Menu

Eaton
XTFCE004BCCSTD
DOL Motor Starter

XTFCE004BCCSTD Motor Starter

MSC-DE-1.2-M17-SP(220V50HZ,240V60HZ) shown


XTFCE004BCCSTD Motor Starter

Short Circuit Current Rating Setting Range
Overload Release
Ir
Old Moeller
Part Number
New Eaton
Part Number
240 V
kA
480 Y
277 V
kA
600 Y
347 V
kA
1.0 - 4.0A MSC-DE-1,2-M7
(24VDC)
XTFCE004BCCSTD

XTFCE004BCCSTD Technical Data

Delivery programme
Basic function Type E DOL starters (complete devices)
Basic device MSC
Connection to
SmartWire-DT
No
Components for North America
Maximum Motor Rating
AC HP = PS
200 V 208 V HP 0.75
230 V 240 V HP 7.5
460 V 480 V HP 2
Short Circuit Current Rating
240 V kA 18
480 Y / 277 V kA 18
Setting range
Setting range of overload releases    Ir A 1 - 4
Short-circuit releases     
Non-delayed    Irm A 168
Contact sequence
Actuating voltage 24 V DC
Motor-protective circuit-breakers PKE12/XTU-4
Contactor DILM17-10(...)
DOL starter wiring set
Mechanical connection element and electrical electric contact module BK25/3-PKZ0-E

Notes

The DOL starter type E (complete devices) consists of a PKE motor-protective circuit-breaker with AK-PKZ0, a DILM contactor and an extension terminal BK25/3-PKZ0-E.

Motor-protective circuit-breaker and contactor mounted on top hat rail adapter plate.

The connection of the main circuit between PKE and contactor is established with electrical contact modules.


Technical data
General
Standards IEC/EN 60947-4-1, VDE 0660
Main conducting paths
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution degree     III/3
Rated operational voltage Ue V 208 - 600
Rated operational current
Open, 3-pole: 50-60 Hz
380 V 400 V
Ie A 4
Additional technical data
Motor protective
circuit breaker PKZM0, PKE
PKE motor-protective circuit-breaker,
see motor-protective circuit-breaker product group DILM
contactors, see contactors product group
DILM contactors
Power consumption of the coil
in a cold state and 1.0 x Uc
Dual-voltage coil 50 Hz
Sealing W 0.5
Data for design verification according to IEC/EN 61439
Technical data for design verification
Heat dissipation capacity Pdiss W 0
IEC/EN 61439 design verification
10.2 Strength
of materials and parts
10.2.2 Corrosion
resistance
Meets the product standard's requirements.
10.2.3.1 Verification
of thermal
stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification
of resistance
of insulating materials
to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification
of resistance
of insulating materials
to abnormal heat
and fire due to internal
electric effects
Meets the product standard's requirements.
10.2.4 Resistance
to ultra-violet
(UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear
needs to be evaluated.
10.2.6 Mechanical
impact
Does not apply, since the entire switchgear
needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree
of protection
of ASSEMBLIES
Does not apply, since the entire switchgear
needs to be evaluated.
10.4 Clearances
and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear
needs to be evaluated.
10.6 Incorporation
of switching devices
and components
Does not apply, since the entire switchgear
needs to be evaluated.
10.7 Internal electrical
circuits and connections
Is the panel builder's responsibility.
10.8 Connections
for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse
withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing
of enclosures made
of insulating material
Is the panel builder's responsibility.
10.10 Temperature
rise
The panel builder is responsible
for the temperature rise calculation.
 Eaton will provide heat dissipation data
for the devices.
10.11 Short-circuit
rating
Is the panel builder's responsibility.
The specifications for the switchgear
must be observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility.
The specifications for the switchgear
must be observed.
10.13 Mechanical
function
The device meets the requirements,
provided the information in
the instruction leaflet (IL) is observed.
Technical data ETIM 5.0
Low-voltage industrial components (EG000017) / Motor starter combination (EC001037)
Electric engineering, automation, process control engineering / Low-voltage switch technology /
Load breakout, motor breakout / Motor starter combination (ecl@ss8-27-37-09-05 [AJZ718009])
Function Direct starter
Rated control supply
voltage Us at AC 50HZ
V 0 - 0
Rated control supply
voltage Us at AC 60HZ
V 0 - 0
Rated control supply
voltage Us at DC
V 24 - 24
Voltage type for actuating DC
Rated operation power
at AC-3, 400 V
kW 7.5
Rated operation
current Ie
A 16.7
Conditioned rated
short-circuit current Iq
kA 100
Setting range overload protector A 1 - 4
With short-circuit release Yes
Type of coordination 2
Connection type
main current circuit
Screw connection
Degree
of protection (IP)
IP20
Suited for bus
connection
Yes

XTFCE004BCCSTD Dimensions

XTFCE004BCCSTD Dimensions

Inch to MM Conversion

Convert to MM

MM to Inch Conversion

Convert to Inches