 V DC EASY512- DA-RCX
8 2 4 ~ ~ 24 V DC EASY512- DC-R
8 2 4 ~ 24 V DC EASY512- DC-RC
8 2 4 ~ ~ 24 V DC EASY512- DC-RCX
8 2 ~ 4 24 V DC EASY512- DC-TC
8 2 ~ 4 ~ 24 V DC EASY512- DC-TCX

easy700

Expandable: Digital inputs/outputs and bus systems AS-Interface, PROFIBUS-DP, CANopen, DeviceNet

Overview

  • Full functional range of an easy500
  • 128 rungs with 3 contacts each and 1 coil in series
  • Local and remote expansion
  • Connection possible to standard bus systems (Profibus, CANopen, DeviceNet, As-i) and ethernet (programming and OPC functionality)

Function

  • 16 counting relays (0 to 32000, up and down counter relays)
  • 2 frequency counters (max. 1 kHz)
  • 4 operating hours counters (the operating hours value is super retentive, i.e. also retained with program change)
  • 8 week time switches (4 channels per time switch, 1 on/off point per channel)
  • 16 timing relays (0.01s - 99h 59m, on-delayed and/or off-delayed (optional random switching), single pulse, flashing)
  • 8 jump function blocks
  • 3 master reset function blocks
  • 16 analog value comparators
  • 16 text displays (4 x 12 characters, editable via programming software
  • Value entry
    (counter values, setpoints,…)
  • Value display (actual values,…)
  • Date and time entry
Inputs Outputs Further Features Supply Voltage Part Number
Digital Can be used for analog Relay 10A (UL) Transistor Display & Keypad Real-time clock
12 4 6 ~ 24 V AC EASY719- AB-RC
12 4 6 ~ ~ 24 V AC EASY719- AB-RCX
12 ~ 6 ~ 100 - 240 V AC EASY719- AC-RC
12 ~ 6 ~ ~ 100 - 240 V AC EASY719- AC-RCX
12 4 6 ~ 12 V DC EASY719- DA-RC
12 4 6 ~ ~ 12 V DC EASY719- DA-RCX
12 4 6 ~ 24 V DC EASY719- DC-RC
12 4 6 ~ ~ 24 V DC EASY719- DC-RCX
12 4 ~ 8 24 V DC EASY719- DC-TC
12 4 ~ 8 ~ 24 V DC EASY719- DC-TCX

easy800

Expandable: Digital inputs/outputs and bus systems AS-Interface, CANopen, PROFIBUS-DP, DeviceNet

Overview

  • Full function range of an easy700
  • A host of additional funcitons such as PID controller, math functions, pulse width modulation…
  • 256 rungs with 4 contacts each and 1 coil in series
  • Digital and analog expandability
  • Integrated communication via easyNet (up to 8 devices - up to 1000m)
  • Connection possible to standard bus systems (Profibus, CANopen, DeviceNet, As-I) and Ethernet (programming and OPC functionality)

Function

  • 32 Counting relays (+/-231, up and down counter relays)
  • 4 frequency counters (max. 5 kHz)
  • 4 high-speed frequency counters (max. 5 kHz)
  • 2 incremental value counters (max. 3 kHz)
  • 4 operating hours counters (operating hours value is super retentive, i.e. also retained with program change)
  • 32 weekly time switches (4 channels per time switch, 1 on/off point per channel)
  • 32 year time switches
  • 1 set cycle time function block
  • 32 timing relays (0.005 s – 232 min, on-delayed and/or off-delayed (optional random switching), single pulse, flashing)
  • 32 jump function blocks
  • 32 conditional jump function blocks
  • 32 master reset function blocks
  • 32 analog value comparators
  • 32 comparators (ADD, SUB, MUL, DIV)
  • 32 PID controllers
  • 32 PT1 signal smoothing filter
  • 32 value scaling function blocks
  • 2 numerical converters
  • 2 pulse output function blocks
  • 2 pulse width modulation function blocks
  • 32 value limitation function blocks
  • 32 block comparison function blocks
  • 32 block transfer function blocks
  • 32 Boolean operation (AND, OR, NOT)
  • 32 comparators
  • 32 data function blocks
  • 32 data multiplexer
  • 32 shift registers
  • 32 table functions
  • 32 get value from NET function blocks
  • 32 put value in NET function blocks
  • 32 bit output from NET function blocks
  • 32 bit input from NET function blocks
  • 9 diagnostics alarms
  • 32 serial protocol function blocks
  • 1 synchronize clock via NET function blocks
  • 32 text displays (4 x 16 characters, editable via programming software)
  • Value entry (counter values, setpoints, …)
  • Value display (actual values, …)
  • Date and time entry
  • Date and time display
Inputs Outputs Further Features Supply Voltage Part Number
Digital Can be used for analog Relay 10A (UL) Transistor Analog Display & Keypad Real-time clock
12 ~ 6 ~ ~ 100 - 240 V AC EASY819- AC-RC
12 ~ 6 ~ ~ ~ 100 - 240 V AC EASY819- AC-RCX
12 4 6 ~ ~ 24 V DC EASY819- DC-RC
12 4 6 ~ ~ ~ 24 V DC EASY819- DC-RCX
12 4 6 ~ 1 24 V DC EASY820- DC-RC
12 4 6 ~ 1 ~ 24 V DC EASY820- DC-RCX
12 4 ~ 8 ~ 24 V DC EASY821- DC-TC
12 4 ~ 8 ~ ~ 24 V DC EASY821- DC-TCX
12 4 ~ 8 1 24 V DC EASY822- DC-TC
12 4 ~ 8 1 ~ 24 V DC EASY822- DC-TCX

