The XTPR001BC1 is a 3 phase thermal magnetic motor
protective device incorporating adjustable bimetal trips
for motor overload protection and magnetic trips for
branch circuit overcurrent protection. It can be used as
a stand-alone combination controller or in group
applications to fulfill important branch circuit
functions per the NEC and CEC:
Self-protected combination controller
The XTPR001BC1 is a UL listed, CSA certified Type E
manual self-protected combination controller. Per the
intent of the CEC and Article 430 of the NEC,
self-protected combination controllers fulfill the
functions of short-circuit protection, disconnect,
controller and overload protection in a single unit when
used within their ratings. This eliminates the need to
provide fuses or circuit breakers for short-circuit
protection and avoids the restrictions stipulated by the
CEC/NEC for motor controllers used in group
installations. They can also be combined with regular
magnetic contactors to provide the performance
capabilities of conventional combination controllers
with remote operation. The XTPR001BC1 is suitable
as a Type E starter for grounded Wye power systems when
the system voltage exceeds 240V.
Group installation ratings
For non-Wye power systems exceeding 240V, theXTPR001BC1
devices are also listed and marked “Suitable for group
installations”, per NEC 430.53 and CEC part 1, rule
28-206. This eliminates the need for individual motor
branch circuit protective devices for each motor and
reduces the cost and space requirements of industrial
control panels and assemblies.
|