Menu

Eaton/Moeller
B3.2/2-PKZ0
3-Phase Commoning Link

B3.2/2-PKZ0 3-Phase Commoning Link

B3.2/2-PKZ0 shown


B3.2/2-PKZ0 3-Phase Commoning Link

For Use With Qty.
MMP
Length
of Link
(mm)
Unit
Width
(mm)
Old Moeller
Part Number
New Eaton
Part Number
Each MMP with an auxiliary contact
and trip-indicating auxiliary contact mounted
on the right or a voltage release
mounted on the left.
2 108 45 + 18 B3.2/2-PKZ0 XTPAXCLKC2


Delivery program
Product range Accessories
Accessories Three-phase commoning link
Protected against accidental contact, short-circuit proof, Ue = 690 V, Iu = 63 A
Can be extended by rotating by installation Attached on the right,
for motor-protective circuit-breakers, with an auxiliary contact or trip-indicating auxiliary contact
For use with Three-phase commoning link PKZ0, PKE
Circuit-breaker 2
Length 108 mm
Unit width 45 + 18 mm
Notes:
For parallel power feed to several motor-protective circuit-breakers on terminals 1, 3, 5
Technical data
Main conducting paths
Rated impulse withstand voltage (Uimp) 6000 V AC
Overvoltage category/pollution degree III/3
Rated operational voltage (Ue) 690 V AC
Rated uninterrupted current (Iu) 63 A
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current
for specified heat dissipation
63
Heat dissipation capacity 0
IEC/EN 61439 design verification
10.2 Strength of materials and parts  
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification
of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification
of resistance of insulating materials
to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification
of resistance of insulating materials
to abnormal heat and fire due
to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance
to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting Does not apply,
since the entire switchgear
needs to be evaluated.
10.2.6 Mechanical impact Does not apply,
since the entire switchgear
needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection
of ASSEMBLIES
Does not apply,
since the entire switchgear
needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's
requirements.
10.5 Protection against electric shock Does not apply,
since the entire switchgear
needs to be evaluated.
10.6 Incorporation
of switching devices and components
Does not apply,
since the entire switchgear
needs to be evaluated.
10.7 Internal electrical
circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties  
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing
of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible
 for the temperature rise calculation.
Eaton will provide heat dissipation
data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility.
The specifications for the switchgear
must be observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility.
The specifications for the switchgear
must be observed.
10.13 Mechanical function The device meets the requirements,
provided the information in the instruction l
eaflet (IL) is observed.
Technical data ETIM 5.0
Low-voltage industrial components (EG000017) / Phase busbar (EC000215)
Electric engineering, automation, process control engineering / Low-voltage switch technology /
Component for low-voltage switching technology / Phase busbar
(ecl@ss8-27-37-13-06 [ACN992007])
Number of phases 3
Suitable for number of devices 2
Pitch dimensions 63 mm
Cross section 0 mm2
Length 108 mm
Rated permanent current Iu 63 A
Type of electric connection Fork
Insulated Yes
Rated surge voltage 6 kV
Conditioned rated short-circuit current Iq 0 kV
Max. rated operation voltage Ue 690 V
Rated short-time withstand current lcw 0 kA
Suitable for devices with N-busbar No
Suitable for devices with auxiliary switch No
Approvals
Product Standards UL 508; CSA-C22.2 No. 14;
IEC60947-4-1; CE marking
UL File No. E36332
UL Category Control No. NLRV
CSA File No. 98494
CSA Class No. 3211-06
North America Certification UL listed, CSA certified
Specially designed for North America No

B3.2/2-PKZ0 Dimensions

B3.2/2-PKZ0 Dimensions

Inch to MM Conversion

Convert to MM

MM to Inch Conversion

Convert to Inches

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.