EATON Current Limiting Circuit Breaker Modules

Current Limiting Circuit Breaker Module

Product Overview

Power demand continues to grow in new and existing facilities. To meet increased demand, larger utility supplies, spot networks and large facility transformers are installed. The increased capacity of the electrical source results in increased fault currents in excess of 100 kA short-circuit protection. Eaton manufactures non-fused current limiting modules with interrupting capacities up to 200 kA at 600 Vac or 70 kA at 690 Vac. Unlike fused current limiters with a one-time use, a current limiter module provides an automatic reset of the module after a shortcircuit event. Resetting the molded-case circuit breaker is the only action required to restore critical power to the system; there is no time wasted with sourcing the correct replacement fuses or module to bring system back online.

Product Description

The current limiting breaker modules use a unique contact design to enhance the system protection similar to that of the circuit breaker. When high short-circuit current is flowing through the contacts of these modules, the design results in very high interrupting capacities and improved current limiting characteristics.

Application Description

High-performance breakers are most commonly applied when very high fault levels are available and with applications where the current limiting capability is used upstream of the final load to limit current. Typical loads include lighting, power distribution, and motor control applications.

Features and Benefits

Superior system protection:

  • Auto reset improves system uptime and eliminates the need for finding replacement parts
  • No fuses to replace, reducing the overall cost of ownership and the waste created by fuses
  • Overloads, by using inverse time current tripping characteristics of the molded-case circuit breaker
  • Low-level short circuits, by using instantaneous and/or short-time delay tripping characteristics of the molded-case circuit breaker
  • High-level short circuits, by using ultra-high-speed, blow-apart contacts of the current limiting module in series with the circuit breaker contacts
  • Let-through currents, by improved opening speed of the contacts, the resultant rapid rise of arc voltage introduces impedance into the system

Standards and Certifications

  • IEC 60947-2
  • UL 489
  • CSA C22.2

EG IC Rating—150 kAIC at 415 and 480 Vac

NOTES:
(1) 600Y/347V.
(2) Two interphase barriers included on line end mounted limiter; (2) line end of limiter. Four interphase barriers included on load end mounted limiter; (2) line end of breaker (2) load end of limiter

JG IC Rating—200 kAIC at 600 Vac and 70 kAIC at 690 Vac

Ampere
Rating
Magnetic
Range
UL Listed, IEC Rated
Breaker With Line Side
Mounted Current Limiter (1)
UL Listed, IEC Rated
Breaker With Load Side
Mounted Current Limiter (2)
IEC Rated Breaker
With Line Side Mounted
Current Limiter (1)
IEC Rated Breaker
With Load Side Mounted
Current Limiter (2)
Fixed Thermal, Adjustable Magnetic Adjustable Thermal, Adjustable Magnetic
70 350—700 JGH3070FAGQ01 JGH3070FAGQ02
90 450—900 JGH3090FAGQ01 JGH3090FAGQ02
100 500—1000 JGH3100FAGQ01 JGH3100FAGQ02 JGH3100AAGQ01 JGH3100AAGQ02
125 625—1250 JGH3125FAGQ01 JGH3125FAGQ02 JGH3125AAGQ01 JGH3125AAGQ02
150 750—1550 JGH3150FAGQ01 JGH3150FAGQ02
160 800—1600 JGH3160AAGQ01 JGH3160AAGQ02
175 875—1750 JGH3175FAGQ01 JGH3175FAGQ02
200 1000—2000 JGH3200FAGQ01 JGH3200FAGQ02 JGH3200AAGQ01 JGH3200AAGQ02
225 1125—2250 JGH3225FAGQ01 JGH3225FAGQ02
Electronic Trip LS
250 JGH325033GQ01 JGH325033GQ02
Electronic Trip LSI
250 JGH325032GQ01 JGH325032GQ02
Electronic Trip LSG
250 JGH325035GQ01 JGH325035GQ02
Electronic Trip LSIG
250 JGH325036GQ01 JGH325036GQ02

Series G HMCP

Ampere
Rating
Motor Circuit Protector with
Line Side Mounted Current Limiter
Breaker with Load Side
Mounted Current Limiter
250 HMCPJ250D5LQ01 HMCPJ250D5LQ02
250 HMCPJ250F5LQ01 HMCPJ250F5LQ02
250 HMCPJ250G5LQ01 HMCPJ250G5LQ02
250 HMCPJ250J5LQ01 HMCPJ250J5LQ02
250 HMCPJ250K5LQ01 HMCPJ250K5LQ02
250 HMCPJ250L5LQ01 HMCPJ250L5LQ02

Line and Load Terminals

Maximum
Breaker
Amperes
Terminal
Body
Material
Wire Type Metric Wire
Range mm 2
AWG Wire
Range/ Number
of Conductors
Part
Number
Standard Pressure Type Terminals
250 Aluminum Cu/Al 10–185 #8–350 (1) TA250FJ (3)

NOTES:
(1) Two interphase barriers provided, mounted on line end of limiter, catalog number FJIPBK.
(2) Four interphase barriers provided, (2) line end of breaker, (2) load end of limiter.
(3) Line and load terminals included with products listed above.