Menu

Eaton/Moeller
S701C25N3BP
Type S701 Soft Start Controller
with Auxiliary Contact

S701C25N3BP Solid State Soft Start Controller
Product Description

The S701 device is a reduced voltage soft start controller designed to control acceleration and deceleration of three-phase motors. With the auxiliary contact, it is possible to control an external bypass to reduce heating and increase acceleration and deceleration times.

 

The unit provides the user with the ability to adjust initial torque, ramp up and down time and also select kick start for high inertia loads.

S701C25N3BP Specifications - Three-Phase Motor

Rated
Current
Line
Voltage
Control
Voltage
(Vac/Vdc)
kW Rating (50 Hz) hp Rating (60 Hz)
200 V 230 V 460 V 575 V
230 V 380-400 V 440 V 1.0 SF 1.15 SF 1.0 SF 1.15 SF 1.0 SF 1.15 SF 1.0 SF 1.15 SF
Ratings without Bypass
25 208–240 24–230 5.5 N/A N/A 5 5 7.5 5 N/A N/A N/A N/A
Ratings with Bypass
30 208–240 24–230 7.5 N/A N/A 7.5 7.5 10 7.5 N/A N/A N/A N/A

S701 Specifications

Description S701C25N3BP S701E25N3BP S701G25N3BP
Maximum current
capacity with
bypass
(without bypass)
30 (25) 30 (25) 30 (25)
Trip Class - 10A 30 (25) 30 (25) 30 (25)
Trip Class - 10 30 (25) 30 (25) 30 (25)
Trip Class - 20 24 (20) 24 (20) 24 (20)
Trip Class - 30 19.5 (15) 19.5 (15) 19.5 (15)
Electrical Characteristics
Line voltage (Vac) 208–240 380–480 500–600
Operating
frequency (Hz)
50/60 50/60 50/60
Leakage current 5 mA AC max. 5 mA AC max. 5 mA AC max.
Minimum
operational current
50 mA 50 mA 50 mA
Control voltage
(Vac/Vdc)
24–230 24–480 24–480
Pickup voltage max. 20.4 Vac/Vdc 20.4 Vac/Vdc 20.4 Vac/Vdc
Dropout voltage min. 5 Vac/Vdc 5 Vac/Vdc 5 Vac/Vdc
Max. control current
for no operation
1 mA 1 mA 1 mA
Response time max. 70 ms 70 ms 70 ms
Control Characteristics
Ramp time (secs) 0.5–20 0.5–20 0.5–20
Ramp settings
(% LRT)
85% 85% 85%
Kick start settings
(% LRT)
85% 85% 85%
Soft stop (secs) 0.5–20 0.5–20 0.5–20
Environmental Characteristics
Temperature
operating (no derating)
–30° to 40° C –30° to 40° C –30° to 40° C
Current rating 50° C 20A 20A 20A
Limited
duty cycle 50° C
25A on-time max.
15 min. duty cycle
max. 0.8
25A on-time max.
15 min. duty cycle
max. 0.8
25A on-time max.
15 min. duty cycle
max. 0.8
Current
rating 60° C
17A 17A 17A
Limited
duty cycle 60° C
25A on-time max.
15 min. duty cycle
max. 0.65
25A on-time max.
15 min. duty cycle
max. 0.65
25A on-time max.
15 min. duty cycle
max. 0.65
Temperature
storage
–30° to 80° C –30° to 80° C –30° to 80° C
Altitude (meters)
no derating
2000 2000 2000
Humidity 95%
noncondensing
95%
noncondensing
95%
noncondensing
Operating position
(no derating)
Vertical ±30° Vertical ±30° Vertical ±30°
Impulse withstand
voltage IEC 947-4-1
4000 V 4000 V 4000 V
Rated insulation
voltage (Ui)
660 V 660 V 660 V
Installation category III III III
Vibration IEC 68-2-6 5g
10–150 Hz
IEC 68-2-6 5g
10–150 Hz
IEC 68-2-6 5g
10–150 Hz
Power dissipation
for continuous operation
2 W/A without bypass 2 W/A without bypass 2 W/A without bypass
Power dissipation
with semiconductor
bypassed
5 W/A max. with bypass 5 W/A max. with bypass 5 W/A max. with bypass
Cooling method Natural convection Natural convection Natural convection
Degree of protection IP20 IP20 IP20
Pollution degree 3 3 3
Agency approvals UL, cUL, CE UL, cUL, CE UL, cUL, CE

S701 Series Part Numbers

Rated
Current
Line
Voltage
Control
Voltage
(Vac/Vdc)
Part
Number
Ratings without Bypass
25 208–240 24–230 S701C25N3BP
25 380–480 24–480 S701E25N3BP
25 500–600 24–480 S701G25N3BP
Ratings with Bypass
30 208–240 24–230 S701C25N3BP
30 380–480 24–480 S701E25N3BP
30 500–600 24–480 S701G25N3BP

S701C25N3BP Dimensions

Width Height Depth Weight
in Lbs (kg)
3.54 (89.9) 3.94 (100.1) 5.04 (128.0) 2.53 (1150)

S701 Part Number Selection Guide

S701 Part Number Selection Guide

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.