Eaton |
PKE65/AK/XTUW-32-SP shown |
XTPE065DCSSP Motor Starter |
|||||
Short Circuit Current Rating | Setting
Range Overload Release Ir |
Old Moeller Part Number |
New Eaton Part Number |
||
---|---|---|---|---|---|
240 V kA |
480 Y 277 V kA |
600 Y 347 V kA |
16.0 - 65.0A | PKE65/AK/XTU-65-SP | XTPE065DCSSP |
XTPE065DCSSP Technical Data |
Delivery programme | |
---|---|
Basic function | Type E DOL starters (complete devices) |
Basic device | MSC |
Connection to SmartWire-DT |
No |
Components for | North America |
Maximum Motor Rating | |||
---|---|---|---|
AC HP = PS | |||
200 V 208 V | HP | 15 | |
230 V 240 V | HP | 15 | |
460 V 480 V | HP | 40 | |
Short Circuit Current Rating | |||
240 V | kA | 65 | |
480 Y / 277 V | kA | 65 | |
600 Y / 347 V | kA | 25 | |
Setting range | |||
Setting range of overload releases | Ir | A | 16 - 65 |
Short-circuit releases | |||
Non-delayed | Irm | A | 910 |
Motor-protective circuit-breakers PKE65/AK/XTU-65 |
Extension terminal BK50/3-PKZ4-E |
Notes The type E DOL starter (without protection) consists of a PKE65 motor-protective circuit-breaker with AK-PKZ0 and a BK50/3-PKZ4-E extension terminal. |
Technical data | |||
---|---|---|---|
General | |||
Standards | IEC/EN 60947-4-1, VDE 0660 | ||
Main conducting paths | |||
Rated impulse withstand voltage | Uimp | V AC | 6000 |
Overvoltage category/pollution degree | III/3 | ||
Rated operational voltage | Ue | V | 208 - 480 |
Rated operational current | |||
Open, 3-pole: 50-60 Hz 380 V 400 V |
Ie | A | 65 |
Additional technical data | |||
Motor protective circuit breaker PKZM0, PKE |
PKE motor-protective circuit-breaker, see motor-protective circuit-breaker product group |
||
Data for design verification according to IEC/EN 61439 | |||
Technical data for design verification | |||
Heat dissipation capacity | Pdiss | W | 0 |
IEC/EN 61439 design verification | — | ||
10.2 Strength of materials and parts |
— | ||
10.2.2 Corrosion resistance |
Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements. | ||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
||
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
||
10.4 Clearances and creepage distances |
Meets the product standard's requirements. | ||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
||
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
||
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility. | ||
10.8 Connections for external conductors |
Is the panel builder's responsibility. | ||
10.9 Insulation properties | — | ||
10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. | ||
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility. | ||
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility. | ||
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
||
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
||
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
||
Technical data ETIM 5.0 | |||
Low-voltage industrial components (EG000017) / Motor starter combination (EC001037) | |||
Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Motor starter combination (ecl@ss8-27-37-09-05 [AJZ718009]) |
|||
Setting range overload protector | A | 16 - 65 | |
Adjustment range undelayed short-circuit release | A | 0 - 0 | |
Phase failure sensitive | - | Yes | |
Switch off technique | - | Electronic | |
Rated operating voltage | V | 690 - 690 | |
Rated permanent current Iu | A | 65 | |
Rated operation power at AC-3, 230 V | kW | 18.5 | |
Rated operation power at AC-3, 400 V | kW | 30 | |
Connection type main current circuit | - | Screw connection | |
Device construction | - | Built-in device fixed built-in technique |
|
With integrated auxiliary switch | - | No | |
With integrated under voltage release | - | No | |
Number of poles | - | 3 | |
Rated short-circuit
breaking capacity lcu at 400 V, AC |
kA | 80 | |
Degree of protection (IP) | - | IP20 |
XTPE065DCSSP Dimensions |
||
© 2016 KMParts.com, Inc. All rights reserved.