Eaton |
XTPEXTA032D shown |
XTPEXTA032D Trip Block |
|||
Description | Setting Range Overload Release |
Old Moeller Part Number |
New Eaton Part Number |
---|---|---|---|
Motor-protective circuit-breaker PKE, Coordination type "1" and "2" |
3.0...12.0A | PKE-XTUWA-32 | XTPEXTA032D |
XTPEXTA032D Technical Data |
Setting range | |||
---|---|---|---|
Overload releases | |||
Setting range ofoverload releases | Ir | A | 8 - 32 |
Overload release, min. | Ir | A | 8 |
Overload release, max. | Ir | A | 32 |
Function | With overload release | ||
Rated uninterrupted current = rated operational current | Iu = Ie | A | 32 |
Motor rating | |||
AC-3 | |||
220 V 230 V | P | kW | 7.5 |
380 V 400 V | P | kW | 15 |
440 V | P | kW | 15 |
500 V | P | kW | 18.5 |
660 V 690 V | P | kW | 30 |
For use with | PKE32 basic device | ||
Connection to SmartWire-DT | with PKE-SWD-32 or PKE-SWD-SP |
Motor rating | |||||
---|---|---|---|---|---|
Motor rating AC-3 |
Rated motor current |
||||
220 V 230 V 240 V |
380 V 400 V 415 V |
440 V |
500 V |
660 V 690 V |
|
P | I | I | I | I | I |
kW | A | A | A | A | A |
2.2 | 8.7 | - | - | - | - |
3 | 11.5 | - | - | - | - |
4 | 14.8 | 8.5 | - | - | - |
5.5 | 19.6 | 11.3 | 10.2 | 9 | - |
7.5 | 26.4 | 15.2 | 13.8 | 12.1 | 8.8 |
11 | - | 21.7 | 19.8 | 17.4 | 12.6 |
15 | - | 29.3 | 26.6 | 23.4 | 17 |
18.5 | - | - | - | 28.9 | 20.9 |
22 | - | 23.8 | |||
30 | - | 32 |
Technical data | |||
---|---|---|---|
General | |||
Standards | IEC/EN 60947, VDE 0660, UL 508, CSA C 22.2 No. 14 |
||
Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
||
Ambient temperature °C | |||
Storage ϑ | °C | -40 - +80 | |
Open | °C | -20 - +55 | |
Enclosed | °C | -20 - +40 | |
Direction of incoming supply | as required | ||
Degree of protection | |||
Device | IP20 | ||
Terminations | IP00 | ||
Busbar tag shroud to EN 50274 | Finger- and back-of-hand proof | ||
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 |
g | 25 | |
Altitude | m | Max. 2000 | |
Main conducting paths | |||
Rated impulse withstand voltage | Uimp | V AC | 6000 |
Overvoltage category/pollution degree | III/3 | ||
Rated operational voltage | Ue | V AC | 690 |
Rated uninterrupted current = rated operational current |
Iu = Ie | A | 32 |
Rated frequency | f | Hz | 40 - 60 |
Maximum operating frequency | Ops./h | ||
Max. operating frequency | Ops/h | 60 | |
Motor switching capacity | kArms | ||
AC-3 (up to 690 V) | A | 32 | |
Trip blocks | |||
Temperature compensation | °C | -5 - +40 (to IEC/EN 60947, VDE 0660) -25 - +55 (operating range) |
|
Temperature compensation residual error for T > 40 °C |
± 55 (Arbeitsbereich) | ||
Setting range of overload releases | 0.25 - 1 x Iu | ||
Fixed short-circuit release | Trip block 15 x Ir delayed approx. 60 ms |
||
Short-circuit release tolerance | ± 20% | ||
Phase-failure sensitivity | yes | ||
Data for design verification according to IEC/EN 61439 | |||
Technical data for design verification | |||
Rated operational current for specified heat dissipation |
In | A | 32 |
Heat dissipation capacity | Pdiss | W | 0 |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements. | ||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. |
||
10.4 Clearances and creepage distances | Meets the product standard's requirements. | ||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
||
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
||
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility. | ||
10.8 Connections for external conductors |
Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. | ||
10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. | ||
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
||
10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
||
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
||
Technical data ETIM 5.0 | |||
Low-voltage industrial components (EG000017) / Tripping bloc for power circuit-breaker (EC000617) |
|||
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Releasing block for circuit breakers (ecl@ss8-27-37-04-10 [AKF008009]) |
|||
Setting range overload protector | A | 8 - 32 | |
Initial value of the undelayed short-circuit release - setting range |
A | 8 | |
End value adjustment range undelayed short-circuit release |
A | 384 | |
Rated permanent current Iu | A | 32 | |
Number of poles | — | 3 | |
Short-circuit release function | — | Delayed |
© 2016 KMParts.com, Inc. All rights reserved.