Bluetooth Adapter


Description Part Number
Bluetooth-Adapter EASY800- BLT-ADP

SmartWire-DT

  • Exchange of data as well as power supply for the SmartWire-DT devices and contactors via the communication systems SmartWire-DT
  • Up to 99 SmartWire-DT devices in total with up to 166 inputs/outputs can be connected
  • easyNet as well as 4 additional fast inputs, 2 of which can be used as fast outputs
  • Serial interface for programming or for connection of a remote text display or touch panel or for connection to the Ethernet

Description Supply Voltage Part Number
Control relay with SmartWire-DT 24 V DC EASY802- DC-SWD
Control relay with SmartWire-DT, 4 inputs, 2 of which can be
used as outputs (transistor 24 V DC, 0.1 A)., easyNET on board
EASY806- DC-SWD

MFD Titan

Overview

MFD Titan

Combines the functions of an easy800 with comfortable visualization for larger
applications with up to 320 I/O

  • Fast and easy to install in 22.5 mm standard fixing holes
  • I/O modules for direct temperature measuring (Pt100 / Ni1000)
  • Individual laser inscription of devices, for example with own company name or logo
  • Digital and analog expandability
  • Communication via easyNet possible (up to 8 devices - up to 1000 m)
  • Connection possible to standard bus systems (PROFIBUS-DP, CANopen, DeviceNet, As-i) and Ethernet (programming and OPC functionalty)

Display/Operator Unit

MFD Titan Dispaly/Operator Unit
Description Part Number
WITH keypad, WITH Eaton logotype. NEMA 4x in conjuction with MFD-XM-80
protective diaphragm
MFD- 80-B
WITH keypad, WITHOUT Eaton logotype. NEMA 4x in conjuction with MFD-XM-80
protective diaphragm
MFD- 80-B-X
WITHOUT keypad, WITH Eaton logotype. NEMA 4x MFD- 80
WITHOUT keypad, WITH Eaton logotype. NEMA 4x MFD- 80-X

Power Supply - CPU Modules

MFD Titan Power Supply / CPU Modules
Supply Voltage Description Part Number
100 - 240 V AC Program and screen memory MFD-AC- CP8-ME
100 - 240 V AC Program and screen memory,
with easyNet
MFD-AC- CP8-NT
24 V DC Program and screen memory MFD- CP8-ME
Program and screen memory,
with easyNet
MFD- CP8-NT
Double program and screen memory (as MFD-CP8) MFD- CP10-ME
Double program and screen memory (as MFD-CP8), with easyNet MFD- CP10-NT

I/O Modules

MFD Titan I/O Modules
Supply Voltage For use with Inputs Outputs Temp. Ranges Part Number
Digital Can be used for analog Pt100 Relay 10a (UL) Trans-
istor
Analog
24 V DC MFD-CP8...
MFD-CP10...
12 4 ~ 4 ~ ~ ~ MFD- R16
24 V DC MFD-CP8...
MFD-CP10...
12 4 ~ ~ 4 ~ ~ MFD- T16
24 V DC MFD-CP8...
MFD-CP10...
12 4 ~ 4 ~ 1 ~ MFD- RA17
24 V DC MFD-CP8...
MFD-CP10...
12 4 ~ ~ 4 1 ~ MFD- TA17
100 - 240 V AC MFD-AC-CP8... 12 ~ ~ 4 ~ ~ ~ MFD- AC-R16

