Description |
S701C25B3S |
S701E25B3S |
Maximum
current capacity |
10 |
10 |
Trip Class - 10A |
10 |
10 |
Trip Class - 10 |
10 |
10 |
Trip Class - 20 |
8 |
8 |
Trip Class - 30 |
6.5 |
6.5 |
Electrical Characteristics |
Line voltage (Vac) |
208–480 |
208–480 |
Operating frequency (Hz) |
50/60 |
50/60 |
Leakage current |
5 mA AC max. |
5 mA AC max. |
Minimum operational current |
1A |
1A |
Control voltage (Vac/Vdc) |
5–24 Vdc |
24–240 Vac/Vdc |
Pickup voltage max. |
4.25 Vdc |
20.4 Vac/Vdc |
Dropout voltage min. |
1.5 Vdc |
7.2 Vac/Vdc |
Max. control current
for no operation |
26.4 Vdc |
253 Vac/Vdc |
Response time max. |
1/2 cycle |
1 cycle |
Interlock time max. |
80 ms |
150 ms |
Control Characteristics |
Operation current AC-3 |
10 |
10 |
Operation current AC-4 |
8 |
8 |
Duty cycle |
Continuous operation |
Continuous operation |
Leakage current |
1 mA AC max. |
1 mA AC max. |
Minimum operation current |
10 mA AC |
10 mA AC |
Environmental Characteristics |
Temperature—operating |
0° to 60° C |
0° to 60° C |
Temperature—storage |
–30° to 80° C |
–30° to 80° C |
Altitude (meters) |
2000 |
2000 |
Humidity |
95% noncondensing |
95% noncondensing |
Operating position |
Vertical ±30° |
Vertical ±30° |
Impulse withstand
voltage IEC 947-4-1 |
4000 V |
4000 V |
Rated insulation voltage (Ui) |
660 V |
660 V |
Installation category |
III |
III |
Vibration |
IEC 68-2-6 5g 10–150 Hz |
IEC 68-2-6 5g 10–150 Hz |
Power dissipation
for intermittent operation |
2.2 W/A x duty cycle |
2.2 W/A x duty cycle |
Power dissipation
for continuous operation |
2.2 W/A |
2.2 W/A |
Cooling method |
Natural convection |
Natural convection |
Degree of protection |
IP20 |
IP20 |
Pollution degree |
3 |
3 |
Agency approvals |
UL, cUL, CE |
UL, cUL, CE |