Eaton/Moeller |
B3.1/5-PKZ0 shown |
B3.1/5-PKZ0 3-Phase Commoning Link |
|||||
For Use With | Qty. MMP |
Length of Link (mm) |
Unit Width (mm) |
Old Moeller Part Number |
New Eaton Part Number |
---|---|---|---|---|---|
Each MMP with one auxiliary contact or trip-indicating auxiliary contact fitted on the right |
5 | 261 | 45 + 9 | B3.1/5-PKZ0 | XTPAXCLKB5 |
Delivery program | |
---|---|
Product range | Accessories |
Accessories | Three-phase commoning link |
Protected against accidental contact, short-circuit proof, Ue = 690 V, Iu = 63 A Can be extended by rotating by installation Attached on the right, for motor-protective circuit-breakers, with an auxiliary contact or trip-indicating auxiliary contact |
|
For use with | Three-phase commoning link PKZ0, PKE |
Circuit-breaker | 5 |
Length | 261 mm |
Unit width | 45 + 9 mm |
Notes: For parallel power feed to several motor-protective circuit-breakers on terminals 1, 3, 5 |
|
Technical data | |
Main conducting paths | |
Rated impulse withstand voltage (Uimp) | 6000 V AC |
Overvoltage category/pollution degree | III/3 |
Rated operational voltage (Ue) | 690 V AC |
Rated uninterrupted current (Iu) | 63 A |
Design verification as per IEC/EN 61439 | |
Technical data for design verification | |
Rated operational current for specified heat dissipation |
63 |
Heat dissipation capacity | 0 |
IEC/EN 61439 design verification | |
10.2 Strength of materials and parts | |
10.2.2 Corrosion resistance | Meets the product standard's requirements. |
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements. |
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements. |
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard's requirements. |
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements. |
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
10.2.7 Inscriptions | Meets the product standard's requirements. |
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances | Meets the product standard's requirements. |
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility. |
10.8 Connections for external conductors | Is the panel builder's responsibility. |
10.9 Insulation properties | |
10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility. |
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction l eaflet (IL) is observed. |
Technical data ETIM 5.0 | |
Low-voltage industrial components (EG000017) / Phase busbar (EC000215) | |
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Phase busbar (ecl@ss8-27-37-13-06 [ACN992007]) |
|
Number of phases | 3 |
Suitable for number of devices | 2 |
Pitch dimensions | 54 mm |
Cross section | 0 mm2 |
Length | 261 mm |
Rated permanent current Iu | 63 A |
Type of electric connection | Fork |
Insulated | Yes |
Rated surge voltage | 6 kV |
Conditioned rated short-circuit current Iq | 0 kV |
Max. rated operation voltage Ue | 690 V |
Rated short-time withstand current lcw | 0 kA |
Suitable for devices with N-busbar | No |
Suitable for devices with auxiliary switch | No |
Approvals | |
Product Standards | UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking |
UL File No. | E36332 |
UL Category Control No. | NLRV |
CSA File No. | 98494 |
CSA Class No. | 3211-06 |
North America Certification | UL listed, CSA certified |
Specially designed for North America | No |
B3.1/5-PKZ0 Dimensions |
||
© 2016 KMParts.com, Inc. All rights reserved.