I/O Modules with Temperature Detection

MFD Titan I/O Modules with Temperature Detection
Supply Voltage For use with Inputs Outputs Temperature Ranges Part Number
Digital Can be used for analog Pt100 Relay 10a (UL) Trans-
istor
Analog
24 V DC MFD-CP8 from device version 08, MFD-CP10 6 2 2 ~ 4 ~ -40...+90°C
0...+250°C
0...+400°C
MFD- TP12-PT-A
6 2 2 ~ 4 ~ -200...+200°C
0...+850°C
MFD- TP12-PT-B
6 2 ~ ~ 4 ~ -40...+90°C
0...+250°C
MFD- TP12-NI-A
6 2 2 ~ 4 1 -40...90°C
0...+250°C
0...+400°C
MFD- TAP13-PT-A
6 2 2 ~ 4 1 -200..+200°C
0...+850°C
MFD- TAP13-PT-B
6 2 ~ ~ 4 1 -40+90°C
0...+250°C
MFD- TAP13-NI-A

easyControl

Overview

easyControl PLC

High-performance CPU with large programming memory (256kB) and versatile communication functions

  • CANopen / easyNet bus interface for connection to distributed peripherals
  • RS232 / Ethernet programming interface
  • Comfortable programming to IEC1131-3 in Ladder Diagram, Function Block Diagram, Instruction List, Structured Text, Sequential Function Chart, Continuous Flow Chart
  • Powerful libraries for control engineering and communication

Functions

easyControl PLC - Functions

  • Variable I/O configurations with digital and analog inputs, outputs optionally in transistor/relay versions. Optional analog output.
  • Ethernet on board
    easyControl can be comfortably programmed via the integrated Ethernet interface. Communication to other controls (UDP, TCP, Modbus-TCP) as well as to higher-level systems via OPC is possible.
  • 2 serial interfaces
    These are used for programming access, or free interfaces are used for communication with other serial end devices.
  • Plug-in memory slot with standard file system Programs or the operating system can be updated via the plug-in memory module (RS-MMC). Reading/writing of operating data for tracing or archiving is possible. The files can be read on every PC (e.g. EXCEL).

Specifications

easyControl PLC - Specifications

EC4P - CANopen/easyNet interface - Approvals UL/CSA - Shipping classifications DNV, GL, ABS, BV, LR

Inputs Digital Outputs Analog Outputs Ethernet Display & Keypad Part Number
Digital Can be used for analog Relay Transistor
12 4 ~ 8 ~ ~ EC4P- 221-MTXD1
12 4 ~ 8 ~ ~ ~ EC4P- 221-MTXX1
12 4 6 ~ ~ ~ EC4P- 221-MRXD1
12 4 6 ~ ~ ~ ~ EC4P- 221-MRXX1
12 4 ~ 8 1 ~ EC4P- 221-MTAD1
12 4 ~ 8 1 ~ ~ EC4P- 221-MTAX1
12 4 6 ~ 1 ~ EC4P- 221-MRAD1
12 4 6 ~ 1 ~ ~ EC4P- 221-MRAX1
12 4 ~ 8 ~ EC4P- 222-MTXD1
12 4 ~ 8 ~ EC4P- 222-MTXX1
12 4 6 ~ ~ EC4P- 222-MRXD1
12 4 6 ~ ~ EC4P- 222-MRXX1
12 4 ~ 8 1 EC4P- 222-MTAD1
12 4 ~ 8 1 EC4P- 222-MTAX1
12 4 6 ~ 1 EC4P- 222-MRAD1
12 4 6 ~ 1 EC4P- 222-MRAX1

Software & Accessories

easyControl PLC - Software & Accessories
Description Part Number
The programming software easySoft-Basic is used for programming easy500/700. "Drag & Drop" functions enable quick and comfortable entry of the circuit diagram. Programming is implemented in Ladder Diagram. Furthermore, the software offers the opportunity for simulation, on-line communication and documentation. easySoft-Basic
With easySoft-Pro, easy500/700/800, the multi-function display MFD-Titan, as well as easy800 with SmartWire-DT can be programmed. In addition to the functions of the easySoft-Basic, a screen editor for creation of the MFD Titan screens is available with the easySoft-pro. The integration of the SmartWire-DT line into the program occurred with the inclusion of the SmartWire-DT configurator. The easySoft-Pro CD contains a free OPC server, which enables the standardized inclusion of higher-level control systems (OPC clients). Just like easySoft-Basic, easySoft-Pro can be installed in 13 languages. easySoft-Pro
XSoft-CoDeSys-2 is the programming software for easyControl and the HMI-PLC. The software is based on standard CoDeSys from 3S for industrial PLCs in compliance with the international standard IEC 61131-3. The available programming languages are Instruction list (IL), Structured Text (ST), Function Block Diagram (FBD), Freely definable graphical function block chart/Continuous Function Chart (CFC), Ladder Diagram (LD) and Sequential Function Chart (SFC). The integrated online simulation facilitates program text even, when the control is not connected. Xsoft-CoDeSys-2
GALILEO is an easy-to-learn, and nevertheless powerful, visualization software. It is ideally suited for all machine and process-orientated applications in system and machine building. With its non-sector specific concept, GALILEO offers seamless project design for all Eaton Touch Panels. Simple placement of the objects by "Drag & Drop" and a clear menu guidance facilitate fast creation of a comfortable visualization system. This can be simulated directly on the development PC without connection to a HMI or a HMI-PLC. GALILEO

