S511E10N3D Specifications - Three-Phase Motor

Rated
Current
Line
Voltage
Control
Voltage
(Vac/Vdc)
kW Rating (50 Hz) hp Rating (60 Hz)
200 V 230 V 460 V
230 V 380-400 V 440 V 1.0 SF 1.15 SF 1.0 SF 1.15 SF 1.0 SF 1.15 SF
10 208-480 5-24 Vdc 2.2 4 4 2 2 3 2 5 5

S701 Specifications

Description S701C25B3S S701E25B3S
Maximum
current capacity
10 10
Trip Class - 10A 10 10
Trip Class - 10 10 10
Trip Class - 20 8 8
Trip Class - 30 6.5 6.5
Electrical Characteristics
Line voltage (Vac)  208–480 208–480
Operating frequency (Hz)  50/60 50/60
Leakage current  5 mA AC max. 5 mA AC max.
Minimum operational current 1A 1A
Control voltage (Vac/Vdc) 5–24 Vdc 24–240 Vac/Vdc
Pickup voltage max. 4.25 Vdc 20.4 Vac/Vdc
Dropout voltage min.  1.5 Vdc 7.2 Vac/Vdc
Max. control current
for no operation 
26.4 Vdc 253 Vac/Vdc
Response time max. 1/2 cycle 1 cycle
Interlock time max. 80 ms 150 ms
Control Characteristics
Operation current AC-3 10 10
Operation current AC-4 8 8
Duty cycle Continuous operation Continuous operation
Leakage current 1 mA AC max. 1 mA AC max.
Minimum operation current 10 mA AC 10 mA AC
Environmental Characteristics
Temperature—operating 0° to 60° C 0° to 60° C
Temperature—storage –30° to 80° C –30° to 80° C
Altitude (meters) 2000 2000
Humidity  95% noncondensing 95% noncondensing
Operating position Vertical ±30° Vertical ±30°
Impulse withstand
voltage IEC 947-4-1
4000 V 4000 V
Rated insulation voltage (Ui) 660 V  660 V
Installation category III III
Vibration IEC 68-2-6 5g 10–150 Hz IEC 68-2-6 5g 10–150 Hz
Power dissipation
for intermittent operation
2.2 W/A x duty cycle 2.2 W/A x duty cycle
Power dissipation
for continuous operation 
2.2 W/A 2.2 W/A
Cooling method Natural convection Natural convection
Degree of protection IP20 IP20
Pollution degree 3 3
Agency approvals UL, cUL, CE UL, cUL, CE

S701 Series Part Numbers

Rated
Current
Line
Voltage
Control
Voltage
Part
Number
10 208 - 480 5–24 Vdc S511E10N3D
10 208 - 480 24–240 Vac/Vdc S511E10N3S

S511E10N3D Dimensions

Width Height Depth Weight
in Lbs (kg)
1.77 (45.0) 3.94 (100.1) 5.04 (128.0) 1.52 (690)

S701 Part Number Selection Guide

S701 Part Number Selection Guide

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.