Eaton |
U-PKZ0 shown |
XTPAXUVR415V50H Undervoltage Release |
|||
Description | Actuating Voltage |
Old Moeller Part Number |
New Eaton Part Number |
---|---|---|---|
Undervoltage Release | 415 V 50 Hz | U-PKZ0(415V50HZ) | XTPAXUVR415V50H |
XTPAXUVR415V50H Technical Data |
|
Design verification as per IEC/EN 61439 | |
---|---|
Technical data for design verification | |
Static heat dissipation, non-current-dependent (Pvs) |
0.5 W |
Heat dissipation capacity (Pdiss) | 0 W |
IEC/EN 61439 design verification | |
10.2 Strength of materials and parts | |
10.2.2 Corrosion resistance | Meets the product standard's requirements. |
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements. |
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements. |
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard's requirements. |
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements. |
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
10.2.7 Inscriptions | Meets the product standard's requirements. |
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances | Meets the product standard's requirements. |
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
10.8 Connections for external conductors | Is the panel builder's responsibility. |
10.9 Insulation properties | |
10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility. |
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Technical data ETIM 5.0 | |
Low-voltage industrial components (EG000017) / Under voltage coil (EC001022) | |
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Undervoltage trip (ecl@ss8-27-37-04-17 [AKF015009]) |
|
Rated control supply voltage Us at AC 50HZ | 415 - 415 V |
Rated control supply voltage Us at AC 60HZ | 0 - 0 V |
Rated control supply voltage Us at DC | 0 - 0 V |
Voltage type for actuating | AC |
Type of electric connection | Screw connection |
Number of contacts as normally open contact | 0 |
Number of contacts as normally closed contact | 0 |
Number of contacts as change-over contact | 0 |
Delayed | No |
Suitable for power circuit breaker | No |
Suitable for switch disconnector | No |
Suitable for motor safety switch | Yes |
Suitable for overload relay | No |
XTPAXUVR415V50H Dimensions |
||
© 2016 KMParts.com, Inc. All rights reserved.