I/O Expansions

easyControl PLC I/O Expansion

can be used via easyLink

Digital Inputs Outputs Supply Voltage Part Number
Relay 10 A (UL) Transistor
12 6 ~ 100 - 240 V AC EASY 618-AC-RE
12 ~ 8 24 V DC EASY 620-DC-TC
12 6 ~ 24 V DC EASY 618-DC-RE
~ 2 ~ 24V DC EASY 202-RE
6 4 ~ 24 V DC EASY 410-DC-RE
6 ~ 4 24 V DC EASY 410-DC-TE
For distributed connection of a digital input/output expansion at up to 30m distance EASY 200-EASY
easyControl PLC I/O Expansion via CANopen



via CANopen can be used for: XC100/200, EC4P, XV

6 4 ~ 24 V DC EC4E- 221-6D4R1
6 ~ 4 24 V DC EC4E- 221-6D4T1
easyControl PLC I/O Expansion via easyLink

can be used via easyLink

Inputs Digital Outputs Analog Outputs Supply Voltage Part Number
Digital/Analog Can be used for Digital Relay 10 A (UL) Transistor
1 / 2 2 ~ 2 1 24 V DC EASY 406-DC-ME
1 / 6 2 ~ 2 2 24 V DC EASY 411-DC-ME

Power Supply

easyControl Power Supply Unit

Power supply units, 1-phase. *Rated input voltage 100 - 240 V AC

Input voltage range Rated output voltage Output voltage setting range Rated output power Rated output current Part Number
85 - 264 V AC 24 V DC / 12 V DC ~ 8 W 0.35 A / 20 mA EASY 200-POW
85 - 264 V AC 24 V DC ~ 30 W 1.25 A EASY 400-POW
85 - 264 V AC 24 V DC ~ 60 W 2.5 A EASY 500-POW
85 - 264 V AC 24 V DC ~ 100 W 4.2 A EASY 600-POW

easySafety

Overview

easySafety PLC
  • Circuits for stopping in an emergency
  • Guard door monitoring with and without interlocking/guard locking
  • Safe operation with two-hand control
  • Electro-sensitive protective equipment (ESPE)
  • Optional with muting function
  • Enabling switch
  • Mode switch
  • Start element
  • Safety-related timing relay
  • Feedback loop monitoring (EDM)

Functions

easySafety - Functions

The Rugged
ES4P-221-DRXX1, ES4P-221-DRXD1

  • 14 safety inputs
  • 4 safety relay outputs
  • 4 test signals
  • 16 operating and message texts
  • easyNet on board
  • easyLink on board
  • Safety and standard circuit diagram
  • With and without display

The versatile
ES4P-221-DMXX1, ES4P-221-DMXD1

  • 14 safety inputs
  • 4 safety transistor outputs + 1 redundant safety relay output
  • 4 test signals
  • 16 operating and message texts
  • easyNet on board
  • easyLink on board
  • Safety and standard circuit diagram
  • With and without display

Specifications

easySafety PLC - Specifications
Inputs / Outputs Display Expansion / Communication Circuit Diagram Part Number
Safety inputs Safety relay outputs safety tran. Outputs Redundant safety relay outputs Test Signals easyNet easyLink Open fieldbuses Safety Standard
14 ~ 4 1 4 ~ up to
8 Net stations
digital I/O Standard expansions Profibus DP CanOpen DeviceNet AS-i Yes Yes ES4P- 221-DMXX1
14 ~ 4 1 4 Yes Yes Yes ES4P- 221-DMXD1
14 4 ~ ~ 4 ~ Yes Yes ES4P- 221-DRXX1
14 4 ~ ~ 4 Yes Yes Yes ES4P- 221-DRXD1

Accessories

easySafety PLC - Accessoeies
Description Part Number
Memory Module ES4A- MEM-CARD1
easySoft-Safety + easySoft Pro ESP-Soft
Standard easy USB programming cable EASY800- USB-CAB
Standard easy serial programming cable EASY800- PC-CAB
I/O-Simulator ES4A- 221-DMX-SIM