Menu

Eaton
HFDE308036
Thermal-Magnetic Circuit Breakers
with Non-Interchangeable Trip Units



Series-C
Frame Size - F
Part Index
CLICK HERE

Type FDE (3-Pole) Shown

HFDE308036 Electronic Circuit Breakers with Non-Interchangeable Trip Units

Number
of Poles
Amperes IC Rating Type
of Trip(1)
3 80 65 kAIC at 480 Vac Electronic LSIG

TRIP KEY:
L = Adjustable Long Delay Pickup
S = Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)
I = Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous
G = Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)

Quick Reference Guide

UL 489 Interrupting Capacity Ratings
Circuit
Breaker
Type
Number
of Poles
Interrupting Capacity (kA Symmetrical Amperes)
Volts AC (50/60 Hz) Volts DC(1)
240 277 480 600 125 250(2)(3)
EDB 2, 3 22 10
EDS 2, 3 42 10
ED 2, 3 65 10
EDH 2, 3 100 10
EDC 2, 3 200 10
EHD 1 4 10
2, 3 18 14 10
FDB 2, 3, 4 18 14 14 10
FD 1 35 10
2, 3, 4 65 35 18 10
FDE(4) 2, 3, 4 65 35 18
HFD 1 65 10
2, 3, 4 100 65 25 22
HFDE(4) 2, 3, 4 100 65 25
FDC(5) 2, 3, 4 200 100 35 22
FDCE(4)(5)(6) 3 200 100 25
IEC 157-1 (P1) Interrupting Capacity Ratings (P1)
Circuit
Breaker
Type
Number
of Poles
Interrupting Capacity (kA Symmetrical Amperes)
Volts AC (50/60 Hz) Volts DC(1)
220, 240 380, 415 440 500 125 250(2)(3)
EDB 2, 3 22 10
EDS 2, 3 42 10
ED 2, 3 65 10
EDH 2, 3 100 10
EDC 2, 3 200 10
EHD 1 14 10
2, 3 18 14 10
FDB 2, 3, 4 18 14 14 14 10
FD 1 35 10
2, 3, 4 65 35 35 18 10
HFD 1 65 10
2, 3, 4 100 65 65 25 22
FDC 2, 3, 4 200 100 100 35 22

Digitrip Electronic Trip Units

Circuit Breaker
Type
Frame Ratings
FDE, HFDE, FDCE 225 100, 110, 125, 150, 160, 175, 200, 225
FDE, HFDE, FDCE 160 60, 70, 80, 90, 100, 125, 150, 160
FDE, HFDE, FDCE  80 15, 20, 30, 40, 50, 60, 70, 80

NOTES:
(1) DC ratings apply to substantially non-inductive circuits.
(2) Two-pole circuit breaker, or two poles of three-pole circuit breaker.
(3) Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
(4) Electronics available on three-pole only, no DC rating for FDE, HFDE, FDCE.
(5) Current limiting.
(6) Check with Eaton for availability.

HFDE308036 Dimensions

Number of Poles Width Height Depth
1 1.38 (35.1) 6.00 (152.4) 3.38 (86.0)
2 2.75 (70.0) 6.00 (152.4) 3.38 (86.0)
3 4.13 (105.0) 6.00 (152.4) 3.38 (86.0)
4 5.50 (139.7) 6.00 (152.4) 3.38 (86.0)



Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.