Description |
S701C25B3S |
S701E25B3S |
Maximum
current capacity |
25 |
25 |
Trip Class - 10A |
25 |
25 |
Trip Class - 10 |
25 |
25 |
Trip Class - 20 |
20 |
20 |
Trip Class - 30 |
15 |
15 |
Electrical Characteristics |
Line voltage (Vac) |
208–240 |
380–480 |
Operating frequency (Hz) |
50/60 |
50/60 |
Leakage current |
5 mA AC max. |
5 mA AC max. |
Minimum operational current |
1A |
1A |
Control voltage (Vac/Vdc) |
24–230 |
24–480 |
Pickup voltage max. |
20.4 Vac/Vdc |
20.4 Vac/Vdc |
Dropout voltage min. |
5 Vac/Vdc |
5 Vac/Vdc |
Max. control current
for no operation |
1 mA |
1 mA |
Response time max. |
100 ms |
100 ms |
Control Characteristics |
Ramp time (secs) |
0.5–10 |
0.5–10 |
Ramp settings (% LRT) |
85% |
85% |
Kick start settings (% LRT) |
85% |
85% |
Soft stop (secs) |
0.5–10 |
0.5–10 |
Brake current |
0–50 Vdc |
0–50 Vdc |
Environmental Characteristics |
Temperature—operating |
–30° to 40° C |
–30° to 40° C |
Current rating 50° C |
20A |
20A |
Limited duty cycle 50° C |
25A on-time max.
15 min. duty cycle max. 0.8 |
25A on-time max.
15 min. duty cycle max. 0.8 |
Current rating 60° C |
17A |
17A |
Limited duty cycle 60° C |
25A on-time max.
15 min. duty cycle max. 0.65 |
25A on-time max.
15 min. duty cycle max. 0.65 |
Temperature—storage |
–30° to 80° C |
–30° to 80° C |
Altitude (meters)—no derating |
2000 |
2000 |
Humidity |
95% noncondensing |
95% noncondensing |
Operating position |
Vertical ±0° |
Vertical ±0° |
Impulse withstand
voltage IEC 947-4-1 |
4000 V |
4000 V |
Rated insulation voltage (Ui) |
660 V |
660 V |
Installation category |
III |
III |
Vibration |
IEC 68-2-6 5g 10–150 Hz |
IEC 68-2-6 5g 10–150 Hz |
Power dissipation
for intermittent operation |
2 W/A x duty cycle |
2 W/A x duty cycle |
Power dissipation
for continuous operation |
2 W/A |
2 W/A |
Cooling method |
Natural convection |
Natural convection |
Degree of protection |
IP20 |
IP20 |
Pollution degree |
3 |
3 |
Agency approvals |
UL, cUL, CE |
UL, cUL, CE |