Power demand continues to grow in new and existing facilities. To meet increased demand, larger utility supplies, spot networks and large facility transformers are installed. The increased capacity of the electrical source results in increased fault currents in excess of 100 kA short-circuit protection. Eaton manufactures non-fused current limiting modules with interrupting capacities up to 200 kA at 600 Vac or 70 kA at 690 Vac. Unlike fused current limiters with a one-time use, a current limiter module provides an automatic reset of the module after a shortcircuit event. Resetting the molded-case circuit breaker is the only action required to restore critical power to the system; there is no time wasted with sourcing the correct replacement fuses or module to bring system back online.
The current limiting breaker modules use a unique contact design to enhance the system protection similar to that of the circuit breaker. When high short-circuit current is flowing through the contacts of these modules, the design results in very high interrupting capacities and improved current limiting characteristics.
High-performance breakers are most commonly applied when very high fault levels are available and with applications where the current limiting capability is used upstream of the final load to limit current. Typical loads include lighting, power distribution, and motor control applications.
Superior system protection:
NOTES:
(1) 600Y/347V.
(2) Two interphase barriers included on line end mounted limiter; (2) line end of limiter. Four interphase barriers included on load end mounted limiter; (2) line end of breaker (2) load end of limiter
|
Ampere
Rating |
Magnetic
Range |
UL Listed, IEC Rated
Breaker With Line Side Mounted Current Limiter (1) |
UL Listed, IEC Rated
Breaker With Load Side Mounted Current Limiter (2) |
IEC Rated Breaker
With Line Side Mounted Current Limiter (1) |
IEC Rated Breaker
With Load Side Mounted Current Limiter (2) |
| Fixed Thermal, Adjustable Magnetic | Adjustable Thermal, Adjustable Magnetic | ||||
| 70 | 350—700 | JGH3070FAGQ01 | JGH3070FAGQ02 | — | — |
| 90 | 450—900 | JGH3090FAGQ01 | JGH3090FAGQ02 | — | — |
| 100 | 500—1000 | JGH3100FAGQ01 | JGH3100FAGQ02 | JGH3100AAGQ01 | JGH3100AAGQ02 |
| 125 | 625—1250 | JGH3125FAGQ01 | JGH3125FAGQ02 | JGH3125AAGQ01 | JGH3125AAGQ02 |
| 150 | 750—1550 | JGH3150FAGQ01 | JGH3150FAGQ02 | — | — |
| 160 | 800—1600 | — | — | JGH3160AAGQ01 | JGH3160AAGQ02 |
| 175 | 875—1750 | JGH3175FAGQ01 | JGH3175FAGQ02 | — | — |
| 200 | 1000—2000 | JGH3200FAGQ01 | JGH3200FAGQ02 | JGH3200AAGQ01 | JGH3200AAGQ02 |
| 225 | 1125—2250 | JGH3225FAGQ01 | JGH3225FAGQ02 | ||
| Electronic Trip LS | |||||
| 250 | — | JGH325033GQ01 | JGH325033GQ02 | — | — |
| Electronic Trip LSI | |||||
| 250 | — | JGH325032GQ01 | JGH325032GQ02 | — | — |
| Electronic Trip LSG | |||||
| 250 | — | JGH325035GQ01 | JGH325035GQ02 | — | — |
| Electronic Trip LSIG | |||||
| 250 | — | JGH325036GQ01 | JGH325036GQ02 | — | — |
|
Ampere
Rating |
Motor Circuit Protector with
Line Side Mounted Current Limiter |
Breaker with Load Side
Mounted Current Limiter |
| 250 | HMCPJ250D5LQ01 | HMCPJ250D5LQ02 |
| 250 | HMCPJ250F5LQ01 | HMCPJ250F5LQ02 |
| 250 | HMCPJ250G5LQ01 | HMCPJ250G5LQ02 |
| 250 | HMCPJ250J5LQ01 | HMCPJ250J5LQ02 |
| 250 | HMCPJ250K5LQ01 | HMCPJ250K5LQ02 |
| 250 | HMCPJ250L5LQ01 | HMCPJ250L5LQ02 |
|
Maximum
Breaker Amperes |
Terminal
Body Material |
Wire Type |
Metric Wire
Range mm 2 |
AWG Wire
Range/ Number of Conductors |
Part
Number |
| Standard Pressure Type Terminals | |||||
| 250 | Aluminum | Cu/Al | 10–185 | #8–350 (1) | TA250FJ (3) |
NOTES:
(1) Two interphase barriers provided, mounted on line end of limiter, catalog number FJIPBK.
(2) Four interphase barriers provided, (2) line end of breaker, (2) load end of limiter.
(3) Line and load terminals included with products listed above.