BUY HERE
CALL NOW
IN STOCK
866.595.9616

Eaton/Moeller
A-PKZ0(24VDC)
Shunt Release



A-PKZ0(24VDC) Shunt Release

A-PKZ0 shown


A-PKZ0(24VDC) Shunt Release

Description Actuating
Voltage
For Use With Old Moeller
Part Number
New Eaton
Part Number
Shunt Release 24 VDC PKZM0
PKZM4
PKZM0-T
PKM0
PKZM01
PKE
A-PKZ0(24VDC) XTPAXSR24VDC


A-PKZ0(24VDC) Technical Data

General
Moeller Part No. A-PKZ0(24VDC)
Eaton Part No. XTPAXSR24VDC
Delivery program
Product range Accessories
Accessories Shunt release
Actuating voltage 24 VDC
For use with Shunt release PKZ0(4), PKE
Voltage type Standard voltage
Current actuation DC
Connection technique Screw terminals
For use with PKZM0
PKZM4
PKZM0-T
PKM0
PKZM01
PKE
For PKE, only A-PKZ0 or U-PKZ0...
with a serial number of 02
or higher can be retrofitted.
Notes:
Can be fitted to the left of: Motor-protective circuit-breakers
Cannot be combined with: U-PKZ0 undervoltage release
DC: Intermittent operation 5 s
Technical data
General
Terminal capacities  
Solid or flexible conductor,
with ferrule (mm2)
1 x (0,75 - 2,5)
2 x (0,75 - 2,5)
Solid or stranded (AWG) 1 x (18 - 14)
2 x (18 - 14)
Actuating voltage 24 VDC
Operating range
Alternating voltage 0.7- 1.1 (x US)
DC Voltage (x US) 0.7- 1.1 (x US)
Power consumption
Pull-in power (Pick-up) 5 VAC
Sealing power (Sealing) 3 VAC
Design verification as per IEC/EN 61439
Technical data for design verification
Static heat dissipation, non-current-dependent (Pvs) 0.5 W
Heat dissipation capacity (Pdiss) 0 W
IEC/EN 61439 design verification  
10.2 Strength of materials and parts  
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification
of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification
of resistance of insulating materials
to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification
of resistance of insulating materials
to abnormal heat and fire due
to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply,
since the entire switchgear
needs to be evaluated.
10.2.6 Mechanical impact Does not apply,
since the entire switchgear
needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply,
since the entire switchgear
needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's
requirements.
10.5 Protection against electric shock Does not apply,
since the entire switchgear
needs to be evaluated.
10.6 Incorporation
of switching devices and components
Does not apply,
since the entire switchgear
needs to be evaluated.
10.7 Internal electrical circuits
and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties  
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made
of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible
 for the temperature rise calculation.
Eaton will provide heat dissipation
data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility.
The specifications for the switchgear
must be observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility.
The specifications for the switchgear
must be observed.
10.13 Mechanical function The device meets the requirements,
provided the information in
the instruction leaflet (IL) is observed.
Technical data ETIM 5.0
Low-voltage industrial components
(EG000017) / Shunt release
(for power circuit breaker) (EC001023)
Electric engineering, automation, process control engineering / Low-voltage
switch technology / Circuit breaker (LV < 1 kV) / Full load current trip
(ecl@ss8-27-37-04-18 [AKF016009])
Rated control supply voltage Us at AC 50HZ 0 - 0 V
Rated control supply voltage Us at AC 60HZ 0 - 0 V
Rated control supply voltage Us at DC 24 - 24 V
Voltage type for actuating AC
Initial value of the undelayed
short-circuit release - setting range
0 V
End value adjustment range undelayed
short-circuit release
0 V
Type of electric connection Screw connection
Number of contacts as normally open contact 0
Number of contacts as normally closed contact 0
Number of contacts as change-over contact 0
Suitable for power circuit breaker No
Suitable for switch disconnector No
Suitable for motor safety switch Yes
Suitable for overload relay No
Approvals
Product Standards UL 508; CSA-C22.2 No. 14;
IEC60947-4-1; CE marking
UL File No. E36332
UL Category Control No. NLRV
CSA File No. 165628
CSA Class No. 3211-05
North America Certification UL listed, CSA certified
Specially designed for North America No


A-PKZ0(24VDC) Dimensions

A-PKZ0(24VDC) Dimensions

Inch to MM Conversion

Convert to MM

MM to Inch Conversion

Convert to Inches

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.