Electronic release 4-Pole Systems, Cable, Selectivity and Generator Protection Terminals Standard, terminal screws as accessories |
||||||
| European | ||||||
|
Rated current = rated
uninterrupted current In = Iu |
Neutral Conductor |
Setting range
Overload releases |
Short-circuit releases | |||
| Non Delayed | Delayed | |||||
| NZMN4-4-VE800 | 800 | 400 - 800 | 400 - 800 | 1600 - 9600 | 800 - 8000 | |
| NZMN4-4-VE800/500 | 250 - 500 | |||||
| NZMN4-4-VE800/0 | -- | |||||
| NZMN4-4-VE1000 | 1000 | 500 - 1000 | 500 - 1000 | 2000 - 12000 | 1000 - 10000 | |
| NZMN4-4-VE1000/630 | 315 - 630 | |||||
| NZMN4-4-VE1000/0 | -- | |||||
| NZMN4-4-VE1250 | 1250 | 630 - 1250 | 630 - 1250 | 2500 - 15000 | 1250 -1250 | |
| NZMN4-4-VE1250/800 | 400 - 800 | |||||
| NZMN4-4-VE1250/0 | -- | |||||
| NZMN4-4-VE1600 | 1600 | 800 - 1600 | 800 - 1600 | 3200 -19200 | 1600 - 16000 | |
| NZMN4-4-VE1600/1000 | 500 - 1000 | |||||
| NZMN4-4-VE1600/0 | -- | |||||