SOLID STATE TRIP Type NZM10...(N)(S)/ZM(A)-...-NA molded case circuit breakers are UL listed (UL 489) and CSA certified (22.2 No. 5.1) Inverse time, Solid State Trip Circuit Breakers with a fixed or adjustable long time response and adjustable instantaneous pick-up range.
Type NZM10-...H/ZM(A)-...-NA molded case circuit breakers are UL listed (UL489) and CSA certified (22.2 No. 5.1) Current-limiting Inverse Time, Solid State Trip Cucuit Breakers with a fixed or adjustable long time response and adjustable instaneous pick-up range. |
|||||
CIRCUIT BREAKER | LONG TIME RESPONSE CURRENT SETTING |
SETTING RANGES ADJUSTABLE INSTANTANEOUS PICK-UP SETTING |
NORMAL INTERRUPTING CAPACITY
42 kA at 480 V 50/60 HZ 35 kA at 600 V 50/60 HZ
|
MEDIUM INTERRUPTING CAPACITY 65 kA at 480 V 50/60 HZ 42 kA at 600 V 50/60 HZ
|
HIGH INTERRUPTING CAPACITY 100 kA at 480 V 50/60 HZ 50 kA at 600 V 50/60 HZ Fuseless current limiting |
n Supplied with toggle operator. Refer to --- table for additional handle types. n Supplied with bolt on connection as standard. For line and load field wiring terminals for cable connection refer to --- table for details on available terminals.
|
150 |
300 - 1800 | |||
175 | 350 - 2100 | ||||
200 | 400 - 2400 | ||||
225 | 450 - 2700 | ||||
250 | 500 - 3000 | ||||
300 | 600 - 3600 | ||||
350 | 700 - 4200 | ||||
400 | 800 - 4800 | NZM10-400H/ZMA-400-NA |
|||
500 | 1000 - 6000 | ||||
600 | 1200 - 7200 | ||||
WITH ADJUSTABLE LONG TIME
RESPONSE SETTINGS
n Supplied with toggle operator. Refer to --- table for additional handle types. n Supplied with bolt on connection as standard. For line and load field wiring terminals for cable connection refer to --- table for details on available terminals. |
125 - 250 | 250 - 3000 |
|
|
|
200 - 400 | 400 - 4800 |
|
|
|
|
300 - 600 | 600 - 7200 | NZM10-600N/ZM-650-NA
|
|
|
Return to NZM10 |