Moeller NZM1
|
15 - 125 Amps
|
Size 1 (B) Basic Switching
Capacity
NZMB1 |
|
| 240VAC 60Hz | 480VAC 60Hz | |
| 35kA | *25kA | |
|
*CAUTION
: 60 Amp and over @
480 Volt Useable only on
"480/277 Y "(WYE)" Systems "NOT 480 D (Delta)" Else use NZM2 |
||
15 - 125 Amps
|
Size 1 (N)
NORMAL
Switching
Capacity
|
|
| 240VAC 60Hz | 480VAC 60Hz | |
| 8 5kA | 35kA | |
|
*CAUTION
: 60 Amp and over @
480 Volt Useable only on
"480/277 Y "(WYE)" Systems "NOT 480 D (Delta)" Else use NZM2 |
||
15 - 125 Amps
|
Size 1 (H) HIGH
Switching Capacity
NZMH1 |
|
| 240 VAC 60Hz | 480VAC 60Hz | |
|
||
(Example Part Number) >> NZM-1-N-VE- (xxx-NA) xxx=Rated Amps -=North A NAmerica NZM (1)(2)(3)(4) - (B)(N)(H)(L) - (A)(AE)(AF)(AEF)(VE)(VEF)(S)(SE) - AMPS -NA |
|
NZM
1
15-125 AMP |
-B
(Basic) |
-A | ( Thermal Magnetic, Adjustable ) | |||
| -AE | ( Solid State, Adjustable ) | |||||
|
NZM
2
15-250 AMP |
-N
(Normal) |
-AF | ( Thermal Magnetic, Fixed ) | |||
| -AEF | ( Solid State, Fixed ) | |||||
|
NZM
3
125-600 AMP |
-H
(High) |
-M | ( Thermomagnetic release ) | |||
| -ME | (Electronic Release ) | |||||
| -VE | ( Time Delay, Solid State, Adjustable) | |||||
| -VEF | ( Time Delay, Solid State, Fixed ) | |||||
|
NZM
4
300-1200 AMP |
-L
(Limiter) |
-S | ( Instantaneous Only ) | |||
| -SE | ( Instantaneous, Solid State ) |
|
At the PDF download page you
can choose from a wide selection of instruction and
dimension sheets for NZM1, NZM1 handles, covers, shunt
releases, under voltage releases and more.
|
|
Click here to view the NZM1 Detailed Overview |
Dimensions |
|||
| WIDTH | HEIGHT | DEPTH | |
| NZM1 | 90mm | 145mm | 68mm ( 84.5mm ) |
| 3.5" | 5.75" | 2.75" ( 3.33") |
| NZM 2 | 105mm | 206mm | 103mm ( 149mm ) |
| 4.13" | 8.11" | 4.00" ( 5.87" ) |
| NZM3 | 140mm | 300mm | 121mm ( 166mm ) |
| 5.50" | 11.81" | 4.76" ( 6.54") |
| NZM 4 | 204 | 401 | 138mm ( 207mm ) |
| 8.03" | 15.80" | 5.43" ( 8.15" ) |