Menu

Eaton
XTTR6A100H70B
Electronic Timing Relay

Multi-Function Electronic Timing Relay
With two changeover contacts and connection for remote potentiometer. Can be configured for two timed contacts or for one instantaneous contact and timed contact.
Contact Rating EC Rated
operational
current l at
AC-15
220V, 230V, 240V
Actuating
Voltage
UL/CSA Pilot
Duty Rating
Time Range

Eaton/Moeller XTTR6A100H70B Electronic Timing Relay
XTTR6A100H70B

3 24-240V DC
24-240, 50/60 Hz
B 300 0.05 - 100 h

 Selectable Range switch on timer sets the maximum time that the potentiometer shown on the right utilizes.

XTTR6A100H70B Timing Relay Range Setting

Combined with the maximum range selector switch the below Potentiometer on the timer adjusts to your exact requirement
XTTR6A100H70B Timing Relay Timing Setting

Clock Graphic

Full Scale Range Select
100 h 100 h on the Range Selector Knob =

(0.5-10=0.5 to
100 Hours)
on the time adjust
30 h 30 h on the Range Selector Knob =

(1.5-30=1.5 to
30 Hours)
on the time adjust
300 s 300 s on the Range Selector Knob =

(1.5-30=15 to
300 Seconds)
on the time adjust
80 s 100 s on the Range Selector Knob =

(0.5-10=0.5 to
100 Seconds)
on the time adjust
1.8 s 3 s on the Range Selector Knob =

(1.5-30=.15 to
3 Seconds)
on the time adjust
0.2 s 1 s on the Range Selector Knob =

(0.5-10=0.5 to
100 Seconds)
on the time adjust

Clock Graphic

Time within range
100h
0.5-10 =
0.5 to 100 Hours
on the time adjust
 


3 h


nnbsp;
1.5 - 30 = 1.5 to
30 Hours
on the time adjust


120 s


1.5 - 30 = 15 to
300 Seconds
on the time adjust


80 s


0.5 - 10 = 0.5 to
100 Seconds
on the time adjust
 
1.8 s


1.5-30=.15 to
3 Seconds
on the time adjust

0.2 s
0.5 - 10= 0.5 to
100 Seconds
on the time adjust

 

M22-R10K
Remote mounted Potentiometer for applications that need operator access)

Remote Mounted Potentiometer

Degree of protection IP66
3 individual screw terminals, Pmax = 0.5 W

Wiring Diagram

XTTR6A100H70B Potentiometer Dimensions

Mounts in standard 22mm or 7/8" pushbutton hole.

Other resistances available in the M22 potentiometer line but only use the M22-R10K with the timers.

Potentiometer Chart

 Download button graphic

Multi-function relay
ETR4
01/08 AWA2527-1485
[307 KB] [07.03.2002]PDF Icon


Accuracy of resistance value: g 10% (linear)

XTTR6A100H70B Dimensions

Eaton/Moeller XTTR6A100H70B Dimensions

Inch to MM Conversion

Convert to MM

MM to Inch Conversion

Convert to Inches

Function Switch Diagram

1 Instantaneous Contact, 1 Timed Contact A2/X1 not jumped together

Wiring Diagram

Wiring Diagram

With A1 and B1 either connected together or at the same potential through an external contact.

11 On-Delayed
21 With Fleeting Make Contact
42 Flashing
81 Pulse Generating
12 Off Delayed
16 On and Off Delayed
22 With Fleeting Break Contact
82 Pulse Shaping

2 Timed Contacts, A2/X1 open not jumped

Wiring Diagram

Wiring Diagram
With A1 and B1 either connected together or at the same potential through an external contact.

11 On-Delayed
21 With Fleeting Make Contact
42 Flashing
81 Pulse Generating
12 Off Delayed
16 On and Off Delayed
22 With Fleeting Break Contact
82 Pulse Shaping


 XTTR6A100HS11B  XTTR6A60S51B XTTR6A100H69B XTTR6A100H70B XTTR6A Index
 XTTR6A100HS11N  XTTR6A60S51N XTTR6A100H69N XTTR6A100H70N