Description | Old Moeller Part Number |
New Eaton Part Number |
---|---|---|
Motor-protective circuit-breaker PKE, Coordination type "1" and "2" |
PKE12 | XTPE012BCSNL |
PKE12 Technical Data |
|||
General | |||
---|---|---|---|
Standards | IEC/EN 60947, VDE 0660 | ||
Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
||
Ambient temperature | ϑ Storage |
°C | -40 - +80 |
Open | °C | -25 - +55 | |
Enclosed | °C | -25 - +40 | |
Mounting position | |||
Direction of incoming supply | as required | ||
Degree of protection | Device | IP20 | |
Terminations | IP00 | ||
Busbar tag shroud to EN 50274 | Finger- and back-of-hand proof | ||
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 |
g | 25 | |
Altitude | m | Max. 2000 | |
Terminal capacity screw terminals | mm2 | ||
Solid | mm2 | 1 x (1 - 6) 2 x (1 - 6) |
|
Flexible with ferrule to DIN 46228 | mm2 | 1 x (1 - 6) 2 x (1 - 6) |
|
Solid or stranded | AWG | 14 - 10 | |
Specified tightening torque for terminal screws | Main cable |
Nm | 1.7 |
Control circuit cables |
Nm | 1 | |
Main conducting paths | |||
Rated impulse withstand voltage |
Uimp | V AC | 6000 |
Overvoltage category/pollution degree |
III/3 | ||
Rated operational voltage | Ue | V AC | 690 |
Rated uninterrupted current = rated operational current |
Iu = Ie | A | 12 |
Rated frequency | f | Hz | 40 - 60 |
Current heat loss (3 pole at operating temperature) |
W | 3.5 (with PKE-XTU(A)-12) 0.5 (with PKE-XTU(A)-4) 0.4 (with PKE-XTU(A)-1,2) |
|
Lifespan, mechanical | Operations | x 106 | 0.05 |
Lifespan, electrical (AC-3 at 400 V) |
Operations | x 106 | 0.05 |
Maximum operating frequency |
Ops./h | ||
Max. operating frequency | Ops/h | 60 | |
Other technical data (sheet catalogue) | Switching capacity | ||
Motor switching capacity | kArms | ||
AC-3 (up to 690 V) | A | 12 | |
Trip blocks | |||
Temperature compensation | °C | -5 - +40 (to IEC/EN 60947, VDE 0660) -25 - +55 (operating range) |
|
Temperature compensation residual error for T > 40 °C |
± 55 (Arbeitsbereich) | ||
Setting range of overload releases |
0.25 - 1 x Iu | ||
Fixed short-circuit release | Basic device 15.5 x Iu | ||
Short-circuit release tolerance |
± 20% | ||
Phase-failure sensitivity | yes | ||
Data for design verification according to IEC/EN 61439 | |||
Technical data for design verification | |||
Rated operational current for specified heat dissipation | In | A | 12 |
Heat dissipation capacity | Pdiss | W | 0 |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts |
|||
10.2.2 Corrosion resistance | Meets the product standard's requirements. |
||
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements. |
||
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements. |
||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard's requirements. |
||
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements. |
||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
||
10.2.7 Inscriptions | Meets the product standard's requirements. |
||
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
||
10.4 Clearances and creepage distances |
Meets the product standard's requirements. | ||
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated. |
||
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
||
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. | ||
10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. | ||
10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
||
10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
||
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
||
Technical data ETIM 5.0 | |||
Low-voltage industrial components (EG000017) / Motor protective circuit-breaker (EC000074) |
|||
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker motor protection (ecl@ss8-27-37-04-01 [AGZ529012]) |
|||
Setting range overload protector | A | 0 - 0 | |
Adjustment range undelayed short-circuit release |
A | 0 - 0 | |
Phase failure sensitive | No | ||
Switch off technique | Electronic | ||
Rated operating voltage | V | 690 - 690 | |
Rated permanent current Iu | A | 12 | |
Rated operation power at AC-3, 230 V | kW | 0 | |
Rated operation power at AC-3, 400 V | kW | 0 | |
Connection type main current circuit | Screw connection | ||
Device construction | Built-in device fixed built-in technique |
||
With integrated auxiliary switch | No | ||
With integrated under voltage release | No | ||
Number of poles | 3 | ||
Rated short-circuit breaking capacity lcu at 400 V, AC |
kA | 0 | |
Degree of protection (IP) | IP20 | ||
Approvals | |||
Product Standards | UL508; CSA-C22.2 No.14-10;IEC60947-4-1; CE marking |
||
UL File No. | E36332 | ||
UL Category Control No. | NLRV | ||
CSA File No. | 165628 | ||
CSA Class No. | 3211-05 | ||
North America Certification | UL listed, CSA certified |
||