Menu

Eaton/Moeller
S701C03N3S
Type S701 Soft Start Controller

S701C03N3S Solid State Soft Start Controller
Product Description

The S701 device is a reduced voltage soft start controller designed to control acceleration and deceleration of three-phase motors. The S701 provides the user with the ability to adjust initial torque, ramp up and down time, and also select kick start for high inertial loads.

S701C03N3S Specifications - Three-Phase Motor

Rated
Current
Line
Voltage
Control
Voltage
(Vac/Vdc)
kW Rating (50 Hz) hp Rating (60 Hz)
200 V 230 V 460 V 575 V
230 V 380-400 V 440 V 1.0 SF 1.15 SF 1.0 SF 1.15 SF 1.0 SF 1.15 SF 1.0 SF 1.15 SF
3.5 208–240 24–230 7.5 N/A N/A 1 1 1 1 N/A N/A N/A N/A

S701 Specifications

Description S701C03N3S S701D03N3S S701E03N3S S701G03N3S
Maximum
current capacity
3.5 3.5 3.5 3.5
Trip Class - 10A 3.5 3.5 3.5 3.5
Trip Class - 10 3.5 3.5 3.5 3.5
Trip Class - 20 2.8 2.8 2.8 2.8
Trip Class - 30 2.1 2.1 2.1 2.1
Electrical Characteristics
Line voltage (Vac) 208–240 380–415 440–480 500–600
Operating frequency (Hz) 50/60 50/60 50/60 50/60
Leakage current 5 mA AC max. 5 mA AC max. 5 mA AC max. 5 mA AC max.
Minimum
operational current
50 mA 50 mA 50 mA 50 mA
Control voltage
(Vac/Vdc)
24–230 24–415 24–480 24–480
Pickup voltage max. 20.4 Vac/Vdc 20.4 Vac/Vdc 20.4 Vac/Vdc 20.4 Vac/Vdc
Dropout voltage min. 5 Vac/Vdc 5 Vac/Vdc 5 Vac/Vdc 5 Vac/Vdc
Max. control current
for no operation
1 mA 1 mA 1 mA 1 mA
Response time max. 70 ms 70 ms 70 ms 70 ms
Control Characteristics
Ramp time (secs) 0.5–10 0.5–10 0.5–10 0.5–10
Ramp settings
(% LRT)
85% 85% 85% 85%
Kick start settings
(% LRT)
85% 85% 85% 85%
Soft stop (secs) 0.5–10 0.5–10 0.5–10 0.5–10
Environment Characteristics
Temperature–operating
(no derating)
–30° to 40° C –30° to 40° C –30° to 40° C –30° to 40° C
Current rating 50° C N/A N/A N/A N/A
Limited duty cycle 50° C N/A N/A N/A N/A
Current rating 60° C N/A N/A N/A N/A
Limited duty cycle 60° C N/A N/A N/A N/A
Temperature–storage –30° to 80° C –30° to 80° C –30° to 80° C –30° to 80° C
Altitude (meters)
no derating
2000 2000 2000 2000
Humidity 95%
noncondensing
95%
noncondensing
95%
noncondensing
95%
noncondensing
Operating position
(no derating)
Vertical ±30° Vertical ±30° Vertical ±30° Vertical ±30°
Impulse withstand
voltage IEC 947-4-1
4000 V 4000 V 4000 V 4000 V
Rated insulation
voltage (Ui)
660 V 660 V 660 V 660 V
Installation category III III III III
Vibration IEC 68-2-6 5g
10–150 Hz
IEC 68-2-6 5g
10–150 Hz
IEC 68-2-6 5g
10–150 Hz
IEC 68-2-6 5g
10–150 Hz
Power dissipation
for intermittent operation
4 W/A x duty cycle 4 W/A x duty cycle 4 W/A x duty cycle 4 W/A x duty cycle
Power dissipation
for continuous operation
4 W/A x duty cycle 4 W/A x duty cycle 4 W/A x duty cycle 4 W/A x duty cycle
Cooling method Natural convection Natural convection Natural convection Natural convection
Degree of protection IP20 IP20 IP20 IP20
Pollution degree 3 3 3 3
Agency approvals UL, cUL, CE UL, cUL, CE UL, cUL, CE UL, cUL, CE

S701 Series Part Numbers

Rated
Current
Line
Voltage
Control
Voltage
(Vac/Vdc)
Part
Number
3.5 208–240 24–230 S701C03N3S
3.5 380–415 24–415 S701D03N3S
3.5 440–480 24–480 S701E03N3S
3.5 500–600 24–480 S701G03N3S
15 208–240 24–230 S701C15N3S
15 380–480 24–480 S701E15N3S
15 500–600 24–480 S701G15N3S
25 208–240 24–230 S701C25N3S
25 380–480 24–480 S701E25N3S
25 500–600 24–480 S701G25N3S

S701C03N3S Dimensions

Width Height Depth Weight
in Lbs (kg)
0.89 (22.5) 3.94 (100) 5.01 (127) 0.6 (270)

S701 Part Number Selection Guide

S701 Part Number Selection Guide