Moeller PKZM1-1 |
PKZM1-1 PKZM1-1.6 shown |
Setting Range of Adjustable Thermal Trips | Response Current of Magnetic Trips | General Use 600 V - 25 A 1 Phase at: 230 | Max HP 3 Phase at: 460 V |
0.6 - 1.0 | 12 | In this range select in accordance with motor nameplates full load current. | 1/2 |
The PKZM1 is a 3 phase thermal magnetic motor protective device incorporating bimetal trips for motor overload protection and magnetic trips to de-energize the motor circuit in case of a short circuit. It is UL Listed and CSA certified as a HIP rated manual motor controller which provides motor running overload protection. In addition, the PKZM1 is UL listed and CSA certified for group applications as per NEC 450-53(c) and CEC part 1, Rule 28-206. This means that a group of motors, each protected and controlled by a PKZM1, can be combined under a single branch circuit short circuit and ground fault protective device the maximum rating of which is marked on each PKZM1 manual motor protector. |
© 2016 KMParts.com, Inc. All rights reserved.